Carrier Access ÐSet Thermidistat Control Configuration, Option 1ÐAnticipator Adjustment

Page 3

3.A2Ðfor 2-speed air conditioner

4.H2Ðfor 2-speed heat pump

5.dFÐfor 1-speed dual fuel

6.d2Ðfor 2-speed dual fuel

7.HSÐfor 1-speed heat pump with Intelligent Heat Staging (3-stage auxiliary heat with 40FK, FK4C, or FV4A Series fan coils.)

When this identifier disappears, normal operation begins. The MODE control should be set to OFF and FAN control to AUTO, so equipment does not start until further configuration and check- out is completed.

Step 4ÐSet Thermidistat Control Configuration

Configuration options, like DIP switch settings, are intended to be selected at installation and normally are not modified by the homeowner. These options are not discussed in the homeowner's manual and therefore must be made as part of the installation. A special procedure allows entry into the configuration mode. While in configuration mode, up to 17 selections can be made. A description of each selection and how to use the configuration mode follows.

CONFIGURATION OPTIONS Ð SUMMARY:

Option 1ÐAnticipator adjustment

Option 2ÐClean filter timer adjustment

Option 3ÐEnglish/Metric selection

Option 4ÐFan (G) ON with W selection

Option 5ÐVariable-speed blower present selection

Option 6ÐCooling lockout below 55° selection

Option 7ÐVariable-speed super dehumidification selection (only available when variable-speed blower is used)

Option 8ÐAuxiliary heat lockout temperature setting (only avail- able when heat pump is used)

Option 9ÐIntelligent Heat Staging selection (only available when single-speed heat pump is used)

Option 10ÐDual Fuel selection (only available when heat pump is used)

Option 11ÐBalance point setting (only available when Dual Fuel is selected)

Option 12ÐDefrost heat selection (only available when heat pump is used)

Option 13ÐRoom temperature offset adjustment

Option 14ÐHeat/cool dead band adjustment

Option 15ÐEnable Auto mode

Option 16ÐEnables Super Comfort Heat Mode

Option 17ÐNon-Programmable selection

TO ENTER CONFIGURATION MODE:

Press and hold FAN button for approximately 10 sec until COOL set point display indicates a flashing 1. The Thermidistat Control is now in configuration mode. It will automatically exit this mode if no button is pressed for 3 minutes. Pressing END button will exit configuration mode immediately.

WHILE IN CONFIGURATION MODE:

The upper small (COOL set point) display indicates selected option number and large display indicates selection made within that option. One of these will be flashing. The up and down buttons are used both to move between available options and to make selection for each option. When option number (small display) is flashing, up and down buttons adjust it, moving between available option numbers. After desired option number has been selected,

press SET TIME/TEMP button once. The large display will now flash, indicating that up and down buttons now control available choices within that option. Each press of TIME/TEMP button switches between available option (small display) and available selections within each option (large display).

CONFIGURATION OPTIONS Ð SELECTION:

Option 1ÐAnticipator Adjustment

This adjustment controls sensitivity and cycle rate of Thermidistat Control. Higher numbers decrease sensitivity and slow cycle rate. Lower numbers increase sensitivity and cycle rate. However, a limiting feature will not allow more than 4 cycles per hr, regardless of setting. Anticipator values can range from 1 to 9. Factory default is 3. This default selection provides optimum performance in nearly all installations. Try it first. Do not change setting unless there is evidence of need to do so.

Unlike conventional anticipators, this setting is not determined by current draw. There is no need to measure, know, or compensate for current draw. There is also no droop with this Thermidistat Control. Regardless of setting and number of stages, both heating and cooling will control to their respective set points.

TO ADJUST:

1.Enter configuration mode if not already there. See Step 4 "To Enter Configuration Mode." The upper small (COOL set point) display will be flashing 1. If not, use up and down buttons to move it to 1.

2.Press SET TIME/TEMP button once to flash current selection of 1, 2, 3, 4, 5, 6, 7, 8, or 9 on large display. Factory default is 3.

3.Use up and down buttons to move between available choices.

4.Press SET TIME/TEMP button again to flash upper small display for selection of another option, or press END to exit configuration mode.

Option 2ÐClean Filter Timer

Select hours of blower operation (heating, cooling, or fan) before CLEAN FILTER icon is displayed. With OFF selected, icon will never come on, disabling this feature. Time selection can range from 400 to 3600 hr by selecting numbers 1 through 9. (Time is 400 X number selected.) Factory default is 2 (800 hr). Recom- mended selections are: disposable filterÐ400 to 800 hr, media filterÐ1200 to 1600 hr, or electronic air cleanerÐ1600 to 2400 hr of blower operation.

