Greenheck Fan dimensions Pressure Drop Data FSD-M211, Amca Test Figures

Page 2

Pressure Drop Data

FSD-M211

This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of 1.201 kg/m3.

Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC system.

AMCA Test Figures

Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper.

Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.

Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high entrance and exit losses due to the sudden changes of area in the system.

5D

5D

6D

D4 (W) (H)

3.14

Image 2
Contents Ratings Optional FeaturesApplication Standard ConstructionPressure Drop Data FSD-M211 Amca Test FiguresAmca 5.2 Pressure Drop FSD-M211 $&7&-0$*5.&5&344&$0/% $10.3 12.9 15.4 17.7 20.8 610mm x 610mm Amca 5.3 Pressure Drop FSD-M211305mm x 305mm 10.1 12.7 15.3 20.6Amca 5.5 Pressure Drop FSD-M211 Damper Sizing Information Damper Sleeve Dimensional DataSpecifications