IBM UPS1481 UNIT user manual Product Features

Page 8

OnLine Power

systems, from electrical interference. The Fire Alarm Back-up UPS1481 protects these systems from power problems associated with poor quality AC power including complete power Outages. Electrical disturbances can come from practically anywhere: from the incoming power lines and even from within a building. Outside electrical disturbances include lightning strikes, utility switching, brown—outs, and accidents. Electrical disturbances from within a building can be caused by load cycling (elevators, HVAC systems), fault conditions, welders, and other electrically noisy equipment. Whether the electrical disturbances are generated outside or from within the facility, the following power problems will occur:

1-3 PRODUCT FEATURES

The following describes the major blocks within the Fire Alarm Back-up UPS1481. Please refer to Illustration. Block Diagram for additional information.

Bypass Static Switch — The SCR solid state switch bypasses the complete UPS and provides utility input directly to the load in case of problem with UPS. This switch also supplies input power to the load during the start up. It is connected on the primary side of the optional output isolation Transformer, when used. This switch maintains it’s status opposite of that of the output SCR solid state switch.

Output Static Switch — This SCR solid state switch connects the output of the inverter (UPS) to the load. It is connected on the primary side of the optional output isolation transformer, when used. This switch shuts—off in case of a problem or failure within the UPS and transfers the load directly to the utility input via bypass static switch. It maintains it’s status opposite to that of bypass switch.

Power Board with IGBTs — The Power board is bolted onto the IGBT blocks that are mounted on a heat sink. The complete heat sink assembly with IGBT and power board is replaceable as one part. This assembly processes ail the power, ie. input AC power converted to DC bus, battery power boosted to DC bus and finally DC bus power converted to output AC power using PWM technology for smooth AC Sinewave. The complete heat sink assembly is easily replaceable using only a screwdriver, in case of a catastrophic failure, if required. This board also has the housekeeping power supplies and driver circuits for IGBTs. This board also provides the landing place for all internal input, output, and DC cables as well as it monitors the input-output current for control and metering.

Control Board — The microprocessor with programmable logic controllers and on board memory is located on this board. It is mounted on the door and communicates, controls, and monitors the power board via a ribbon cable. This board also senses the input AC and sends the command to close/open the input contactor, bypass static switch and output static switch. This board also sends all the data to the LCD display panel located on the door. It also has modem, AS400, RS232, and RS485 output capabilities.

LCD Display Panel — This front panel provides all the metering data for input, output and battery; alarm data and UPS status for customer use in a constantly changing and updating, the 3 sets of the screens.

(6002-1646) REV.X8

2

Image 8
Contents Fire Alarm Back-up UPS1481 Unit OnLine Power Information Important Safety Instructions Table of Contents Revision History Operation Product Features OnLine Power OnLine Power Functional Block Diagram Customers Connections 120V IN/OUTPUT Unit 120V Output Unit Fire Alarm Back-up UPS1481 Sizing Options Installation Site Planning Specifications for KVA Unit Model Part Number Nomenclature Pre-Installation Remote Signaling Connections AS400 2 RS232 Connection Control Pcbd OnLine Power Operation Operation Turning On the Fire Alarm Back-up UPS1481 Turning off the Fire Alarm Back-up UPS1481 OnLine Power COMPONENT’S Location & List COMPONENT’S Table OnLine Power OnLine Power Appendix a Extended Battery RUN Chart Appendix B Optional Main Input & Main Output Breakers Input Circuit Breaker Appendix C LCD Display Menu & Troublshooting Guide Screen B The screen appears as below OnLine Power Appendix D Specification Power Rating KVA/KW OnLine Power OnLine Power Battery Cabinet B 2ND 4TH Level 1ST Level OnLine Power OnLine Power OnLine Power OnLine Power OnLine Power OnLine Power

UPS1481 UNIT specifications

The IBM UPS1481 is a robust uninterruptible power supply (UPS) designed to ensure the seamless operation of critical equipment in various environments, including data centers, telecommunications, and enterprise applications. This model is particularly noted for its reliability, efficiency, and advanced features, catering to the demands of modern IT infrastructures.

One of the main features of the UPS1481 is its high-capacity output, which can handle significant power loads. With an impressive power rating, the unit is equipped to support various devices, from servers to networking equipment, guaranteeing that essential operations remain uninterrupted during power outages or fluctuations. This capability is crucial for maintaining business continuity and minimizing potential downtime.

In terms of technology, the IBM UPS1481 integrates advanced power management systems that provide real-time monitoring and control. This functionality allows users to track power consumption, battery status, and overall system health through an intuitive interface. Additionally, the UPS includes features such as an automatic voltage regulator (AVR), which helps stabilize voltage levels, protecting connected equipment from surges, spikes, and drops that can cause damage or data loss.

The UPS1481 also comes with a modular design, allowing for scalability. Users can expand the capacity of the UPS to meet growing power demands without needing to replace the entire unit. This flexibility is beneficial for organizations undergoing rapid growth or technological upgrades.

Another important characteristic of the IBM UPS1481 is its energy efficiency. Designed to comply with various energy standards, the unit operates with minimal power loss, thereby reducing operational costs and contributing to a greener environment. By optimizing energy usage, organizations can enhance their sustainability initiatives while ensuring reliable power protection.

Furthermore, the UPS1481 offers a robust battery system that supports extended runtime options. Users can configure the UPS with additional battery packs to ensure that critical systems remain operational for extended periods during extensive outages.

In summary, the IBM UPS1481 UNIT stands out for its high capacity, advanced power management features, modular design, and energy efficiency. It is an ideal solution for businesses looking to safeguard their critical equipment and maintain operational integrity in the face of power disruptions.