Page 5

This product is not approved for manufactured homes (mobile home), recreational vehicles (RV) or boats. Reference ANSI Z21.10.3.

This product is neither designed or approved for outside installations.

COMBUSTION AIR REQUIREMENTS

The AquaStar water heater holds cold water in its copper heat exchanger and water valve when not in use. Because of this, any cold air that comes in through the unit’s vent pipe is capable of freezing these components. This Installation Manual specifies the minimum vertical vent pipe and the amount of combustion air required for this unit. The vent pipe must not be restricted and its 6 foot minimum height (provided there are no elbows) must terminate 2 feet above any obstruction within a 10 foot radius.

When all requirements are followed, the unit will operate properly and safely. However, there may still be a risk of freezing due to negative draft if all the combustion appliances in the area are not being supplied with a sufficient amount of make-up air. A wood stove or furnace can rob the make- up air in the AquaStar’s vent pipe, leaving the cold infiltrating air capable of freezing the cold water in the AquaStar heat exchanger. More make up air is the solution. Follow the instructions on venting and checking adequacy of make up air. A HVAC specialist should be used to design solutions for providing more make-up air if necessary.

Observe the following instructions concerning combustion air.

Appliances located in unconfined spaces:

a)An unconfined space is one whose volume is greater than 50 cubic feet per 1000 Btu per hour of the combined rating of all appliances installed in the space.That would be 5850 cubic feet for the AquaStar 125HX alone.

b)In unconfined spaces in buildings of conventional frame, masonry, or metal construction, infiltration is normally adequate to provide air for combustion, ventilation, and dilution of flue gasses.

Appliances located in confined spaces:

The confined space must be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. Each opening must have a minimum free area of one square inch per:

-1000 Btu/hr if all air is taken from inside the building.

-2000 Btu/hr if all air is taken from the outside by horizontal ducts.

-4000 Btu/hr if all air is taken from the outside by direct openings or vertical ducts.

Or the confined space must be provided with one permanent opening or duct that is within 12 inches of the ceiling of the enclosure. This opening must have a minimum free area of one square inch per:

-3000 Btu/hr if all air is taken from the outside by a direct opening or vertical duct.

Louvers, grills and screens have a blocking effect. If the effective free area is not known, increase the sizes of your openings by 75% if your louvers are wood and by 30% if your louvers are metal. Refer to the National Fuel Gas Code for complete information. In buildings of tight construction all air should be taken from outside.

CLEARANCES

The Aquastar 125 HX is design certified for installation on a combustible wall and for installation in an alcove or closet with the minimum clearances to combustible and non - combustible construction listed below

A.Top 12 inches (306 mm)

B.Front 4 inches (102 mm)

C.Back 0 inches

D.Sides 4 inch (102mm)

E.Bottom 12 inches (306 mm)

Clearance from vent is dependent upon the clearance rating of the venting material used. For example: type B-1 vent is approved for 1 inch clearance.

Note: Minimum clearance to combustible materials should not be less than 6" for single wall flue pipe. Note that this clearance can be reduced if combustible material are protected as per table VI of the National fuel Gas Code or if Type B gas vent is used.

MOUNTING INSTALLATION

The Aquastar 125 HX is design certified for mounting on a wall.

Secure the two L shaped hooks provided with the heater to a wall surface. Place them 13 ¼ inches apart as shown in Fig 1.

Do not install this appliance on a carpeted wall or over floor covering which is combustible, such as carpet. The heater must be mounted on a wall using appropriate anchoring materials. If wall is a stud wall sheathed with plasterboard, it is recommended that support board(s), either 1x4’s or 1/2" (minimum) plywood first be attached across a pair of studs and then the heater should be attached to the support boards. See Fig 1.

Expansion and contraction of piping due to changing water temperature in the pipes imparts movement to the heater which, if mounted directly to a brittle, friable board, such as plasterboard, can cause failure of mounting.

