CyberPower Systems OL6KRT2UTFHW Hardwiring the Input Terminals, Safety Precautions Check Wiring

Page 5

HARDWIRING THE INPUT TERMINALS

SAFETY PRECAUTIONS

CAUTION! Input and Output circuit breakers must be “OFF” during the building installation.

CAUTION! The OL6KRT2UTF and OL8K10KRT3UTF with power cord L6-30P DO NOT require hardwiring. Use the attached power cord to connect to the UPS outlet.

CAUTION! The OL6KRT2UTFHW and OL8K10KRT3UTFHW require them to be hard wired into the UPS. Only qualified maintenance personnel should perform this task.

CHECK WIRING

Check wiring dimensions with the following table.

Step-Down Transformers with hardwire

Wiring AWG

Wiring mm2

OL6KRT2UTFHW

10 AWG

5.5 mm2

OL8K10KRT3UTFHW

8 AWG

8.0 mm2

Step 1: Separate the top and bottom covers

Loosen the four screws to separate the top and bottom covers.

Step 2: Fix the bottom cover on the terminal block

Tighten the two screws to fix the bottom cover on the terminal block.

4

Copyright © 2011 CyberPower Systems, Inc.

Image 5
Contents User’s Manual Unpacking OverviewSafety Precautions Rackmount Installation Hardware InstallationHardware Installation Safety Precautions VERTICAL/TOWER InstallationRotate the Multifunction LCD Module Attach the base standsSafety Precautions Check Wiring Hardwiring the Input TerminalsSeparate the top and bottom covers Fix the bottom cover on the terminal blockInput configuration Hardwiring the INPUT/ Output TerminalsFix the top cover on the bottom cover STEP-DOWN Transformer FRONT/REAR Panel Description Basic OperationModel Technical SpecificationsConfiguration What Does This Warranty Cover? Who is Providing this Warranty?What is the Period of Coverage? How Do You Get Warranty Service?What Other Limitations Apply? Where Can I Get More Information?Who Pays For Shipping? Need Additional Help? Conformance ApprovalsFCC Notice

OL8K10KRT3UTFHW, OL6KRT2UTFHW, OL6KRT2UTF, OL8K10KRT3UTF specifications

CyberPower Systems offers a powerful lineup of uninterruptible power supplies (UPS) designed to protect critical equipment from power disturbances. The OL8K10KRT3UTF and OL6KRT2UTF, OL6KRT2UTFHW, and OL8K10KRT3UTFHW models are engineered to deliver reliable performance, ensuring that sensitive devices remain operational during outages.

The OL8K10KRT3UTF model is a robust UPS that provides 8,000 to 10,000 VA of power. It is designed for high-demand environments such as data centers and telecom applications. One of its notable features is the Smart App Sinewave output, which delivers pure sine wave power to connected devices, ensuring compatibility and optimal performance for sensitive electronics. This model also includes an LCD panel that provides real-time status updates on battery health, load capacity, and operational modes, allowing users to monitor performance easily.

The OL6KRT2UTF and OL6KRT2UTFHW models are similarly engineered for versatility and efficiency, offering 6,000 VA of power in a compact design. The OL6KRT2UTFHW version includes additional features for high-temperature environments, making it suitable for locations with less control over ambient conditions. Both models come equipped with advanced communication ports for seamless integration with existing systems. They support various connection types, such as USB, RS-232, and optional SNMP, enabling remote management and monitoring for critical systems.

Key technologies employed across these UPS models include automatic voltage regulation (AVR), which stabilizes voltage fluctuations, thereby protecting sensitive equipment from damage. Additionally, these models feature a high-efficiency design that reduces energy consumption and operational costs, benefiting both the environment and the organization's bottom line.

CyberPower's UPS systems utilize high-capacity, maintenance-free sealed lead-acid batteries that provide extended runtime capabilities. This ensures that connected devices stay powered on during outages or fluctuations, minimizing downtime and protecting data integrity.

In conclusion, the CyberPower Systems OL8K10KRT3UTF, OL6KRT2UTF, OL6KRT2UTFHW, and OL8K10KRT3UTFHW models represent a strong commitment to reliability and innovation in power management. With their advanced features, robust design, and efficient technologies, they serve as vital components for any mission-critical infrastructure requiring consistent power protection.