A.O. Smith BFC -100, BFC - 80 Connecting the mains voltage, Isolating transformer, Preparation

Page 34

3

Installation

is

 

In preparation, you must first remove the two plastic covers and the protective cap of the electrical section.

1.Undo the screws of the plastic covers.

2.Carefully remove the covers from the appliance. The electrical section is now visible.

3.Loosen the 2 screws (A) of the electrical section, and remove the protective cap (B) from the electrical section.

The connector block (C) is now visible.

Note

Consult the table for the connections and consult the electrical diagram for the electrical component connections.

Electrical connector block

 

Circulation

Frequency

Tank

Program-

 

 

 

 

 

 

 

 

 

 

 

 

Mains

 

 

controlled

Alarm Off

 

Isolating transformer

 

 

 

 

 

pump

 

controller

 

ON

 

 

voltage

 

 

 

 

 

pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

primary

secondary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

L5

 

N

 

L4

N

X3

X4

N

L3

 

 

X1

X2

 

N

L2

 

N

L1

 

 

L

N

 

 

1

2

 

3

 

4

5

6

7

8

 

9

10

 

11

 

12

13

14

15

16

 

17

18

19

20

 

21

22

 

23

 

24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.10.3Connecting the mains voltage

The appliance is supplied without a power cable and isolator.

Note

In order to receive electrical power, the appliance has to be connected to the mains power by means of a permanent electrical connection. A double-pole isolator with a contact gap of at least 3 mm must be fitted between this permanent connection and the appliance. The power cable must have cores of at least 3 x 1.0 mm2.

Warning

Leave the appliance isolated until you are ready to start it up.

1.Connect phase (L), neutral (N) and earth () of the power cable to terminals 22 through 24 of the connection block as indicated in the

table (3.10.2 "Preparation").

2.Fit the power cable in the strain relief.

3.Connect the power cable to the isolator.

4.If you have no more connections to make:

-Fit the cap on the electrical terminal block.

-Fit the plastic covers onto the appliance.

3.10.4Isolating transformer

An isolating transformer should be used if there is a case of 'floating neutral'.

1.Refer to fitting instructions provided with the isolating transformer. (Contact the supplier for details of the correct isolating transformer.)

2.Connect phase (L), neutral (N) and earth () to terminals 16 through 21 of the terminal block as stated in the table (3.10.2 "Preparation").

3.Fit the cables in the strain relief.

