D. Install Attic Insulation Shield

WARNING! Fire Risk. DO NOT allow loose materials or insulation to touch vent. Hearth & Home Technologies Inc. requires the use of an attic shield.

The National Fuel Gas Code ANSI Z223.1 and NFPA 54 requires an attic shield constructed of 26 gauge minimum metal that extends at least 2 in. (51 mm) above insulation.

Attic shields must meet specified clearance and be se- cured in place.

Flat Ceiling Installation

• Remove one shield from box.

NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.

Wrap shield around pipe if pipe is already installed in area to be insulated.

Match the three holes in each side and fasten with three screws to form a tube.

Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling firestop.

Bend the remaining bottom tabs inward 90º to maintain the air space between the pipe and the shield. Set the shield on the ceiling firestop and attach to the firestop.

Bend all tabs inward 90º around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance.

Vaulted Ceiling Installation

• Remove one shield from box.

NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.

Cut the attic insulation shield (if application is for vaulted ceiling) to fit your ceiling pitch. Snip cut edge to recreate 1 in. bend tabs all the way around the bottom.

Wrap shield around pipe if pipe is already installed in area to be insulated.

Match the three holes in each side and fasten with three screws to form a tube.

Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling firestop.

Bend the remaining bottom tabs inward 90º to maintain the air space between the pipe and the shield. Set the shield on the ceiling firestop and attach to the firestop.

Bend all tabs inward 90º around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance.

BEND ALL TABS INWARD 90° TO MAINTAIN CLEARANCE AND PREVENT INSULATION FROM FALLING INSIDE

INSERT 3

SCREWS

Figure 8.9 Attic Insulation Shield

BEND 3 TABS

OUTWARD TO FASTEN TO CEILING FIRESTOP-BEND REMAINING TABS INWARD 90 DEGREES TO MAINTAIN CLEARANCE

Heat & Glo • 8000CF-OAK-IPI2059-900 Rev. Q • 11/08

31

Image 31
Contents HOT Surfaces What to do if you smell gasHot glass will cause burns Homeowner Reference Information CongratulationsXxxxxxxx User Guide Table of ContentsReference Materials Appliance SetupTroubleshooting FinishingCONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsOperating Instructions User Guide Gas Fireplace SafetyYour Fireplace Clear Space Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Fan Kit optionalGAS Valve Lighting Instructions IPIFinal inspection by What to do if YOU Smell GASIssue Solutions Frequently Asked QuestionsAfter Fireplace is Lit Remote Control Maintenance and ServiceMaintenance Tasks-Homeowner Glass CleaningLogs Maintenance Tasks-Qualified Service TechnicianGasket Seal and Glass Assembly Inspection VentingEither cobrahead or SIT Typical Appliance System Getting StartedAny such action may cause a fire hazard Design and Installation ConsiderationsTools and Supplies Needed Inspect Appliance and ComponentsSelecting Appliance Location Framing and ClearancesConstructing the Appliance Chase Minimum Framing DimensionsClearances Combustible Mantels Mantel and Wall ProjectionsCombustible Mantel Legs or Wall Projections Vent Termination Minimum Clearances Termination Locations= Vent Terminal = AIR Supply Inlet = Area Where Terminal is not PermittedUse of Elbows Vent Information and DiagramsApproved Pipe Vent Table KeyV1 Minimum H1 + H2 Maximum Vent Diagrams Top Vent Horizontal Termination One ElbowTwo Elbows V1 Minimum H1 MaximumV1 Min H1 Max V2 Min H2 Max V1 + V2 Min H1 + H2 Max Top Vent Horizontal Termination Three ElbowsVertical Top Vent ChartH1 Maximum V1 + Minimum Top Vent Vertical Termination Two ElbowsH1+ H2 V1+ V2 Minimum H1+ H2 Maximum Required Vent Clearances and FramingPipe Clearances to Combustibles Heat Shield Above First 900 ElbowCombustible Wall Penetration Wall Penetration FramingNon-Combustible Wall Penetration Pipe DVP Install the Ceiling FirestopFlat Ceiling Installation Install Attic Insulation ShieldVaulted Ceiling Installation Appliance Preparation Temporary Access PanelAttaching Sheetrock Ledges Securing and Leveling the Appliance Installing the Fiberglass GasketChecking Pilot Plate Completing Grate Set-upAssemble Pipe Sections Installing Vent PipeAttach Vent to the Firebox Assembly Assemble Vent SectionsSecure the Vent Sections Assemble Slip SectionsDisassemble Vent Sections 10 Rotate Seams for DisassemblyAssemble and Install Storm Collar Install Metal Roof FlashingApply Sealant TOP & Partial Sides Install RF4-8Heat Shield Requirements for Horizontal Termination Install Vertical Termination CapAnsi Z223.1 and CAN/CGA-B149 installation codes Install Horizontal Termination CapGas Connection Gas InformationFuel Conversion Gas PressureElectrical Information Wiring RequirementsIntellifire Ignition System Wiring Optional Accessories RequirementsIntellifire Pilot Ignition IPI Wiring Diagram Electrical Service and RepairWall Switch Installation for Fan Optional Junction Box InstallationFacing Material FinishingAppliance Setup Ember Placement Install the Optional RefractoryInstall the Log Assembly Log Assembly LOGS-8OAKHeat & Glo 8000CF-OAK-IPI 2059-900 Rev. Q 11/08 Air Shutter Settings Install the MeshInstall Trim and/or Surround Air Shutter SettingSymptom Possible Cause Corrective Action TroubleshootingIntellifire Ignition System Ues to spark, and main Reference Materials Appliance Dimension DiagramLocation Inches Millimeters DVP vent components Vent Components DiagramsHorizontal Termination Cap DVP-TRAPCOOL-ADD RF6M RF12MBEK DVP-BEK2 DVP-TRAPFL305 mm DVP-TB1Service Parts Log Set AssemblyAt Depot Service Parts ListStocked Valve AssemblyContact Information