TO SELECT OR ADJUST:

1.Enter configuration mode if not already there. See Step 4 "To Enter Configuration Mode." Use up and down buttons to make small (now flashing) display indicate 2.

2.Press SET TIME/TEMP button once to flash current selection of OF, 1, 2, 3, 4, 5, 6, 7, 8, or 9 on large display. Factory default is 2.

3.Use up and down buttons to move between available choices.

4.Press SET TIME/TEMP button again to flash upper small display for selection of another option, or press END to exit configuration mode.

Option 3ÐEnglish/Metric

Select between Fahrenheit and Celsius operation. Factory default is Fahrenheit.

TO SELECT OR ADJUST:

1.Enter configuration mode if not already there. See Step 4 "To Enter Configuration Mode." Use up and down buttons to make small (now flashing) display indicate 3.

2.Press SET TIME/TEMP button once to flash current selection of F or C. Factory default is F.

3

Image 3
Contents Introduction Safety ConsiderationsInstallation Considerations IndexÐThermidistat Control Location InstallationÐSet DIP Switches ÐInstall Thermidistat ControlOption 3ÐEnglish/Metric ÐSet Thermidistat Control ConfigurationOption 1ÐAnticipator Adjustment Option 2ÐClean Filter TimerOption 6ÐCooling Lockout Below 55F Option 8ÐAuxiliary Heat Lockout SettingOption 4ÐFan G On With W Option 5ÐVariable-Speed ICM BlowerOption 12ÐDefrost Heat Select Option 11ÐBalance Point SettingÐW1 / W2 Outputs Option 10ÐDual Fuel EquipmentOption 16ÐEnable Super Comfort Heat Mode Option 13ÐRoom Temperature Offset AdjustOption 14ÐHeat/Cool Dead Band Adjustment Option 15ÐEnable Auto ModeTo Test FAN Option 17ÐEnable Non-Programmable OperationRedefinition of Buttons ÐSystem Start-Up and CheckoutÐEquipment Outputs ÐEnergy Star Default ScheduleÐFinal Settings Humidity Control FeaturesSuperdehumidify With Cool to Dehumidify ÐHumidification SelectionsAdditional Humidify Comments To Select Dehumidification Between NORMAL, Cool TO, and OFFVacation Set Points ÐDehumidification SelectionsDehumidify Output and Equipment Connections VacationThermidistat Control Troubleshooting Vacation DehumidificationOperational Information Thermidistat Control Configuration Record WakedayEvesleep

Thermidistat specifications

The Carrier Access Thermidistat is an advanced thermostat designed to optimize indoor climate control, providing both comfort and energy efficiency. As part of Carrier's commitment to innovation in heating, ventilation, and air conditioning (HVAC), the Access Thermidistat combines modern technology with user-friendly features.

One of the standout features of the Carrier Access Thermidistat is its Wi-Fi connectivity. This allows users to control their home environment remotely via a smartphone, tablet, or computer. With the Carrier mobile app, users can adjust temperature settings, schedule heating and cooling cycles, and monitor energy usage from anywhere. This convenient feature not only enhances user control but also helps in managing energy consumption more effectively.

The Access Thermidistat is equipped with advanced algorithmic technology, which continuously learns user preferences and adapts accordingly. This smart technology assesses factors such as occupancy patterns and external weather conditions, optimizing the HVAC system’s performance to create a personalized comfort experience. By doing so, it reduces energy waste and lowers utility bills, making it an economical choice for homeowners.

In terms of compatibility, the Carrier Access Thermidistat works seamlessly with a wide range of heating and cooling systems, including central air units, heat pumps, and zone control systems. This versatility makes it an ideal solution for both new installations and retrofitting existing systems, ensuring homeowners can easily transition to a smarter climate control solution.

Another notable characteristic of the Access Thermidistat is its intuitive touchscreen interface. Users can easily navigate the menu to adjust settings, create schedules, and view energy reports. The display also provides real-time feedback on current indoor conditions, including temperature and humidity levels, which helps users make informed decisions about their HVAC usage.

Moreover, the Carrier Access Thermidistat features multiple scheduling options, enabling homeowners to set specific temperature settings for different times of the day or days of the week. This flexibility ensures that energy is conserved when the house is unoccupied while maintaining comfort during peak living hours.

Safety and reliability are also paramount in the design of the Access Thermidistat. It incorporates features such as energy-saving modes and alerts for system malfunctions or maintenance needs, ensuring that users are always informed about their HVAC system's performance.

In summary, the Carrier Access Thermidistat is a cutting-edge solution that combines connectivity, automation, and user-centric design to enhance the overall HVAC experience. By integrating smart technology with practical features, it offers a superior way to manage indoor climates efficiently and conveniently.