| Space Envelopes | Electrical Ratings |
|
|
|
Dampers Less Than 25 Inches (635mm) In Height |
|
3 in.
6 3⁄4 in.
Typical Actuator
(ML series shown; other actuators available)
Single Point W iring (Standard) Smoke detector, actuator, and all control options are prewired to junction box at the factory.
Dampers Equal To Or Greater Than 25 Inches (635mm) In Height
2 3/4 in. (70mm)
15 in.
(381mm)
Typical Actuator
(other actuators available)
Single Point Wiring (Standard): Smoke detector, actuator, and all control optiong are prewired to junction box at the factory.
Electrical Ratings
Power Supply Voltage: | 24 VAC | 120 VAC | 220/240 VAC | |
Input Capacitance: | 270 µF max. | 270 µF max. | N/A | N/A |
Reset Voltage: | 3.0 VDC min. | 2.0 VAC min. | 10 VAC min. | 20 VAC min. |
Reset Time: | 0.6 sec. max. | 0.6 sec. max. | 0.6 sec. max. | 0.6 sec. max. |
Power Up Time: | 34 sec. max. | 34 sec. max. | 34 sec. max. | 34 sec. max. |
Alarm Response Time: | ||||
Sensitivity Test: | See detector label | See detector label | See detector label | See detector label |
Current Requirements |
|
|
|
|
Max. Standby Current: | 15 mA | 35 mA RMS | 25 mA RMS* | 15 mA RMS* |
Max. Alarm Current: | 70 mA | 125 mA RMS | 35 mA RMS* | 25 mA RMS* |
Contact Ratings |
|
|
|
|
Alarm Initiation Contacts (SPST): | 2.0A @ 30 VAC/DC (0.6 power factor) |
| ||
Alarm Auxiliary Contacts (DPDT): | 10A @ 30 VDC |
|
| |
|
| 10A @ 250 VDC |
|
|
Note: Alarm auxiliary contacts must switch 100 mA minimum at 5 VDC. Alarm auxiliary contacts shall not be connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose.
Trouble Contacts (SPDT): | 2.0A @ 30 VDC (resistive) |