Desa FA-60BA, FA-10BA, FAS-10BB Troubleshooting, Observed Problem Possible Cause Remedy

Page 14

NATURAL GAS HEATER

TROUBLESHOOTING

Note: For additional help, visit DESA International’s technical service web site at www.desatech.com.

Note: All troubleshooting items are listed in order of operation.

WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.

CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/ pilot unit.

 

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

 

When ignitor button is pressed, there is no

1.

Ignitor electrode positioned wrong

1.

Replace ignitor

 

spark at ODS/pilot

2.

Ignitor electrode broken

2.

Replace ignitor

 

 

3.

Ignitor electrode not connected to igni-

3.

Reconnect ignitor cable

 

 

 

tor cable

 

 

 

 

4.

Ignitor cable pinched or wet

4.

Free ignitor cable if pinched by any

 

 

 

 

 

metal or tubing. Keep ignitor cable dry

 

 

5.

Broken ignitor cable

5.

Replace ignitor cable

 

 

6.

Bad Piezo ignitor

6.

Replace control valve (ignitor is part of

 

 

 

 

 

control valve)

 

 

 

 

 

 

 

When ignitor button is pressed, there is

1.

Gas supply turned off or equipment

1.

Turn on gas supply or open equipment

 

spark at ODS/pilot but no ignition

 

shutoff valve closed

 

shutoff valve

 

 

2.

Control knob not in PILOT position

2.

Turn control knob to PILOT position

 

 

3.

Control knob not pressed in while in

3.

Press in control knob while in PILOT

 

 

 

PILOT position

 

position

 

 

4.

Air in gas lines when installed

4.

Continue holding down control knob.

 

 

 

 

 

Repeat igniting operation until air is

 

 

 

 

 

removed

 

 

5.

ODS/pilot is clogged

5.

Clean ODS/pilot (see Cleaning and

 

 

 

 

 

Maintenance, page 13) or replace ODS/

 

 

 

 

 

pilot assembly

 

 

6.

Gas regulator setting is not correct

6.

Replace gas regulator

 

 

 

 

 

 

 

ODS/pilot lights but flame goes out when

1.

Control knob not fully pressed in

1.

Press in control knob fully

 

control knob is released

2.

Control knob not pressed in long enough

2.

After ODS/pilot lights, keep control

 

 

 

 

 

knob pressed in 30 seconds

 

 

3.

Equipment shutoff valve not fully open

3.

Fully open equipment shutoff valve

 

 

4.

Thermocouple connection loose at con-

4.

Hand tighten until snug, then tighten 1/4

 

 

 

trol valve

 

turn more

 

 

5.

Pilot flame not touching thermocouple,

5.

A) Contact local natural gas company

 

 

 

which allows thermocouple to cool,

 

 

 

 

 

causing pilot flame to go out. This prob-

 

B) Clean ODS/pilot (see Cleaning and

 

 

 

lem could be caused by one or both of

 

Maintenance, page 13) or replace ODS/

 

 

 

the following:

 

pilot assembly

 

 

 

A) Low gas pressure

 

 

 

 

 

B) Dirty or partially clogged ODS/pilot

 

 

 

 

6.

Thermocouple damaged

6.

Replace thermocouple

 

 

7.

Control valve damaged

7.

Replace control valve

www.desatech.com

14

105564

Image 14
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualFAS-10BB Safety Information Natural GAS HeaterLocal Codes Product FeaturesProduct Identification UnpackingUnusually Tight Construction Fresh AIR for Combustion and VentilationProviding Adequate Ventilation Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space Fresh AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installation Methods For Attaching Mounting Bracket To Wall Installing Bottom Mounting ScrewsRemoving Front Panel Of Heater Marking Screw LocationsConnecting to GAS Supply Installing Bottom Mounting ScrewChecking GAS Connections Pressure Testing Gas Supply Piping SystemPressure Testing Heater Gas Connections Lighting Instructions Manual Lighting ProcedureOperating Heater To Turn OFF GAS To ApplianceFor Your Safety Read Before Lighting Thermostat Control OperationCleaning and Maintenance Inspecting BurnerTroubleshooting Observed Problem Possible Cause RemedyMaintenance, Gas leak. See Warning statement at Service Hints SpecificationsTechnical Service Service PublicationsParts Under Warranty AccessoryReplacement Parts Parts not Under WarrantyTarantin Tank Co Parts CentralsBaltimore Electric Washer Equipment Co Dayton Hardware Heater & Fireplace Store Cans Unlimited, IncFA-10BA Illustrated Parts ListODS Pilot Assembly KEY FA-10BA Description QTY FA-60BA KEY FA-60BA Description QTY FAS-10BB KEY FAS-10BA Description QTY Warranty Information