INSTALLATION ADUSTMENTS AND CHECKOUT

Fig. 1 O-Typical wiring of C7015A Infrared Flame Detector to nearby wiring subbase or terminal strip.

cmi5A

FLEXIBLE CABLE (MECHANICALLY

SUPPORT TO MINIMIZE MOVEMENT)

GROUNDlNG

RING SUBBASE

OR TERh

STRAP,

 

n1 1 BROWN WIRE AND 1 WHITE WIRE FROM THE C7015A. CONNECT TO FLAME SAFEGUARD CONTROL’S SUBBASE, COLOR NOT IMPORTANT, KEEP WIRES AS SHORT AS POSSIBLE. AND TWIST THEM.

AFLEXIBLE CABLE MUST BE RUN To FLAME SAFEGUARD CONTROL ’S

SUBBASE AND GROUNDED WHERE THE EXPOSED WIRES BEGIN.

Fig. 1 l-Typical wiring of C7015A Infrared Flame Detector to distant wiring subbase or terminal strip.

FLEXIBLE CABLE (MECHANICALLY SUPPORT TO MINIMIZE MOVEh

BX CABLE, SHIELDED

ICABLE, OR TWISTED

PAIR; MUST BE ALONE

IN CONDUIT.

I FLAME SAFEGUARD

CONTROLS SUBBASE

II

JUNCTION BOX A

1 BROWN WIRE AND 1 WHITE WIRE FROM THE C7015A; CONNECT lNSlDE JUNCTlON Box; COLOR NOT IMPORTANT; LEADWIRES FROM JUNCTION BOX NEED NOT BE PHASED OR POLARIZED.

APPLY CAUTION STICKER, FORM NO. 96-610 SUPPLIED WITH Ci’O15A. TO THIS JUNCTION BOX. BOX MUST BE GROUNDED.

USE RIGID CONDUIT. OR SUPPORT FLEXIBLE CONDUIT TO

.MINIMIZE MOVEMENT.

CONDUIT MUST BE RUN TO FLAME SAFEGUARD CONTROL’S SUBBASE AND GROUNDED THERE. KEEP EXPOSED WIRES AS SHORT AS POSSIBLE AND TWIST THEM.

IA3046

Adjustments and Checkout

IMPORTANT: Before welding the sight pipe in its final location, complete the AdjustmentsandCheckout Tests below and any tests required by the burner man@ac- turer.

ADJUST DETECTOR SIGHTING POSITION

For initial burner lightoff, consult the burner manufacturer instructions or flame safeguatd control instructions.

With the flame detector installed and the burner running, adjust the sighting position of the detector for optimum flame signal.

Most existing Honeywell flame safeguard controls have a flamecurrentjackonthecontrolplug-inflameamplifier.The flame signal (current) can be measured with a volt-ohmmeter such as the Honeywell W 136A with a zero to 25 microampdc scale. To measure the flame current (signal), a Cable Connec- tor (part number 1%146, included with W136A) must be used with the meter. With the W136A (or equivalent) posi- tioned to the zero to 25 microamp scale, make connections from the meter probes to the two ends of the cable connector plug, red to ted, black to black The plug end of the connector pluginsertsdirectlyintotheamplifierflamejack(seeFig. 12).

If the flame safeguard control is using a R7248B AMRLI- CHECP amplifier, the red flame-indicating lamp on the

amplifEr should blink at the same rate that the flame is flickering (may be as high as 20 times a second). If the lamp is ON (bright) continuously or not blinking while measuring the flame current, replace the amplifier.

Refer to Table 6 for the minimum acceptable flame currents for the amplifiers and associated flame safeguard controls.

The R7748B AMRLI-CHECKTM ; R7848A and R7848B (AMPLI-CHECKTM)amplifiersusedwiththeBCS7700and 7800 SERIES flame safeguard controls respectively, have a dc voltage flame signal output.

To measure flame signal voltages when using a R7748B amplifier, a 20,000 ohm/voltmeter with a zero to 5 or 10 Vdc scale is suggested To measure the flame signal voltage when using R7848A,B amplifiers, a volt-ohm meter with a mini- mum sensitivity of one megohm/volt is recommended. The flame signal (voltage) measurements are made as shown in Figs. 13 and 14. The positive (red) meter lead is connected to the positive (+) control jack and the negative (black) meter lead to the negative (-) control jack (Corn jack with 7800 SERIES controls). If the BCS 7700 and 7800 SERIES controls have the Keyboard Display Module, a zero to five Vdc voltage is displayed on the module. Refer to Table 6 for minimum and maximum flame voltages for the amplifiers

Image 10
Contents Infrared Flame Detector Super Tradeline Features SpecificationsSpecifications Ordering Information Order InformationApprovals Wiring ConnectionsAccessories Rrplacfment PartsCell Construction Operation InstallationTory Basic RequirementsLength Length Distance From End of Pipe To Sighted Area-in36 I 42 I 66 1 Pipe-mmInstallation Table Adiamexer of Area Sighted Through ORIFICE,Sighting Summary Flame has been extinguished760-2306-5 Prepare Hole in Wall of Combustion Chamber Installing AccessoriesClearance Sight Pipe VentilationFor splicing in high temperature installations, use ‘e. Underwriters Laboratories INC. REInstallation Adustments and Checkout Adjustments and CheckoutCmi5A Minimum 1 Maximum 1 Minimum Adjustments and CheckoutFlame Safeguard Control Acceptable ExpectedIgnition Interference Test Flickering radiation of the l&me itselfHOT Refractory HOLD-IN Test Close Manual Fljbl Valves to the Pilot and Main BurnerAdjustments and Checkout Troubleshooting Service Periodic MaintenanceTable of Contents

C7015A specifications

The Honeywell C7015A is a versatile, high-performance electronic air temperature sensor designed for use in a variety of HVAC applications. Recognized for its reliability and advanced technology, this sensor ensures accurate temperature measurements, contributing to the overall efficiency of climate control systems.

One of the main features of the C7015A is its exceptional sensing accuracy. The sensor utilizes a thermistor-type temperature sensing element, which allows for precise measurements across a broad temperature range. This precision is critical in maintaining the desired environmental conditions in residential, commercial, and industrial settings.

Another key characteristic of the Honeywell C7015A is its robust design. It is built to withstand a range of installation environments, ensuring longevity and consistent performance. The sensor comes with an IP rating that indicates its resistance to dust and moisture, making it suitable for various indoor and outdoor applications. Its durable construction ensures that it can operate effectively even in challenging conditions, enhancing its reliability.

The C7015A is designed for easy installation and integration into existing systems. It features standard electrical connections, which allows for straightforward wiring to a variety of control systems. Additionally, the sensor can be utilized with a multitude of Honeywell control units, enhancing system compatibility and flexibility. This interoperability is a significant advantage for HVAC technicians and engineers who require seamless integration with existing equipment.

Furthermore, the C7015A leverages advanced technologies such as digital signal processing to minimize noise and improve the accuracy of temperature readings. This technology ensures that the sensor can provide stable output even in fluctuating conditions, which is vital for precision climate control.

In summary, the Honeywell C7015A electronic air temperature sensor is characterized by its high accuracy, durable construction, ease of installation, and advanced technological features. These attributes make it a reliable choice for HVAC professionals aiming to optimize temperature control in various applications, ensuring both comfort and energy efficiency. The C7015A stands as a testament to Honeywell's commitment to quality and innovation in the field of environmental control solutions.