TROUBLESHOOTING – HEATING OPERATION
| Symptom | Cause | |
| 
 | 
 | |
| Thermostat does not call for heat | ||
| HEAT and make a call for heat. | ||
| 
 | ||
| 
 | 
 | |
| Heating does not come on at all | RH terminal not connected – see wiring diagrams. | |
| 
 | ||
| Heating equipment power not on. | ||
| 
 | ||
| Auxiliary Heat does not come on | High Balance point limit – set balance point higher than outdoor temperature | |
| or disconnect outdoor temperature sensor during system checkout. | ||
| 
 | ||
| 
 | Furnace plenum sensor keeps fan on – normal. | |
| 
 | 
 | |
| Fan stays on after heat call | Blower Extension for humidifier operation. Verify that the message | |
| "HUMIDIFYING" appears at the message center, alternating with the time | ||
| 
 | ||
| 
 | and date and any other currently active messages. | |
| Fan comes on before heat starts, or | Change position of ELEC/GAS dip switch – ELEC for electric heat systems | |
| (fan on with heat call) or to GAS for fossil fuel systems where the fan is | ||
| Fan does not come on with heat | ||
| controlled internally by the heating equipment. | ||
| 
 | ||
| 
 | 
 | |
| Cooling comes on instead of heat | Reversing valve wiring. | |
| 
 | ||
| Miswiring – check wire colors at thermostat and HVAC equipment. | ||
| 
 | ||
| Takes longer than 4 minutes for auxiliary | SINGLE/MULTI dip switch set incorrectly – set to SINGLE for  | |
| heat to come on after compressor heat. | compressor systems. | |
| 
 | 
 | 