Field Controls S2000 Setting the Humidistat, Recommended Indoor, Dry Bulb

Page 7

RH

OD

%

 

 

T

RH

 

EMP

 

 

M

 

AU

ODE

 

T

 

Figure 14.

O

M

 

AN

 

 

Installation instructions for the 072000 model Humidistat are packaged with the 072000.

Your humidifier may include Model 062000 Humidistat. Installation instructions for the 062000 model are packaged with the 062000.

There are many ways to wire and control a humidifier. Refer to the wiring diagrams on pages 4 and 7.

10. SETTING THE HUMIDISTAT

It is recommended that humidistat settings of 30-45% not be exceeded. If condensation is noticed on windows during very cold outside temperatures, the humidistat setting should be lowered.

The maximum recommended relative humidity for your home depends upon many factors such as outdoor air temperature, type and placement of insulation, vapor barriers, effectiveness of weather stripping, type of windows and doors (including frames and jambs) and whether or not storm windows and doors are used. With all these variables it is nearly impossible to recommend a proper humidity setting. The best humidistat setting is one that you are most comfortable with. Also, as the outdoor temperature fluctuates, it may be necessary to adjust the humidity level of your system a few times during the heating season.

Refer to the "Relative Humidity Chart" as a starting point for your proper humidistat setting. Generally, in a tighter and better insulated house, the humidistat may be set higher than in a drafty, un-insulated house.

IMPORTANT: If the humidifier is installed in the return air plenum the humidistat must be located at least five (5) feet upstream from the humidifier. Fan should be operated in continuos mode when the humidistat is mounted in the return air plenum. Mounting the humidistat on an interior wall is always preferable to mounting on the return duct. But mounting the humidistat on an interior wall takes more time, material and labor than a return duct location. Sometimes it may be impossible to mount a humidistat on an interior wall and the return duct location is the only solution.

RELATIVE HUMIDITY CHART

Variable Speed WIRING DIAGRAM

FIG. 15

 

Variable Speed Heat & Cool System and

 

 

 

 

SteamHumidifier with 072000Humidistat

 

 

 

Humidifier with 072000 Humidistat

 

 

 

SteamVariable Sp ed Heat & Cool System and

 

 

Typical Thermostat

S2000 & S2020 Humidifier

 

Low Voltage Terminal Block

A

R W G Y C

G1 R G2 H

 

H

A

 

 

 

 

 

 

 

REMOVE

 

 

 

 

 

 

 

 

FACTORY

 

 

 

 

 

 

 

JUMPER

 

R W G Y C

 

 

 

 

Model APD or

Variable Speed Furnace

OD OD C

R

H

H

 

 

 

Equivalent

 

 

 

Outdoor

 

 

 

 

 

R

Y

C

072000 Humidistat

 

 

Temperature

 

 

 

 

 

Sensor

 

 

 

 

 

Hi-Efficiency

 

 

 

 

 

 

Condensing

 

 

 

 

 

 

 

Unit

 

 

 

 

 

 

Outside

Recommended Indoor

Dry Bulb

Relative Humidity

Temperature

Setting

0 Deg. F

15%

10 Deg. F

20%

20 Deg. F

25%

30 Deg. F

35%

35 Deg. F

40-45%

and up

 

The diagram above should be followed if it is required to operate the fan system at high speed during the humidify operation. Such a requirement may be necessary if condensation occurs inside the duct-work due to the lower velocities of a variable speed system

when only the fan is running. The “Y” circuit must be wired exactly as shown to achieve the correct operation. This wiring configuration may result in the loss of the “enhanced” latent effect operations of your variable speed HVAC system. If you do not want this to happen, you should consider installing a different type of whole house humidifier that does not require dominance over the HVAC fan and full CFM capacities while operating. Variations onthisthisdiagramdiagramareareavailableavailable. .ContactContactEWCFieldControlsControlsTechnicalTechnicalSupportSupportHotlineHotline. .

Copyright © 2011 Field

Controls All Rights Reserved.

7

Image 7 Contents
Options and additional parts recommended Parts included in the Steam Humidifier package areMounting Template Insulate Water Tank ReservoirDrillholesand CUT Openings Correct Hose Incorrect Installingand Wiring the HumidistatField Wiring Overflow & Drain Lines Required Criteria00.3 OHM Control Wiring Solutions for Various Hvac SystemsCopyright Field Controls All Rights Reserved NTR WER Humidifier W/ ScoopRecommended Indoor Setting the HumidistatDry Bulb Service LED Indicators Service Indicators MAINTENANCE/SPRING ShutdownAllow the unit to dry thoroughly before using Service Indicators Olt Service and Replacement PartsOverflow Tube Technical Bulletin Application Note AN SC100APPLICATION 2009 Note AN Copyright 2011 Field Controls All Rights Reserved