In earthquake-prone zones, CEC recommends that installers use a large washer and lag screw through the existing holes used to hang the heater to affix the upper third of the heater to the mounting board. To affix the lower third of the heater, CEC recommends that two new holes be drilled in the heater’s frame, each one 16 inches below the top two holes, and that washers and lag screws be used to secure the lower portion of the heater to a spacing board.

Before installing the unit, be certain you have the correct heater for your type of Gas – Propane or Natural Gas. Identification labels are found on the shipping box, and on the rating plate which is located on the right side panel of the cover. Also, each burner orifice is stamped with a number (79 for LPG and 120 for Natural Gas).

6 720 606 804 (02.10)

5

Image 5
Contents What to do if YOU Smell GAS For Your SafetyTable of Contents AquaStar 125HX LP and 125HX NG Specifications FeaturesUnpacking the Aquastar Heater Principle of OperationAquastar Model 125HX Water is being used do not Install in AN Area Proper Location for Installing Your HeaterWhere IT could Freeze General Rules to Follow For Safe OperationClearances Mounting InstallationCombustion AIR Requirements To check the draft VentingAltitude Natural Gas Liquid Propane Maximum Inlet GAS Flow Pressure SettingGAS Line Sizing For LP GAS For Natural GASOperating Instructions For Your Safety Read Before Operating Your HOT Water HeaterWater Connections Lighting and Operating Instructions Setting the Water TemperatureTo Turn OFF GAS to Appliance OffTrouble Shooting Maintenance and ServiceReview Maintenance Table on the Back of this Manual To clean the pilot burner and/ or the pilot orifice TurnNo Spark AT the Pilot Main Burners GO OUT During HOT Water USE Pilot Lights but Burners will not Come onWater is TOO HOT Water is not HOT EnoughGas pressure is too low HOT Water Temperature FluctuatesUnbalanced pressure in waterlines Diagram of AquaStar 125 HX Interior Components Diagram and Parts List Interior Components Diagram Parts List 125HX 720 606 804 720 606 804 Controlled Energy Corp Installation Checklist GAS Line Size

125HX NG specifications

Bosch Appliances has long been synonymous with innovation and quality, and their 125HX NG model is no exception. Designed for home cooks and culinary enthusiasts alike, the Bosch 125HX NG is a natural gas cooktop that combines state-of-the-art features with unmatched performance.

One of the standout features of the Bosch 125HX NG is its five powerful burners, which offer flexibility for various cooking techniques. These burners include a high-heat burner perfect for searing meats and achieving high-temperature cooking, along with a simmer burner designed for those delicate sauces and slow cooking tasks. The configuration of the burners allows for multiple pots and pans to be used simultaneously, maximizing efficiency and convenience in the kitchen.

The surface of the cooktop is constructed from premium stainless steel, offering not only a sleek aesthetic but also durability that withstands the rigors of daily cooking. The seamless design facilitates easy cleaning, ensuring that spills and stains can be wiped away with minimal effort.

Technology plays a key role in the Bosch 125HX NG model, featuring precise temperature control and rapid ignition systems. The automatic re-ignition feature enhances safety, ensuring that the flame is reignited if it goes out unexpectedly, providing peace of mind to users while cooking.

Another notable characteristic is the cooktop’s continuous grates, which provide stability for pots and pans, allowing for effortless sliding between burners without the risk of spills. These heavy-duty grates contribute to the overall robustness of the cooktop, reinforcing Bosch’s commitment to functional design.

In terms of installation, the Bosch 125HX NG is compatible with various kitchen layouts, making it a versatile choice for both new builds and remodels. The model is also designed with energy efficiency in mind, helping homeowners to save on gas consumption while enjoying consistent cooking results.

Overall, the Bosch Appliances 125HX NG is a sophisticated and reliable natural gas cooktop that caters to the needs of modern cooking. With its array of features, advanced technologies, and high-quality materials, it's a perfect addition to any kitchen, appealing to both amateur cooks and seasoned chefs. Investing in a Bosch 125HX NG means enjoying durability, functionality, and style in one exceptional cooking appliance.