Honeywell T8775A specifications Customize Thermostat, DIP Switch, Setting Fuel Switch T8775C only

Page 5

T8775A,C THE DIGITAL ROUNDNON-PROGRAMMABLE THERMOSTATS

Rc

B

G

2

Y

R

W

 

COMPRESSOR

CONTACTOR

 

HEATING

FAN

1

RELAY OR

RELAY

 

VALVE COIL

 

1

FUEL SWITCH

M19497

Fig. 12. Fuel switch.

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2REMOVE FACTORY INSTALLED JUMPER BETWEEN R AND RC.

M19517

Fig. 10. Typical hookup of T8775C in heat-cool system

with two transformers.

4

 

O

 

B

 

Rc

2

G

Y 3

R

 

W

DIP Switch

To adjust the heat cycle rate or the Fahrenheit/Celsius temperature display, locate DIP switch 1, 2 and 3 on the back of the thermostat. See Fig. 13.

BACK OF THERMOSTAT

 

COMPRESSOR

 

HEAT

 

CHANGEOVER

 

CONTACTOR

 

 

VALVE

 

 

 

1

FAN

 

COOL

 

 

 

RELAY

CHANGEOVER

 

VALVE

 

 

 

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS

 

AND OVERLOAD PROTECTION AS REQUIRED.

2

FACTORY INSTALLED JUMPER.

3

USE A JUMPER WIRE (NOT SUPPLIED) TO CONNECT W TO Y.

4

USE EITHER O OR B FOR HEAT PUMP CHANGEOVER.

 

 

 

M19516

Fig. 11. Typical hookup of T8775C in single-stage heat

pump system.

CUSTOMIZE THERMOSTAT

Setting Fuel Switch (T8775C only)

The fuel switch is preset at the factory in the F position. See Fig. 12. This is the correct setting for gas or oil systems. If the T8775C is being installed on an electric heat system, or a heat pump, set the switch to the E position. The E position allows the fan to turn on immediately with the heating equipment in a system where the G terminal is connected.

 

3

 

2

ON

1

M19567

DIP SWITCH

Fig. 13. DIP switch.

Set Heat Cycle Rate

Use DIP switches 1 and 2 to set the heat cycle rate. See Table 1.

Table 1. Heat Cycle Rate.

 

 

 

 

 

Cycles

DIP

DIP

Heating System

Per

Switch

Switch

Hour

1

2

Steam, Gravity

1

On

On

 

 

 

 

High Efficiency Warm Air (90%+

3

Off

On

efficiency), Hot Water, Heat Pump

 

 

 

Gas or Oil Warm Air (factory setting)

6

Off

Off

 

 

 

 

Electric Warm Air

9

On

Off

 

 

 

 

In Floor Radiant Heat

Check with manufacturer

 

for recommended cycle

 

rate.

 

 

5

68-0279

Image 5
Contents Contents Features ApplicationOrdering Information SpecificationsSeparate Wallplate from Thermostat Mm holes where markedMount Wallplate to Wall Mount wallplate to wall See as followsRefer to through 11 for typical wiring diagrams WiringSetting Fuel Switch T8775C only DIP SwitchCustomize Thermostat Set Heat Cycle RateFeatures and Operation SET System and FAN Switches T8775C onlyCheckout Automation and Control Solutions Troubleshooting Guide