8000CF-OAK-IPI, 8000CFLP-OAKIPI specifications

Hearth and Home Technologies (HHT) is recognized for its commitment to quality and innovation in the fireplace and home heating industry. Among its popular products are the 8000CFLP-OAKIPI and 8000CF-OAK-IPI gas fireplaces, which stand out in terms of design, features, and efficiency.

The 8000CFLP-OAKIPI is a contemporary linear gas fireplace that features a stunning design suitable for modern living spaces. With its expansive viewing area, the 8000CFLP-OAKIPI provides a captivating flame presentation that transforms any room into a cozy retreat. Its clean face design eliminates a bulky frame, giving the appearance of a window to the flames. This model is equipped with LED accent lighting that enhances the ambiance further when the fireplace is not in use.

On the other hand, the 8000CF-OAK-IPI offers a more traditional design that features a classic fireplace experience while incorporating modern technology. It uses high-efficiency gas combustion to deliver unmatched warmth while ensuring minimal emissions. Both models come with the option for ceramic fiber logs, which mimic the natural look of real wood while enhancing heat production.

The advanced IntelliFire app supports both units, allowing users to control the fire conveniently via smartphone or tablet. This technology offers increased functionality, enabling users to adjust flame height, fan speed, and lighting settings for the perfect ambiance.

In terms of energy efficiency, both the 8000CFLP-OAKIPI and the 8000CF-OAK-IPI are designed to offer significant savings on heating bills. They are equipped with an electronic ignition system that offers seamless startup and optimal combustion efficiency. The design also adheres to stringent efficiency standards, ensuring that users enjoy a sustainable and cost-effective heating solution.

Installation is made straightforward with their versatile venting options, allowing for both direct vent and vent-free configurations. This flexibility ensures compatibility with various home layouts while optimizing heat distribution.

In summary, the Hearth and Home Technologies 8000CFLP-OAKIPI and 8000CF-OAK-IPI gas fireplaces represent a blend of style, technology, and efficiency. With their focus on innovation and customer satisfaction, HHT continues to lead the way in providing modern heating solutions that elevate any living space.