A.O. Smith BFC -100, BFC - 80 service manual Conversion to a different gas category

Page 40

4

Conversion to a different gas category

is

 

5.Detach the 3-part gas coupling (2) adjacent to the burner.

6.Select and fit the correct orifice from the conversion kit, based on the gas table (3.4.3 "Gas data"). The injector diameter is stamped into each injector

(6).

7.Refit the 3-part gas coupling (2).

8.Check the burner pressure and supply pressure (3.11 "Checking the supply pressure and burner pressure").

9.Replace the cover.

10.Remove the sticker showing the new gas category from the conversion kit, and attach it below the appliance's rating plate. This clearly indicates that the appliance may no longer be run on the gas for which it was originally supplied.

11.Start (9 "Starting and running") the appliance.

40

Instruction manual BFC

Image 40
Contents 100 Your installer Read this manual carefully TrademarksLiability More informationGis Table of contents Service program TroubleshootingMaintenance frequency Performing maintenanceAppendices Table of contents About the appliance IntroductionWhat to do if you smell gas Regulations Symbol Target group Target groups Maintenance Forms of notationIntroduction Document Overview of thisChapter Target groups Description Gis Working principle of the appliance General working principle of the applianceAppliances heating cycle Protection for the appliance Water temperature protection TheGas valveWorking principle of the appliance Water temperature protection Pressure switchGas valve 4 FanSafety of the installation Unvented installationVented installation Flame probeInstallation PackagingEnvironmental ConditionsAir humidity and ambient temperature Maximum floor loadWater composition Working clearancesTechnical specifications Dimensions of the appliance Dimen Description BFC Sion General and electrical specificationsUnit BFC Gas data Description II2H3P Unit BFC Natural gasInstallation diagram Water connections, Vented Cold water sideHot water side Circulation pipeWater connections, Unvented Air supply and flue Introduction Gas connectionRequirements for flue gas discharge materials C43 B23 C33 C13 C53 Concentric connections Practical example of concentric flue gas dischargeType of appliance Description Appliance Diameter Maximum length Number BendsSpecifications Appliance with concentric flue gas discharge materialConcentric wall flue terminal specifications C13 Subject DescriptionParallel connections Practical example of parallel flue gas dischargePreparation Connecting the mains voltage Electrical connectionPreparation Isolating transformer Connecting the mains voltage10.2 Preparation Connecting a program-controlled pump Connecting an extra on mode switch Tank onConnecting an extra error signal Alarm OUT Checking the supply pressure and burner pressureProcedure to check pressures 11.1Gas data Adjusting the pressure 11.3Finalising Finish off 3.11.4 FinalisingOrifice assembly Conversion to a different gas categoryConversion to a different gas category Start 9 Starting and running the applianceInstallation diagram FillingFilling unvented installations Filling vented installationsFilling the appliance FillingDraining Draining Min Gis Electronic controller ON/OFF switch Control panelControls Meaning of iconsPC connection Control panelStatus of the appliance Operating modes Error conditions Service conditionOperating modes Error conditions Manual 13 TroubleshootingStatus of the appliance Menu 11 Main menu chapterService condition Manual 14 Maintenance frequencyGis Open 3.5 Installation diagram the manual gas valve Starting and runningAppliances heating cycle Starting and running Appliances heating cycleStarting and running Shut the appliance down for a brief period OFF mode Shutting downElectrically isolating the appliance Shutting the appliance down for a long periodShutting down Switching on the on mode Setting water temperature during on modeMain menu Notational convention for menu-related instructionsWeek program setting the switch- on time Starting and stopping the week programChanging the appliances standard week program Main menuWeek program setting the switch- off time Week program setting the water temperatureWeek program setting the program- controlled pump Adding times to a week programPump 11.6.4 Week program setting the program-controlled pump Deleting times from a week programExtra period Setting the switch-on timeProgramming an extra period Settings Setting menu languageSetting day and time Displaying appliance specificationsRelevant display appears Setting the hysteresis Service programDisplaying the error history Switching the pump on or off Setting the service intervalSetting the display contrast Setting the display backlight timeGeneral errors TroubleshootingDisplayed errors Troubleshooting table for general errors Symptom Cause Solution Remark Gas smellDisplay is off Start the appliance up 9 Starting and runningSymptom Cause Solution Remark Water leakage Explosive ignitionHot water supply Insufficient or absentDisplayed errors Code + Description Cause Solution Remark S12 blocking error S13 blocking errorS14 blocking error S15 blocking errorCode + Description Cause Solution Remark F02 lock out error Code + Description Cause Solution Remark Check the values 2.4.5 Pressure switchReplaced Code + Description Cause Solution Remark F03 lock out error Maintenance 15.2 Preparation for maintenance. If there isAppliance FlueCode + Description Cause Solution Remark F04 lock out error F05 lock out errorCode + Description Cause Solution Remark F06 lock out error F07 lock out errorF08 lock out error F09 lock out errorCode + Description Cause Solution Remark F10 lock out error F11 blocking errorCode + Description Cause Solution Remark C02 lock out error C03 blocking errorC04 blocking error Selected applianceE03 lock-out error Code + Description Cause Solution Remark E01 blocking errorE04 lock-out error Maintenance frequency IntervalMaintenance frequency Performing maintenance Introduction Preparation for maintenancePerforming maintenance Descaling and cleaning the tank Water-side maintenance IntroductionChecking the anodes Cleaning condensation water discharge Gas-side maintenance Finalizing maintenance IntroductionClean the burners Clean the orificesWarranty certificate 16.1 General warranty16.2 Tank warranty Conditions for Installation and useWarranty certificate Appendices Week program cardBFC Electrical Diagram AppendicesTerminal Block Connections Appendices Week program card PeriodTset Pump Example PeriodPage Index 0308 Index

