Aprilaire 8800 installation instructions Conventional HEAT/COOL

Page 3

Installation

Wiring terminal

Installation

CONVENTIONAL HEAT/COOL

Single transformer (use Jumper wire)

B+ A+ B- A- C

B O Y Y2 G RC RH W2 W R S2 S1 T1 T2 RSB RSA

Wire specifications:

B+ / B- – Receive communication terminal

18-24 gauge thermostat wire

(reference automation system)1

 

COMMUNICATION

TERMINALS

NOT USED

NOT USED

 

 

 

 

 

 

 

COOLING

COOLING

FAN

 

1st

2nd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

JUMPER

2nd HEATING 1st HEATING

THERMOSTAT IS POWERED FROM 8819 OR 24VAC

TRANSFORMER

OUTDOOR TEMP SENSOR

REMOTE TEMP SENSOR

SUPPORT

MODULE

CAT-5 or equivalent for communication terminals

A+ / A- – Transmit communication terminal

(reference automation system)1

 

Installation notes:

C – 24VAC Thermostat power (common) from 8819

• Ensure power at the HVAC equipment is off.

R – 24VAC Thermostat power (hot) from 8819

• Loosen screw terminals, insert stripped wire and

B – Reversing valve for heat2

B+ A+ B- A- C B O Y Y2 G RC RH W2 W R S2 S1 T1 T2 RSB RSA

Two transformers (Remove Jumper Wire)

re-tighten..

O – Reversing valve for cool2

• Push the excess wire back into the opening and plug

Y – 1st stage cooling / compressor or dehumidifier3

the wall opening to prevent drafts.

Y2 – 2nd stage cooling / compressor

Note: If the HVAC system was installed before the

G – Fan

automation system, the HVAC installer may have

 

powered the thermostat connecting a wire to the

RC – 24VAC supply cooling4

C terminal and installing a jumper wire from the R

RH – 24VAC supply heating4

terminal to RH or RC.. When used with an automation

W2 – 2nd stage heat / auxiliary / E-Heat

system, the R and C terminals on the Model 8800

W – 1st stage heat / auxiliary / E-Heat / humidifier3

thermostat should only be connected to the same

terminals on the 8819 or a dedicated 24VAC transformer.

S1 & S2 – outdoor temperature sensor (optional)

There should be no connection to the R or C terminals

T1 & T2 – remote temperature sensor (optional)

coming from the HVAC equipment.

RSA & RSB – 8081 or 8082 Support Module

 

 

communication (half duplex)5

1Refer to Aprilaire HVAC Automation System Installation Manual for communication wiring details.

COMMUNICATION

TERMINALS

NOT USED

NOT USED

 

 

 

 

 

 

COOLING

COOLING

FAN

1st

2nd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOLING TRANSFORMER

TRANSFORMER

HEATING

2nd HEATING 1st HEATING

THERMOSTAT IS POWERED FROM 8819 OR 24VAC

TRANSFORMER

OUTDOOR TEMP SENSOR

REMOTE TEMP SENSOR

SUPPORT

MODULE

2O and B terminals are both de-energized when system mode is OFF or in AUTO when the heating and cooling equipment is idle.

3When the unit is configured for humidistat mode.

4Jumper between RC & RH is used in single transformer systems (see wiring diagrams).

5Refer to Support Module literature for wiring details.

B+ A+ B- A- C B O Y Y2 G RC RH W2 W R S2 S1 T1 T2 RSB RSA

4

5

Image 3
Contents Table of contents Installation Conventional HEAT/COOL Humidistat DRY Contact Powered ContactThermostat is Powered Heat PumpSystem setting Description Setting range Setup & TestingEquipment Type Selection Switch SW1 Installer System Settings TableFactory default setting bold Installer System Settings TableScreen of the first test step is displayed How to enter the system test menuSystem test menu System Test TablesHumidistat Quick Reference to controls & DisplayHome Screen Main MenuTroubleshooting Thermostat FeaturesError Codes SpecificationsError code Message Error Description Aprilaire a division of Research Products Corporation
Related manuals