Johnson Controls IFC-640 manual System Capacity, Specifications, Temperature and Humidity Ranges

Page 9

SYSTEM SPECIFICATIONS

System Capacity

 

• Intelligent Signaling Line Circuits

1 expandable to 2

Intelligent detectors

159 per loop

Addressable monitor/control modules

159 per loop

• Programmable internal hardware and output circuits

 

(4 standard)

68

Programmable software zones

99

Special programming zones

14

• LCD annunciators per CPU-640/-640E and JNCA

 

(observe power)

32

• ACS annunciators per CPU-640/-640E

 

 

.........................................................32 address x 64 points

• ACS annunciators per JNCA

 

 

................................................32 address x 64 or 96 points

NOTE: The JNCA supports up to 96 annunciator address points

per ACM-24/48.

 

Specifications

Primary input power, JCPU-640 board: 120 VAC, 50/60 Hz,

3.0 amps. JCPU-640E board: 220/240 VAC, 50/60 Hz, 1.5 Amps.

Total output 24 V power: 6.0 A in alarm.

NOTE: The power supply has a total of 6.0 Amps of available power. This is shared by all internal modules.

Standard notification circuits (4): 2.5 A each.

Four-wire detector power: 1.25 A.

Non-resettable regulated power outputs: 1.25 A each.

Battery charger range: 12 AH – 55 AH. Use separate cabi- net for batteries over 25 AH.

Optional high-capacity (25 – 120 AH) battery charger: CHG-120 (see CHG-120 data sheet, DN-6040).

Float rate: 27.6 V.

Temperature and Humidity Ranges

This system meets NFPA requirements for operation at 0 – 49ºC/32 – 120ºF and at a relative humidity 93% ± 2% RH

(noncondensing) at 32ºC ± 2ºC (90ºF ± 3ºF). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme tempera- ture ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27ºC/60 – 80ºF.

Agency Listings and Approvals

The listings and approvals below apply to the basic IFC-640 control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Con- sult factory for latest listing status.

UL: S1570

ULC: ML118

FM APPROVED Exceptions – JCPU-640E, Proprietary service

CSFM: 7165-0554:143, 7170-0554:142

MEA: 317-01-E Vol. II

City of Chicago

Standards

The IFC-640 complies with the following UL Standards and NFPA 72 Fire Alarm Systems requirements :

UL 864 (Fire)

UL 1076 (Burglary)

LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervisory).

AUXILIARY (Automatic, Manual and Waterflow) (requires 4XTMF).

REMOTE STATION (Automatic, Manual and Waterflow) (requires 4XTMF).

PROPRIETARY (Automatic, Manual and Waterflow). Not applicable for FM.

EMERGENCY VOICE/ALARM.

AWACS™, HARSH™, NIS™, Notifier Integrated Systems™, and NO- TI•FIRE•NET™ are all trademarks; and FlashScan®, NION®, NOTIFIER®, ONYX®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc.

©2006 by Johnson Controls Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

Made in the U.S. A.

For more information, contact Johnson Controls Field Support Center.

507 East Michigan Street, Milwaukee, WI 53202 www.johnsoncontrols.com

Page 9 of 9 — JCI-6856:A • 12/01/06

Image 9
Contents Jnca 640-CHARACTER Display Features FeaturesFlashscan Intelligent Features GeneralSample SystemOptions Awacs Advanced Warning Address- able Combustion Sensing FlashScan Exclusive World-Leading Detector Pro- tocolField Programming Options Above Keypad program editing Below Autoprogram functionJCPU-640 shown with KDM-2 Display Network DiagramKDM-2 Controls and Indicators Placement of Equipment Chassis and CabinetConfiguration Guidelines Membrane Switch Controls Acknowledge/ScrollOther Option Modules System ModulesCompatible DEVICES, EIA-485 Ports Compatible DEVICES, EIA-232 PortsCompatible Intelligent Devices Other Options8 of 9 JCI-6856A 12/01/06 Temperature and Humidity Ranges SpecificationsSystem Capacity Agency Listings and Approvals

IFC-640 specifications

Johnson Controls IFC-640 is a pioneering fire alarm control panel that integrates advanced technologies to ensure safety and protection in commercial and industrial applications. As a part of the Johnson Controls extensive portfolio, the IFC-640 offers detailed monitoring and control capabilities, making it a reliable choice for fire management systems.

One of the standout features of the IFC-640 is its robust addressable technology. This system allows for precise identification of each alarm device, enabling quick location tracking during emergencies. The incorporation of intelligent algorithms enhances the panel's ability to distinguish between actual fire events and false alarms, thereby improving overall response efficiency.

Another significant characteristic of the IFC-640 is its user-friendly interface. The panel is equipped with a color LCD display that provides real-time status updates on the system’s operation. This visual clarity ensures that operators can quickly comprehend alerts and other vital information. The intuitive navigation allows users to manage settings and view system events with ease, minimizing the training required for new personnel.

The IFC-640 also boasts a modular architecture, allowing for seamless scalability. This feature enables the system to adapt to varying building sizes and complexities without needing extensive upgrades. Integration capabilities with third-party systems facilitate compatibility with existing infrastructure, making the IFC-640 a versatile choice for a diverse range of environments.

Network capabilities are enhanced with the panel's ability to connect monitoring stations and multiple units in a single system. This networking function allows for centralized management of multiple installations, improving overall safety management across large campuses or facilities.

Safety and reliability are further reinforced by the IFC-640’s built-in redundancy features. This ensures continuous operation even in the event of a power outage, providing peace of mind to facility managers and stakeholders.

In summary, the Johnson Controls IFC-640 fire alarm control panel exemplifies cutting-edge engineering with its addressable technology, user-friendly interface, modular design, and robust networking capabilities. With these features, it stands as an effective solution for safeguarding lives and property against fire hazards.