Breckwell P2000I, P2000FS owner manual Thermostat Installation, Optional Thermostat, Modes

Page 17

THERMOSTAT INSTALLATION

OPTIONAL THERMOSTAT

A thermostat may help you maintain a constant house temperature automatically. A millivolt thermostat is required. A fixed wall mount or Breckwell’s hand held model can be used. The control panel can be set up two ways to operate your stove in thermostat mode.

THERMOSTAT INSTALLATION

A MILLIVOLT THERMOSTAT IS REQUIRED.

Unplug stove from power outlet.

Remove control board from stove.

The two thermostat wires connect to the terminal block on the lower left side of the back of the control board.

(See figure 21)

Insert the wires in the terminal side and tighten the two screws.

MODES

TO SWITCH BETWEEN ANY OF THE THREE MODES THE

STOVE MUST BE SHUT OFF, THE NEW MODE SELECTED, AND

THE STOVE RESTARTED.

MANUAL MODE

In this mode the stove will operate only from the control panel as detailed in the “OPERATION” section of this owner’s manual.

HIGH/LOW THERMOSTAT MODE

When engaged in this mode the stove will automatically switch between two settings. When warm enough, it will switch to the #1 or low setting. The room air blower will also slow to its lowest speed.

The Heat Level Advance setting on the bar graph will stay where it was initially set. When the house cools below the thermostat setting, the stove will switch to the feed rate of the heat level advance setting.

ON/OFF THERMOSTAT MODE

In this mode when the home is warm enough the stove will shut off. The fans will continue to run until the stove cools.

When the home cools below the thermostat setting, the stove will automatically restart and run at the last feed rate setting.

NOTE: When in “high/low” or “on/off” thermostat mode –

Do not operate the stove higher than the #3 setting.

Set damper control rod approximately ½” to ¾” out. This will vary depending on elevation and weather conditions. Observe stoves operation and adjust damper as necessary.

FIGURE 21

17

Image 17
Contents Luxury Series P2000 Introduction Mail Your Warranty Card TodaySafety Precautions Table of Contents Installation Combustion AIR Supply When Outside AIR is not UsedVenting Rear View P2000FS Rear View P2000IHorizontally Through Wall Freestanding InstallationEquivalent Vent Length EVL Vertically Into Existing Chimney System Vertically with NEW Chimney System Refer to FigureVertically Into Existing Masonry Fireplace Installation Through Side of Masonry ChimneyAssembling the Flashing SET Insert InstallationsWhen Vent Pipe Extends to Chimney TOP Refer to Figure AS a BUILT-IN Fireplace Chase dimensions shown are minimums and must be maintainedSpecial Mobile Home Requirements Electrical InstallationOperation PRE-START-UP Check Proper FuelBuilding a Fire Hotrod Automatic FirestarterShutdown Procedure Breckwell Maintenance ToolSafety Features RE-STARTING a Warm StoveThermostat Installation Thermostat InstallationOptional Thermostat ∙ a Millivolt Thermostat is RequiredPlease Read this ASH Removal MaintenanceASH Disposal Freestanding Models ASH Disposal InsertBlowers CleaningVacuum USE Recommended Maintenance Schedule Chimney CleaningRemoval and Replacement of Broken Door Glass Daily Weekly Annually or per TonP2000I Possible Causes Troubleshooting GuideStove Shuts OFF and the # 2 Light Flashes Stove Shuts OFF and the # 3 Light Flashes Possible Causes Possible Remedies Stove Feeds PELLETS, but will not IgniteSmoke Smell Coming Back Into the Home Convection Blower Shuts OFF and Comes Back onTroubleshooting Guide Troubleshooting Guide Smoke Smell or Soot BUILD-UP High Limit Switch Keeps TrippingDigital Circuit Board Timing Rates P2000Electrical Diagram Burnpot Replacement PartsLifetime Limited Warranty
Related manuals
Manual 31 pages 19.42 Kb