Setup & Testing
EQUIPMENT TYPE SELECTION SWITCH (SW1)
This thermostat has the option of being used in heat pump or heat/cool systems. Switch SW1 located on the back of the thermostat’s face is used to select this option. This setting can also be checked in the Installer System Settings under Equipment Type..
Note: Thermostat reboots within 10 seconds after switch position is changed..
HC | SW1 | |
HEAT/COOL | ||
HP | ||
| HEAT PUMP | |
| HC | |
| HP |
Setup & Testing
INSTALLER SYSTEM SETTINGS TABLE
The following table is the list of the settings and their details. Default settings are shown in bold.. Some settings are only available to thermostats set to heat pump or humidistat mode.
|
| Factory default setting (bold) |
System setting | Description | and setting range |
|
|
|
00. NETWORK ADDRESS | Network communication address. | 1 |
|
| Address selection of 1 to 64 in steps of 1 |
01. NUMBER OF NODES | Total number of thermostats on the network.. | 64 |
|
| Selection of 1 to 64 in steps of 1 |
02. BAUD RATE | Communication baud rate. | 9600 |
Installer setup menu
How to enter the installer setup menu to change system settings:
Press [MODE] to set system to OFF.. | Press [NEXT] or [BACK] to page through the settings.. | ||||
Press [MENU] to enter main menu.. | Press | or | to adjust the setting. | ||
Press and hold [SETUP] for seven seconds, [INSTALL | Press [DONE] to save and exit, or [CANCEL] to exit | ||||
SETUP] appears.. |
| without saving. |
| ||
Press [INSTALL SETUP] to enter installer setup menu.. | The thermostat will discard changes and exit if nothing | ||||
|
| is pressed within 60 seconds. | |||
SETTING | SETTING | To reset the installer settings to the default, reset the | |||
DESCRIPTION | NUMBER | ||||
thermostat by pressing the [RESET] button inside the | |||||
SETTING |
| ||||
OPTIONS |
| battery cover. |
|
|
| 19200 |
03. CONTROLLER TYPE | Sets controller to Thermostat or Humidistat.. | THERMOSTAT |
|
| HUMIDISTAT |
04. EQUIPMENT TYPE | Equipment type is set by SW1.. | HEAT/COOL |
|
| HEAT PUMP |
05. CONTROL SETUP | Used to lockout heating or cooling outputs | HEAT AND COOL |
| (only available in Heat/Cool mode). | HEAT ONLY |
|
| COOL ONLY |
06. AUTO CHANGEOVER | Enable or disable Auto changeover mode. | DISABLE |
|
| ENABLE |
07. NUMBER OF STAGES | Number of stages of equipment. | SINGLE |
|
| MULTI |
08. AUX HEAT STAGES | Number of stages of auxiliary heat equipment. | ONE |
|
| TWO |
09. Heat/Cool: FAN | Heat/Cool: Determines if the thermostat or | GAS/OIL HEAT (equipment controls fan) |
CONTROL IN HEATING | equipment controls the fan in heating.. | ELECTRIC HEAT (thermostat controls fan) |
Heat Pump: AUXILIARY | Heat Pump: Auxiliary Equipment type.1 |
|
EQUIPMENT TYPE |
|
|
10. Thermostat: | Thermostat: Minimum off time for compressor | 5 MINUTES |
COMPRESSOR MIN OFF | protection.. | 1 to 5 MINUTES |
TIME | Humidistat: Minimum on/off time for dehumidifier |
|
10. Humidistat: | protection.. |
|
DEHUMIDIFIER MIN |
|
|
ON/OFF TIME |
|
|
11. Thermostat: HEATING | Thermostat: Minimum off time for heating. | 2 MINUTES |
MIN OFF TIME | Humidistat: Minimum on/off time for humidifier. | 1 to 5 MINUTES |
11.Humidistat: HUMIDIFIER MIN ON/OFF TIME
12. EQUIPMENT MIN ON | Minimum on time for heating and cooling.. | 2 MINUTES |
TIME |
| 1 to 5 MINUTES |
13.AUTO CHANGEOVER Minimum time between heating and cooling calls.. 4 MINUTES
TIME | 1 to 5 MINUTES |
14. REMOTE SENSOR | Select if remote sensor is attached at T1 and T2.. NO |
| YES |
15.OUTDOOR SENSOR Select if outdoor sensor is attached at S1 and S2.. NO
YES
16. CONTROL SENSOR | Control sensor failure response. | STOP CONTROL (enter Error Mode) |
BACKUP |
| USE |
17. FIRST STAGE | 1st stage differential.. | 1°F (0.5°C) |
DIFFERENTIAL |
| 1°F to 9°F (0.5°C to 4.5°C) |
18. SECOND STAGE | 2nd stage differential.. | 1°F (0.5°C) |
DIFFERENTIAL |
| 1°F to 9°F (0.5°C to 4.5°C) |
1If utilizing a fossil fuel auxiliary heat system, set to Gas or Oil Furnace. In this setting, the heat pump will lock out before the fossil fuel auxiliary heat comes on; eliminating the need for a dual fuel kit. If utilizing electric auxiliary heat, set to Electric. In this setting, the heat pump and electric auxiliary heat are allowed to run simultaneously.
8 | 9 |