BFC - 80, BFC -100 specifications

A.O. Smith is a renowned name in the water heater industry, and its BFC series, which includes the BFC-100 and BFC-80 models, exemplifies their commitment to innovation and efficiency. These units are designed to meet the demanding needs of both residential and commercial applications, providing reliable hot water solutions.

The A.O. Smith BFC-100 and BFC-80 are distinguished by their high capacity and robust design. The BFC-100 model boasts a capacity of 100 gallons, while the BFC-80 is ideal for those requiring 80 gallons. This makes them suitable for larger households or commercial establishments where hot water demand can be significant.

One of the primary features of these models is their advanced heating technology. Both units utilize a high-efficiency burner that ensures rapid heating and minimal energy consumption. This means users benefit from shorter wait times for hot water, reducing overall energy costs. The BFC series is also equipped with a special flame retention head that enhances combustion efficiency and prolongs the lifespan of the unit.

In terms of construction, the BFC-100 and BFC-80 models are built with high-quality materials that enhance durability and resistance to corrosion. The tanks are insulated with high-density foam, which improves energy retention and helps maintain water temperature for longer periods. This is crucial for conserving energy and minimizing heating costs.

Safety is a top priority for A.O. Smith, and the BFC series reflects this commitment. Each unit comes with a range of safety features, including a temperature and pressure relief valve that prevents overheating and excessive pressure buildup. Additionally, they are designed to meet strict industry standards, ensuring peace of mind for users.

Installation of both models is straightforward, with flexible venting options that accommodate various building layouts. Whether you are upgrading an existing water heating system or installing a new one, the BFC series is designed to integrate seamlessly.

In summary, the A.O. Smith BFC-100 and BFC-80 are excellent options for those seeking reliable, efficient, and durable water heating solutions. With their impressive capacity, advanced heating technology, robust construction, and safety features, these models stand out in the market and are sure to meet the hot water needs of any household or commercial space. Whether for residential use or in a business setting, A.O. Smith’s BFC series represents quality and innovation in hot water heating.