Greenheck Fan DH100ACDCLP specifications Space Envelopes Electrical Ratings

Page 3

 

Space Envelopes

Electrical Ratings

 

 

 

Dampers Less Than 25 Inches (635mm) In Height

 

3 in.

6 3⁄4 in.

Typical Actuator

(ML series shown; other actuators available)

Single Point W iring (Standard) Smoke detector, actuator, and all control options are prewired to junction box at the factory.

Dampers Equal To Or Greater Than 25 Inches (635mm) In Height

2 3/4 in. (70mm)

15 in.

(381mm)

Typical Actuator

(other actuators available)

Single Point Wiring (Standard): Smoke detector, actuator, and all control optiong are prewired to junction box at the factory.

Electrical Ratings

Power Supply Voltage:

20-29 VDC

24 VAC 50-60 Hz

120 VAC 50-60 Hz

220/240 VAC 50-60 Hz

Input Capacitance:

270 µF max.

270 µF max.

N/A

N/A

Reset Voltage:

3.0 VDC min.

2.0 VAC min.

10 VAC min.

20 VAC min.

Reset Time:

0.6 sec. max.

0.6 sec. max.

0.6 sec. max.

0.6 sec. max.

Power Up Time:

34 sec. max.

34 sec. max.

34 sec. max.

34 sec. max.

Alarm Response Time:

2-17 sec.

2-17 sec.

2-17 sec.

2-17 sec.

Sensitivity Test:

See detector label

See detector label

See detector label

See detector label

Current Requirements

 

 

 

 

Max. Standby Current:

15 mA

35 mA RMS

25 mA RMS*

15 mA RMS*

Max. Alarm Current:

70 mA

125 mA RMS

35 mA RMS*

25 mA RMS*

Contact Ratings

 

 

 

 

Alarm Initiation Contacts (SPST):

2.0A @ 30 VAC/DC (0.6 power factor)

 

Alarm Auxiliary Contacts (DPDT):

10A @ 30 VDC

 

 

 

 

10A @ 250 VDC

 

 

Note: Alarm auxiliary contacts must switch 100 mA minimum at 5 VDC. Alarm auxiliary contacts shall not be connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose.

Trouble Contacts (SPDT):

2.0A @ 30 VDC (resistive)

Image 3
Contents Purpose/Application SpecificationsFeatures ConfigurationSleeve Length Ordering Options Sleeve LengthOrdering Options Electrical Ratings Space Envelopes Electrical RatingsDampers Less Than 25 Inches 635mm In Height Dampers Equal To Or Greater Than 25 Inches 635mm In HeightWiring Diagrams Duct smoke detector Fusible LinkOCI RRL/OCI RRLTOR OCI w/ EP SwitchRRL/OCI W/ EP Switch RRL W/ EP SwitchTOR w/ EP Switch