Bryant manual 574B048 Cooling Performance Table, 574B060 Cooling Performance Table, Shc, Ecm

Page 15
—15—
t ldb = t edb

PERFORMANCE DATA (cont)

STANDARD INDOOR ECM MOTOR

COOLING CAPACITIES (cont)

574B048 COOLING PERFORMANCE TABLE

 

 

 

 

 

 

 

 

Evaporator Air—CFM/BF

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1260/0.06

 

 

1400/0.06

 

 

 

 

 

1600/0.08

 

 

 

Outdoor Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering

 

 

 

 

 

Evaporator Air — Ewb (F)

 

 

 

 

 

 

 

 

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

63*

67

72

62

 

 

63*

 

67

 

72

 

62

 

63*

 

67

 

72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

45.0

45.8

49.6

54.7

46.7

 

 

47.3

 

51.2

 

56.3

 

48.1

 

48.7

 

52.5

 

57.8

 

75

 

SHC

39.3

32.0

33.4

27.2

42.6

 

 

34.3

 

35.8

 

28.9

 

45.8

 

36.8

 

38.4

 

30.6

 

 

 

kW

3.4

3.4

3.4

3.4

3.4

 

 

3.4

 

3.4

 

3.5

 

3.4

 

3.4

 

3.4

 

3.5

 

 

 

TC

42.8

43.6

47.2

52.1

44.3

 

 

44.9

 

48.6

 

53.5

 

45.6

 

46.1

 

49.9

 

54.8

 

85

 

SHC

38.2

30.9

32.3

26.2

41.3

 

 

33.2

 

34.7

 

27.7

 

44.3

 

35.5

 

37.3

 

29.4

 

 

 

kW

3.7

3.7

3.8

3.8

3.7

 

 

3.7

 

3.8

 

3.8

 

3.8

 

3.8

 

3.8

 

3.8

 

 

 

TC

40.6

41.3

44.7

49.4

41.8

 

 

42.4

 

46.0

 

50.7

 

44.2

 

43.7

 

47.0

 

51.8

 

95

 

SHC

36.9

29.8

31.2

25.2

39.9

 

 

32.0

 

33.6

 

26.7

 

43.0

 

34.6

 

36.1

 

28.3

 

 

 

kW

4.1

4.1

4.2

4.2

4.1

 

 

4.1

 

4.2

 

4.2

 

4.2

 

4.1

 

4.2

 

4.2

 

 

 

TC

38.2

38.9

42.1

46.4

39.6

 

 

39.8

 

43.1

 

47.6

 

41.5

 

40.8

 

44.0

 

48.5

 

105

 

SHC

35.7

28.7

30.1

24.0

38.3

 

 

30.7

 

32.3

 

25.5

 

40.0

 

33.2

 

34.8

 

27.0

 

 

 

kW

4.6

4.6

4.6

4.6

4.6

 

 

4.6

 

4.6

 

4.7

 

4.6

 

4.6

 

4.6

 

4.7

 

 

 

TC

35.7

36.3

39.3

43.3

38.2

 

 

37.1

 

40.1

 

44.2

 

38.7

 

37.9

 

40.8

 

45.0

 

115

 

SHC

34.4

27.5

28.9

22.9

35.7

 

 

29.5

 

31.0

 

24.3

 

38.2

 

31.8

 

33.5

 

25.8

 

 

 

kW

5.0

5.0

5.1

5.1

5.1

 

 

5.0

 

5.1

 

5.1

 

5.1

 

5.1

 

5.1

 

5.1

 

 

 

TC

33.4

33.4

36.2

39.4

34.6

 

 

34.1

 

36.9

 

40.5

 

36.1

 

34.8

 

37.5

 

41.2

 

125

 

SHC

32.1

26.2

27.6

21.5

33.8

 

 

28.2

 

29.7

 

22.9

 

35.6

 

30.2

 

31.9

 

24.4

 

 

 

kW

5.6

5.6

5.6

5.7

5.6

 

 

5.6

 

5.6

 

5.6

 

5.6

 

5.6

 

5.6

 

5.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

574B060 COOLING PERFORMANCE TABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator Air — CFM/BF

 

 

 

 

 

 

 

 

 

