1.Recommended Locations for Smoke Alarms

Put smoke alarms at both ends of a hallway or large room if the hall- way or room is more than 30 ft (9.1 m) long. For large rooms, one smoke alarm is recommended for every 500 square feet of floor space.

In homes that are not well insulated, extreme heat or cold can be transferred from the outside to the inside through poorly insulated walls and roof. This may create a thermal barrier which can prevent the smoke from reaching an alarm mounted on the ceiling. If you are not sure about the insulation in your home, or if you notice that the outer walls and ceiling are either hot or cold, install the alarm on an inside wall. In such homes, install the smoke alarm with the top edge of the alarm at a minimum of 4” (10 cm) and a maximum of 12” (30.5 cm) below the ceiling (see figure 1).

Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 3ft (0.9m) of the highest point (measured horizontally). NFPA 72 states: “Smoke alarms in rooms with ceiling slopes greater than 1 ft in 8 ft (.3m in 2.4 m) horizontally shall be located on the high side of the room.” NFPA 72 states: “A row of detectors shall be spaced and located within 3 ft (0.9m) of the peak of the ceiling measured horizontally” (see figure 2).

Install Smoke Alarms on tray-shaped ceilings (coffered ceilings) on the highest portion of the ceiling or on the sloped portion of the ceiling within 12” (305mm) vertically down from the highest point (see figure 4).

Mobile Home Installation

Modern mobile homes have been designed and built to be energy effi- cient. Install smoke alarms as recommended above (refer to RECOM- MENDED LOCATIONS and Figures 1 and 2). In older mobile homes that are not well insulated compared to present standards, extreme heat or cold can be transferred from the outside to the inside through poorly insulated walls and roof. This may create a thermal barrier which can prevent the smoke from reaching an alarm mounted on the ceiling. In such units, install the smoke alarm on an inside wall with the top edge of the alarm at a minimum of 4” (10cm) and a maximum of 12” (30.5cm) below the ceiling (see figure 1).

If you are not sure about the insulation in your mobile home, or if you notice that the outer walls and ceiling are either hot or cold, install the alarm on an inside wall. For minimum protection, install at least one alarm close to the sleeping rooms. For additional protection, see SINGLE FLOOR PLAN in figure 2.

2.Locations To Avoid

In the garage. Products of combustion are present when you start your automobile.

Less than 4” (10cm) from the peak of an “A” frame type ceiling.

In an area where the temperature may fall below 40ºF or rise above 100ºF, such as garages and unfinished attics; this should also include electrical boxes exposed to these environments.

In dusty areas. Dust particles may cause nuisance alarm or failure to alarm.

In very humid areas. Moisture or steam can cause nuisance alarms.

In insect-infested areas.

Smoke alarms should not be installed within 3 ft (.9m) of the following: the door to a kitchen, the door to a bathroom containing a tub or shower, forced air supply ducts used for heating or cooling, ceiling or whole house ventilating fans, or other high air flow areas.

Kitchens. Normal cooking may cause nuisance alarms. If a kitchen alarm is desired, it should have an alarm silence feature or be a photo- electric type.

Near fluorescent lights. Electronic “noise” may cause nuisance alarms.

Smoke alarms are not to be used with detector guards unless the combination (alarm and guard) has been evaluated and found suitable for that purpose.

WARNING: TEST YOUR SMOKE ALARM OPERATION AFTER RV OR MOBILE HOME VEHICLE HAS BEEN IN STORAGE, BEFORE EACH TRIP AND AT LEAST ONCE A WEEK DURING USE.

Image 4
Contents Smoke Alarm Model i9030, i9040, i9040RV i9050, i9060, i9060RVWelcome Important Warning StatementsContents of This User’s Guide Mobile Home Installation Locations To AvoidInstallation Instructions Mounting InstructionsOperation and Testing Nuisance AlarmsMaintenance Test the Alarm Weekly to Ensure Proper OperationLimitations of Smoke Alarms Safety LightGood Safety Habits NRC InformationNfpa Required Protection Develop and Practice a Plan of EscapeService and Warranty Limited WarrantyQuestions or for More Information
Related manuals
Manual 2 pages 9.56 Kb

L2, PI9000, I9040RV, I9050, I9060RV specifications

Kidde smoke alarms, including the I9060RV, I9040, I9050, I9040RV, and PI9000, are designed to provide robust safety solutions for residential and commercial spaces. Each model incorporates advanced technologies and features to ensure timely detection of smoke and fire hazards, enhancing the safety of occupants.

The Kidde I9060RV is a hardwired smoke alarm with a battery backup, ensuring it remains operational even during power outages. Its residential safety features include an ionic sensing chamber that is highly effective in detecting fast-flaming fires, while the battery backup provides added reliability. The I9040 is another reliable choice with a battery-operated design, ideal for homes without hardwiring. Its photoelectric sensing technology offers enhanced detection of smoldering fires, minimizing false alarms caused by cooking fumes.

The I9050 model continues this trend, featuring both ionization and photoelectric sensing technologies for comprehensive smoke detection. This dual-sensor capability allows it to respond quickly to a wider range of fire types, making it a versatile option for different environments. The I9040RV, tailored specifically for RV and mobile living spaces, maintains reliability while being lightweight and easy to install. It features a battery-operated design that is suitable for the unique electrical requirements of recreational vehicles.

The PI9000 model introduces another important safety feature: a voice alarm system that provides clear alerts to occupants, distinguishing between smoke and carbon monoxide, if combined with Kidde carbon monoxide alarms. This feature increases the effectiveness of emergency responses, as occupants can quickly identify the nature of the threat.

All these alarms come equipped with battery status indicators to ensure operational readiness, and their sleek, compact designs allow for easy installation and integration into any decor. Kidde smoke alarms are also built with tamper-resistant features, preventing unauthorized removal, ensuring that these essential safety devices remain in place.

With a focus on user-friendly designs, enhanced detection technologies, and comprehensive safety features, Kidde smoke alarms stand out as reliable choices for anyone looking to protect their home or workplace from unpredictable fire hazards.