34

Instruction manual BFC

Image 34
Contents 100 Your installer Liability Read this manual carefullyTrademarks More informationGis Table of contents Maintenance frequency Service programTroubleshooting Performing maintenanceAppendices Table of contents About the appliance IntroductionWhat to do if you smell gas Regulations Symbol Target group Target groups Maintenance Forms of notationIntroduction Document Overview of thisChapter Target groups Description Gis Working principle of the appliance General working principle of the applianceAppliances heating cycle Protection for the appliance Water temperature protection TheGas valveWorking principle of the appliance Gas valve Water temperature protectionPressure switch 4 FanVented installation Safety of the installationUnvented installation Flame probeEnvironmental InstallationPackaging ConditionsWater composition Air humidity and ambient temperatureMaximum floor load Working clearancesTechnical specifications Dimensions of the appliance Dimen Description BFC Sion General and electrical specificationsUnit BFC Gas data Description II2H3P Unit BFC Natural gasInstallation diagram Hot water side Water connections, VentedCold water side Circulation pipeWater connections, Unvented Air supply and flue Introduction Gas connectionRequirements for flue gas discharge materials C43 B23 C33 C13 C53 Type of appliance Description Concentric connectionsPractical example of concentric flue gas discharge Appliance Diameter Maximum length Number BendsSpecifications Appliance with concentric flue gas discharge materialConcentric wall flue terminal specifications C13 Subject DescriptionParallel connections Practical example of parallel flue gas dischargePreparation Connecting the mains voltage Electrical connectionPreparation Isolating transformer Connecting the mains voltage10.2 Preparation Connecting an extra error signal Alarm OUT Connecting a program-controlled pumpConnecting an extra on mode switch Tank on Checking the supply pressure and burner pressureProcedure to check pressures 11.1Gas data Finalising Adjusting the pressure11.3 Finish off 3.11.4 FinalisingOrifice assembly Conversion to a different gas categoryConversion to a different gas category Start 9 Starting and running the applianceInstallation diagram FillingFilling the appliance Filling unvented installationsFilling vented installations FillingDraining Draining Min Gis Controls Electronic controller ON/OFF switchControl panel Meaning of iconsPC connection Control panelStatus of the appliance Operating modes Error conditions Service conditionOperating modes Status of the appliance Error conditionsManual 13 Troubleshooting Menu 11 Main menu chapterService condition Manual 14 Maintenance frequencyGis Appliances heating cycle Open 3.5 Installation diagram the manual gas valveStarting and running Starting and running Appliances heating cycleStarting and running Electrically isolating the appliance Shut the appliance down for a brief period OFF modeShutting down Shutting the appliance down for a long periodShutting down Main menu Switching on the on modeSetting water temperature during on mode Notational convention for menu-related instructionsChanging the appliances standard week program Week program setting the switch- on timeStarting and stopping the week program Main menuWeek program setting the program- controlled pump Week program setting the switch- off timeWeek program setting the water temperature Adding times to a week programPump 11.6.4 Week program setting the program-controlled pump Deleting times from a week programExtra period Setting the switch-on timeProgramming an extra period Settings Setting menu languageSetting day and time Displaying appliance specificationsRelevant display appears Setting the hysteresis Service programDisplaying the error history Setting the display contrast Switching the pump on or offSetting the service interval Setting the display backlight timeGeneral errors TroubleshootingDisplayed errors Display is off Troubleshooting table for general errorsSymptom Cause Solution Remark Gas smell Start the appliance up 9 Starting and runningHot water supply Symptom Cause Solution Remark Water leakageExplosive ignition Insufficient or absentDisplayed errors S14 blocking error Code + Description Cause Solution Remark S12 blocking errorS13 blocking error S15 blocking errorCode + Description Cause Solution Remark F02 lock out error Code + Description Cause Solution Remark Check the values 2.4.5 Pressure switchReplaced Appliance Code + Description Cause Solution Remark F03 lock out errorMaintenance 15.2 Preparation for maintenance. If there is FlueCode + Description Cause Solution Remark F04 lock out error F05 lock out errorF08 lock out error Code + Description Cause Solution Remark F06 lock out errorF07 lock out error F09 lock out errorCode + Description Cause Solution Remark F10 lock out error F11 blocking errorC04 blocking error Code + Description Cause Solution Remark C02 lock out errorC03 blocking error Selected applianceE03 lock-out error Code + Description Cause Solution Remark E01 blocking errorE04 lock-out error Maintenance frequency IntervalMaintenance frequency Performing maintenance Introduction Preparation for maintenancePerforming maintenance Descaling and cleaning the tank Water-side maintenance IntroductionChecking the anodes Clean the burners Cleaning condensation water dischargeGas-side maintenance Finalizing maintenance Introduction Clean the orifices16.2 Tank warranty Warranty certificate16.1 General warranty Conditions for Installation and useWarranty certificate Appendices Week program cardBFC Electrical Diagram AppendicesTerminal Block Connections Appendices Tset Pump Week program cardPeriod Example PeriodPage Index 0308 Index

BFC - 80, BFC -100 specifications

A.O. Smith is a renowned name in the water heater industry, and its BFC series, which includes the BFC-100 and BFC-80 models, exemplifies their commitment to innovation and efficiency. These units are designed to meet the demanding needs of both residential and commercial applications, providing reliable hot water solutions.

The A.O. Smith BFC-100 and BFC-80 are distinguished by their high capacity and robust design. The BFC-100 model boasts a capacity of 100 gallons, while the BFC-80 is ideal for those requiring 80 gallons. This makes them suitable for larger households or commercial establishments where hot water demand can be significant.

One of the primary features of these models is their advanced heating technology. Both units utilize a high-efficiency burner that ensures rapid heating and minimal energy consumption. This means users benefit from shorter wait times for hot water, reducing overall energy costs. The BFC series is also equipped with a special flame retention head that enhances combustion efficiency and prolongs the lifespan of the unit.

In terms of construction, the BFC-100 and BFC-80 models are built with high-quality materials that enhance durability and resistance to corrosion. The tanks are insulated with high-density foam, which improves energy retention and helps maintain water temperature for longer periods. This is crucial for conserving energy and minimizing heating costs.

Safety is a top priority for A.O. Smith, and the BFC series reflects this commitment. Each unit comes with a range of safety features, including a temperature and pressure relief valve that prevents overheating and excessive pressure buildup. Additionally, they are designed to meet strict industry standards, ensuring peace of mind for users.

Installation of both models is straightforward, with flexible venting options that accommodate various building layouts. Whether you are upgrading an existing water heating system or installing a new one, the BFC series is designed to integrate seamlessly.

In summary, the A.O. Smith BFC-100 and BFC-80 are excellent options for those seeking reliable, efficient, and durable water heating solutions. With their impressive capacity, advanced heating technology, robust construction, and safety features, these models stand out in the market and are sure to meet the hot water needs of any household or commercial space. Whether for residential use or in a business setting, A.O. Smith’s BFC series represents quality and innovation in hot water heating.