Temp (F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1500/0.004

 

 

1750/0.007

 

 

 

 

 

2000/0.01

 

 

 

Outdoor Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering

 

 

 

 

Evaporator Air — Ewb (F)

 

 

 

 

 

 

 

 

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

62

63*

67

72

62

 

63*

 

67

 

72

 

62

 

63*

 

67

 

72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

57.2

58.2

62.4

68.1

58.8

 

59.7

 

64.0

 

69.8

 

60.0

 

60.8

 

64.9

 

70.8

 

75

 

SHC

49.4

47.9

41.6

33.8

53.6

 

51.8

 

44.5

 

35.4

 

57.6

 

55.4

 

47.1

 

36.8

 

 

 

kW

4.1

4.1

4.2

4.2

4.2

 

4.3

 

4.3

 

4.4

 

4.4

 

4.4

 

4.5

 

4.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

54.7

55.6

59.7

65.2

56.2

 

57.0

 

61.1

 

66.6

 

57.4

 

58.1

 

61.9

 

67.4

 

85

 

SHC

48.2

46.7

40.4

32.6

52.4

 

50.5

 

43.2

 

34.2

 

56.3

 

54.2

 

45.8

 

35.6

 

 

 

kW

4.5

4.5

4.6

4.7

4.7

 

4.7

 

4.8

 

4.9

 

4.8

 

4.9

 

5.0

 

5.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

52.2

53.0

56.9

62.0

53.5

 

54.3

 

58.0

 

63.2

 

55.0

 

55.3

 

58.7

 

64.1

 

95

 

SHC

47.0

45.4

39.2

31.4

51.1

 

49.2

 

41.9

 

32.9

 

55.0

 

52.9

 

44.5

 

34.4

 

 

 

kW

5.0

5.0

5.1

5.2

5.1

 

5.2

 

5.3

 

5.3

 

5.2

 

5.3

 

5.5

 

5.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

49.4

50.2

53.8

58.7

50.7

 

51.4

 

54.8

 

59.6

 

52.5

 

52.4

 

55.4

 

60.2

 

105

 

SHC

45.7

44.1

37.9

30.1

49.8

 

47.9

 

40.6

 

31.6

 

52.5

 

51.6

 

43.2

 

33.0

 

 

 

kW

5.5

5.6

5.6

5.7

5.7

 

5.7

 

5.8

 

5.9

 

5.8

 

5.8

 

6.0

 

6.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

46.5

47.2

50.5

55.0

48.1

 

48.3

 

51.3

 

56.8

 

49.7

 

49.7

 

51.8

 

57.0

 

115

 

SHC

44.3

42.7

36.4

28.7

48.1

 

46.6

 

39.2

 

30.6

 

49.7

 

49.7

 

41.8

 

31.7

 

 

 

kW

6.1

6.2

6.2

6.3

6.2

 

6.3

 

6.4

 

6.4

 

6.4

 

6.4

 

6.6

 

6.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC

43.3

43.9

46.7

52.2

45.2

 

45.1

 

47.4

 

52.5

 

46.4

 

46.4

 

47.9

 

52.2

 

125

 

SHC

42.8

41.2

34.9

27.8

45.2

 

45.1

 

37.6

 

28.9

 

46.4

 

46.4

 

40.2

 

29.7

 

 

 

kW

6.7

6.8

6.8

6.8

6.8

 

6.9

 

7.0

 

7.0

 

7.0

 

7.0

 

7.2

 

7.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

BF

Bypass Factor

Ewb

Entering Wet-Bulb

kW

— Total Unit Power Input

SHC

— Sensible Heat Capacity (1000 Btuh)

TC

— Cooling Capacity (1000 Btuh)

ECM

Electronic Computated Motor

*— TVA Conditions (75°F entering dry bulb)

NOTES:

1.Ratings are net; they account for the effects of the evaporator-fan motor power and heat.

2.Direct interpolation is permissible. Do not extrapolate.

