IBM UPS1481 UNIT user manual Pre-Installation

Page 20

OnLine Power

2-2 Pre-Installation

The Fire Alarm Back-up UPS1481 is designed for indoor installations. All customer connections are brought through knockouts located on the top or side of the Fire Alarm Back-up UPS1481. The Fire Alarm Back-up UPS1481 consists of one (1) integrated cabinet — housing both the electronics and batteries (depending on KVA). Before unpacking the equipment, inspect the exterior the shipping container and the equipment itself for damage that may have occurred during transit. If the shipping container or equipment itself shows evidence of damage, note the damage on the receiving document before signing for receipt of the equipment. Damage claims should be filed directly with the carrier.

2-2-1 Equipment Unpacking

Remove the equipment from the shipping carton. Since the 68” cabinet for 15KVA is designed for pad — mount installations, there are no casters. It is suggested that a fork lift be used to remove the Fire Alarm Back-up UPS1481 from its shipping pallet.

Before placing the Fire Alarm Back-up UPS1481 onto the mounting bolts or leveller (where it will be installed), the conduit knockouts needs to be removed.

1.The conduit knockouts are located on the back-side of the cabinet for 3-15 KVA

2.Remove the conduit knockouts.

3.Measure the locations for the conduits on the conduit knockouts.

4.Drill or punch holes in the conduit knockouts for the conduits.

Anchor the Fire Alarm Back-up UPS1481 to the mounting pad at the four (4) mounting locations, by lowering levellers for 3-15 KVA units.

1.Anchor the conduits to the conduit knockouts

2.This concludes the mechanical installation.

2-3 Electrical Connections: “CAUTION & DE-ENERGIZE UNIT PRIOR TO SERVICING”

CAUTIONS CAUTION

Verity that all customer-supplied wiring Is de-energized before performing any electrical work,

CAUTIONS CAUTION

Even when the Fire Alarm Back-up UPS1481 is off, there are potentially dangerous voltages within the Fire Alarm Back-up UPS1481 due to the batteries. Extreme care must be taken when working within the Fire Alarm Back-up UPS1481 enclosure.

(6002-1646) REV.X8

14

Image 20
Contents Fire Alarm Back-up UPS1481 Unit OnLine Power Information Important Safety Instructions Table of Contents Revision History Operation Product Features OnLine Power OnLine Power Functional Block Diagram Customers Connections 120V IN/OUTPUT Unit 120V Output Unit Fire Alarm Back-up UPS1481 Sizing Options Installation Site Planning Specifications for KVA Unit Model Part Number Nomenclature Pre-Installation Remote Signaling Connections AS400 2 RS232 Connection Control Pcbd OnLine Power Operation Operation Turning On the Fire Alarm Back-up UPS1481 Turning off the Fire Alarm Back-up UPS1481 OnLine Power COMPONENT’S Location & List COMPONENT’S Table OnLine Power OnLine Power Appendix a Extended Battery RUN Chart Appendix B Optional Main Input & Main Output Breakers Input Circuit Breaker Appendix C LCD Display Menu & Troublshooting Guide Screen B The screen appears as below OnLine Power Appendix D Specification Power Rating KVA/KW OnLine Power OnLine Power Battery Cabinet B 2ND 4TH Level 1ST Level OnLine Power OnLine Power OnLine Power OnLine Power OnLine Power OnLine Power

UPS1481 UNIT specifications

The IBM UPS1481 is a robust uninterruptible power supply (UPS) designed to ensure the seamless operation of critical equipment in various environments, including data centers, telecommunications, and enterprise applications. This model is particularly noted for its reliability, efficiency, and advanced features, catering to the demands of modern IT infrastructures.

One of the main features of the UPS1481 is its high-capacity output, which can handle significant power loads. With an impressive power rating, the unit is equipped to support various devices, from servers to networking equipment, guaranteeing that essential operations remain uninterrupted during power outages or fluctuations. This capability is crucial for maintaining business continuity and minimizing potential downtime.

In terms of technology, the IBM UPS1481 integrates advanced power management systems that provide real-time monitoring and control. This functionality allows users to track power consumption, battery status, and overall system health through an intuitive interface. Additionally, the UPS includes features such as an automatic voltage regulator (AVR), which helps stabilize voltage levels, protecting connected equipment from surges, spikes, and drops that can cause damage or data loss.

The UPS1481 also comes with a modular design, allowing for scalability. Users can expand the capacity of the UPS to meet growing power demands without needing to replace the entire unit. This flexibility is beneficial for organizations undergoing rapid growth or technological upgrades.

Another important characteristic of the IBM UPS1481 is its energy efficiency. Designed to comply with various energy standards, the unit operates with minimal power loss, thereby reducing operational costs and contributing to a greener environment. By optimizing energy usage, organizations can enhance their sustainability initiatives while ensuring reliable power protection.

Furthermore, the UPS1481 offers a robust battery system that supports extended runtime options. Users can configure the UPS with additional battery packs to ensure that critical systems remain operational for extended periods during extensive outages.

In summary, the IBM UPS1481 UNIT stands out for its high capacity, advanced power management features, modular design, and energy efficiency. It is an ideal solution for businesses looking to safeguard their critical equipment and maintain operational integrity in the face of power disruptions.