Bryant manual 574B Corner Weights, Selection Procedure with Example, Corner #

Page 12

574B CORNER WEIGHTS

12

y

4x 3

CORNER #

024

030

036

042

048

060

 

 

 

 

 

 

 

1

70

 

78

 

92

100

 

 

 

 

 

 

 

2

54

 

60

 

72

78

 

 

 

 

 

 

 

3

84

 

94

 

111

120

 

 

 

 

 

 

 

4

141

 

156

 

188

201

 

 

 

 

 

 

 

TOTAL WEIGHT

350

 

388

 

463

499

 

 

 

 

 

 

 

SELECTION PROCEDURE (WITH EXAMPLE)

I DETERMINE COOLING AND HEATING REQUIREMENTS

AT DESIGN CONDITIONS:

 

Given:

 

Required Cooling Capacity (TC)

34,500 Btuh

Sensible Heat Capacity (SHC)

26,000 Btuh

Required Heating Capacity

60,000 Btuh

Condenser Entering Air Temperature

95°F

Indoor-Air Temperature

80°F edb 67°F ewb

Evaporator Air Quantity

1200 CFM

External Static Pressure

0.2 in. wg

Electrical Characteristics

230-1-60

IISELECT UNIT BASED ON REQUIRED COOLING CAPACITY.

Enter Net Cooling Capacities table at condenser entering temperature of 95 F. Unit 036 at 1225 cfm and 67 F ewb (entering wet bulb) will provide a total capacity of 36,500 Btuh and a SHC of 27,600 Btuh. Calculate SHC correction, if required, using Note 4 under Cooling Capacities tables.

IIISELECT HEATING CAPACITY OF UNIT TO PROVIDE DESIGN CONDITION REQUIREMENT.

In the Heating Capacities and Efficiencies table on page 4, note that the unit 036090 will provide 70,000 Btuh with an input of 90,000 Btuh.

IV DETERMINE FAN SPEED AND POWER REQUIRE- MENTS AT DESIGN CONDITIONS.

Before entering the air delivery tables, calculate the total static pressure required. From the given example, the Wet Coil Pressure Drop Table, and the Filter Pressure Drop table on page 16, find at 1200 cfm:

Wet Coil Pressure Drop

0.032 in. ws

External Static Pressure

 

0.2 in. wg

Filter Pressure Drop

 

0.13 in. wg

Total Static Pressure

 

 

0.362 in. wg

 

Enter the table for Dry Coil Air Delivery — Horizontal and Downflow Discharge. At 0.362 ESP (external static pressure), the fan will deliver 1235 cfm with the NOM Speed pin selected.

VSELECT UNIT THAT CORRESPONDS TO POWER SOURCE AVAILABLE.

The Electrical Data table shows that the unit is designed to operate at 208/230-1-60.

—12—

Image 12
Contents FEATURES/BENEFITS Unit 574BEfficient Operation DURABLE, Dependable ComponentsHigh and LOW Pressure Switches provide added reli Model Number NomenclatureTable of Contents ARI* Capacities Cooling Capacities and EfficienciesARI* Capacities Heating Capacities and EfficienciesOutdoor Sound Octave Band Data Decibels LwA Range FPhysical Data Unit Size 574BPhysical Data Options and Accessories Factory-installed optionsFilter Rack Manual Outside Air Damper Base Unit Dimensions 574B024-036 Electrical Unit Weight Unit Height Center of Gravity Characteristics Base Unit Dimensions 574B042-060 Required Clearance for Operation and ServicingRequired Clearance to Combustible Matl NEC. Required ClearancesAccessory Dimensions Roof Curb DimensionsSide View Unit Size ODS Order Number574B Corner Weights Selection Procedure with ExampleSelect Unit That Corresponds to Power Source Available II Select Unit Based on Required Cooling Capacity574B024 Cooling Performance Table SHC574B030 Cooling Performance Table Performance Data Cooling Capacities574B036 Cooling Performance Table 574B042 Cooling Performance Table574B048 Cooling Performance Table 574B060 Cooling Performance TableSHC ECMFilter Pressure Drop In. wg Filter Size CFM574B Cooling DRY Coil ECM AIRFLOW-SMALL Cabinet 574B Cooling DRY Coil ECM AIRFLOW-LARGE Cabinet574B Heating ECM AIRFLOW-SMALL Cabinet 574B Heating ECM AIRFLOW-LARGE Cabinet574B ECM AIR Flow VS. Temperature Rise Chart Performance DataHigh Altitude Compensation 574B ECM WET Coil Pressure DropTypical Piping and Wiring Application Data Electrical Data 574B Standard Electrical Data Typical Wiring SCHEMATIC-208/230-1-60 Shown Typical Wiring SCHEMATIC-208/230-3-60 Shown Controls Operating SequencePage Page Guide Specifications Part 1 GeneralPart 2 Products Guide Specifications