Bradford-White Corp Commercial Electric Water Heaters, 900kW Start-Up, Initial START-UP Checks

Page 23

CAUTION: The power supply must remain off until the water heater and all related piping are completely filled with water to insure that there will not be a possible problem with heating element burn out.

6.While the tank is filling, open the electrical control panel and set the thermostat(s) to the desired water temperature. If equipped with multiple thermostats, all individual thermostats may be adjusted to the same temperature set point or they may be set a 2°F to 4°F (1˚C to 2˚C) apart to step the elements on in stages.

7.Insure that any pilot switches or manual limiting switches are placed in the “ON” position.

8.When a constant flow is obtained at the faucet, it may be turned off. The temperature and pressure relief valve should be manually opened to insure that there is no captive air in the storage tank. A constant stream of water must flow from the manually opened relief valve. Release the handle on the relief valve and allow it to close after water flow is observed.

9.Carefully check the tank, pipe and fittings for any sign of a water leak. Immediately repair as needed. Open the access door to the immersion heating elements and check for leaks at the element mounting flanges. If any leak is detected, tighten the screw–in element.

START-UP

10.Insure that the electrical access panel (field wiring compartment) is closed and the heating element access panel is in place before proceeding.

11.After assuring that the tank is completely filled with water and no leaks are detected, you are now ready to start operation of the water heater.

12.Turn on the electric power at the main disconnect point. The contactors should be energized as the elements start to heat the water in the tank.

13.As the water heater starts heating, check the contactors for “buzzing” or “chattering” during operation. If noise is detected, turn off main power, open the control panel and clean the contact points of the magnetic contactor(s). Remove any dust, dirt or foreign matter that may have found its way into the contactor or other electrical components in the control panel during shipping, installation or service.

14.Close the electrical control panel and turn on main power.

15.The water heater is now ready for normal operation.

INITIAL START-UP CHECKS

The following checks should be made by the installer when the water heater is placed into operation for the first time.

WARNING:

HAZARD OF ELECTRICAL SHOCK – Before opening the access panel to perform service on any electrical component, make sure the electrical supply to the water heater is turned “OFF”. Failure to do this could result in death, serious bodily injury or property damage.

1.Allow the water heater to heat for approximately thirty minutes after following the filling and start up procedures.

2.Turn off the main electrical power to the water heater. If the power disconnect point is out of sight, lock it in the open (“OFF”) position and tag to prevent unexpected application of power.

3.Open the electrical control panel door and feel each wire connection and fuse clip for excessive temperature. If any connection is found to be excessively hot, check the tightness of the connection. Check all factory internal wiring connections and the field made main power connections for tightness.

23

Image 23
Contents Checking Equipment WarrantyCHP-I&S-01 Special Instructions To OwnerContents Front View Vertical Round Models Approvals Installation Procedure Location of UnitOwner Warning CodesPage Table a Clearances from Combustible Construction Clearances from Combustible ConstructionWater Connections MountingDo not plug or cap the relief valve Storage TankRelief Valve Thermal Expansion of WaterElectrical Connections Cathodic ProtectionStandard Equipment Jacket AssemblyNever turn on the electric Terminal Block Optional Equipment Components and ControlsControl Circuit Transformer Fuse and Flue BlocksContactors Hotter water increases Temperature RegulationWater Temperature Settings Immersion ThermostatsElectronic Temperature Control Sequencer Temperature AdjustmentMaximum temperature Select and Enter Keys simultaneously SpecificationsOperating Ambient Temperature -30 to 125 F Operating Humidity 5 95% RHProgramming Worksheet Setup of the Temperature ControllerDisplay Programming When power is initiallyHigh Water Temperature Limit Control Immersion Heating Element Disconnect the main powerHigh Water Pressure Switch LOW Water Pressure SwitchTime Clock Optional Filling the Water Heater START-UP ProcedureLeft in the open position when the water heater is in use Initial START-UP Checks START-UPDraining the Water Heater Shutdown ProcedureMaintenance Temperature and Pressure Relief Valve OperationSediment and Lime Scale Removal Water ChemistryFlushing the Storage Tank Sediment RemovalGaskets are available from your distributor Trouble Shooting If YOU Cannot Identify or Correct the Source Malfunction

9kW, 900kW, Commercial Electric Water Heaters specifications

Bradford-White Corporation has established itself as a leader in the water heating industry, providing a diverse range of innovative and efficient water heating solutions. Among its prominent offerings are the 900kW and 9kW Commercial Electric Water Heaters. These models have been designed for a variety of commercial applications, ensuring reliability, performance, and energy efficiency.

The 900kW Commercial Electric Water Heater is specifically engineered for large-scale applications that require significant hot water outputs. This powerhouse can effectively support high-demand environments such as hotels, restaurants, and industrial facilities. One of its standout features is its high-efficiency design, which maximizes hot water production while minimizing operational costs. The heater employs advanced technology to increase thermal efficiency, which in turn reduces energy consumption and lowers utility bills.

This model also features a robust heating element configuration that ensures rapid recovery rates. With multiple heating elements strategically placed within the tank, the 900kW unit can maintain consistent water temperatures even during peak usage hours. Additionally, it is equipped with advanced controls that facilitate precise temperature management, further enhancing user convenience and system performance.

On the other side, the 9kW Commercial Electric Water Heater is ideal for smaller businesses or applications where space and hot water demand are more constrained. This model is compact yet powerful, capable of efficiently delivering hot water for various tasks such as handwashing, cleaning, and food preparation. Its compact design allows for flexible installation options, making it suitable for tight spaces without compromising performance.

Both models incorporate corrosion-resistant tank materials and durable insulation to ensure longevity and reliable operation over time. The integrated safety features, including high-temperature limit switches and automatic shut-off mechanisms, provide users with peace of mind regarding operational safety.

Furthermore, Bradford-White prioritizes sustainability in its product lines. Both the 900kW and 9kW Commercial Electric Water Heaters comply with stringent efficiency regulations, making them eco-friendly options for businesses looking to reduce their carbon footprint.

In summary, Bradford-White’s 900kW and 9kW Commercial Electric Water Heaters represent the perfect fusion of performance, efficiency, and reliability, catering to diverse commercial needs while promoting sustainability and cost-effectiveness in water heating solutions.