3.The following formulas may be used:

sensible capacity (Btuh) 1.10 x cfm

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)

hlwb = hewb

total capacity (Btuh)

4.5 x cfm

 

Where: h ewb =

Enthalpy of air entering evaporator coil

4.The SHC is based on 80°F edb temperature of air entering evaporator coil. Below 80°F edb, subtract (Corr Factor x CFM) from SHC above 80°F edb, add (Corr Factor x CFM) to SHC Correction Factor = 1.10 x (1 – BF) x (edb – 80)

Image 15
Contents DURABLE, Dependable Components FEATURES/BENEFITSUnit 574B Efficient OperationModel Number Nomenclature High and LOW Pressure Switches provide added reliARI* Capacities Cooling Capacities and Efficiencies Table of ContentsRange F ARI* CapacitiesHeating Capacities and Efficiencies Outdoor Sound Octave Band Data Decibels LwAUnit Size 574B Physical DataPhysical Data Factory-installed options Options and AccessoriesFilter Rack Manual Outside Air Damper Base Unit Dimensions 574B024-036 Electrical Unit Weight Unit Height Center of GravityCharacteristics NEC. Required Clearances Base Unit Dimensions 574B042-060Required Clearance for Operation and Servicing Required Clearance to Combustible MatlUnit Size ODS Order Number Accessory DimensionsRoof Curb Dimensions Side ViewII Select Unit Based on Required Cooling Capacity 574B Corner WeightsSelection Procedure with Example Select Unit That Corresponds to Power Source Available574B024 Cooling Performance Table SHC574B030 Cooling Performance Table 574B042 Cooling Performance Table Performance DataCooling Capacities 574B036 Cooling Performance TableECM 574B048 Cooling Performance Table574B060 Cooling Performance Table SHCFilter Size CFM Filter Pressure Drop In. wg574B Heating ECM AIRFLOW-LARGE Cabinet 574B Cooling DRY Coil ECM AIRFLOW-SMALL Cabinet574B Cooling DRY Coil ECM AIRFLOW-LARGE Cabinet 574B Heating ECM AIRFLOW-SMALL Cabinet574B ECM WET Coil Pressure Drop 574B ECM AIR Flow VS. Temperature Rise ChartPerformance Data High Altitude CompensationTypical Piping and Wiring Application Data Electrical Data 574B Standard Electrical Data Typical Wiring SCHEMATIC-208/230-1-60 Shown Typical Wiring SCHEMATIC-208/230-3-60 Shown Operating Sequence ControlsPage Page Guide Specifications Part 1 GeneralPart 2 Products Guide Specifications

574B specifications

The Bryant 574B is a remarkable air conditioning unit renowned for its efficient cooling performance and advanced technology. Designed for both residential and light commercial applications, this model stands out in the market for its durability and energy efficiency.

One of the primary features of the Bryant 574B is its wide capacity range. This unit is designed to cater to various room sizes, allowing homeowners to select an appropriate model that best suits their cooling needs. The 574B series comes with efficient cooling capacities, ensuring that indoor spaces remain comfortable even during the hottest summer months.

In terms of technology, the Bryant 574B integrates advanced refrigeration systems coupled with environmentally conscious refrigerants. The unit utilizes R-410A refrigerant, which is known for its efficiency and energy conservation properties, making it a more environmentally friendly choice compared to older models that used R-22 refrigerant. This transitions not only help in achieving better energy ratings but also align with modern regulations concerning refrigerants.

Another notable characteristic of the Bryant 574B is its impressive Seasonal Energy Efficiency Ratio (SEER). A higher SEER rating translates to lower energy consumption, which is a significant advantage for homeowners looking to minimize their electricity bills. The 574B boasts a SEER rating that meets or exceeds the standards set by the Department of Energy, showcasing its commitment to energy efficiency.

Durability is also a hallmark of the Bryant 574B air conditioner. Its construction includes a robust cabinet designed to withstand harsh weather conditions, ensuring longevity and consistent performance. The unit is equipped with a protective coating to prevent rust and corrosion, further extending its lifespan.

Moreover, the Bryant 574B features easy installation and maintenance. The design allows for straightforward setup, which can significantly reduce installation time. Additionally, the unit comes with an accessible maintenance panel, making routine checks and servicing hassle-free.

In summary, the Bryant 574B is a high-performing air conditioning system characterized by its efficiency, environmentally friendly design, and durability. With its advanced technologies and user-friendly features, it is a reliable choice for those seeking comfort and savings in their cooling systems.