Tableau des plages acceptables pour les niveaux des gaz de combustion

Échantillons sans air

Plage acceptable

Dioxyde de carbone – gaz naturel : allure de chauffe maximale

De 8,0 à 9,5 %

Dioxyde de carbone – gaz propane : allure de chauffe maximale

De 8,5 à 10,0 %

Concentration de monoxyde de carbone

Moins de 200 ppm

 

 

Dioxyde de carbone – gaz naturel : allure de chauffe minimale

De 6,5 à 7,5 %

Dioxyde de carbone – gaz propane : allure de chauffe minimale

De 7,5 à 8,5 %

Concentration de monoxyde de carbone

Moins de 100 ppm

Si les niveaux des gaz de combustion se situent à l’extérieur des plages acceptables, suivre les directives données à la rubrique

Configuration du mode d’essai, et la marche à suivre pour les réglages de combustion maximale et minimale.

Lectures à la mise en service

Date de la mise en service : ______________________

Numéro de modèle : _____________________

Numéro de série : ______________________

Type de gaz : ___________

Tension d’alimentation : ______ Tension/terre : ______ V c.a.; Tension/neutre : ______ V c.a.; Neutre/terre : ______ V c.a.

Niveau de combustion maximale

Niveau de combustion minimale

Pression du gaz à l’entrée (kPa)

Pression au collecteur (kPa)

Dioxyde de carbone (%)

Monoxyde de carbone (ppm)

Oxygène (%)

Vitesse du ventilateur (tours/min)

Température des gaz de combustion (°C)

Température du gaz (°C)

Pression dans la cheminée (kPa)

MESURES À PRENDRE

Tous les essais et toutes les mesures doivent se conformer aux exigences avant que le présent certificat de mise en service soit délivré. Dans le cas contraire, il faut expliquer ci-dessous les mesures prises pour la correction du problème.

AVIS

Tous les essais et toutes les mesures doivent se conformer aux exigences avant que le présent certificat de mise en service soit délivré. Pour tout essai fait sur les lieux, il faut expliquer ci-dessous les mesures prises pour la correction du problème. Le propriétaire a été avisé que le système doit faire l’objet de corrections. Il reconnaît que des modifications doivent être apportées au système d’ici 30 jours,

et ce, avant que la mise en service soit complétée.

Signature obligatoire du propriétaire :

 

Date :

Image 7
Contents II. Component Sequence Verification Verify utilitiesIII. Initial Boiler Set-up Verification IV. Boiler Start-Up Setting of the test modeMaximum Fire Adjustment Combustion sample Minimum Fire Adjustment Combustion sampleMaximum Fire Minimum Fire Start Up RecordDisposition NotificationStatement of Compliance Imprimé Vérification des servicesConfiguration du mode d’essai IV. Mise en service de la chaudièreMise en marche initiale de la chaudière Niveau de combustion maximale Lectures à la mise en serviceMesures À Prendre AvisDéclaration DE Conformité

VB/VW 500/750/1000 specifications

A.O. Smith is a well-known name in the water heating industry, and its VB/VW series models, particularly the 500, 750, and 1000, are designed for commercial applications, offering a range of advanced features and technologies. These models are recognized for their high efficiency, reliability, and performance, making them suitable for various industries, including hospitality, healthcare, and food service.

One of the standout features of the VB/VW series is their impressive recovery rates. With a powerful heating capacity, these units can deliver hot water consistently, ensuring that large demands are met without interruptions. This is particularly important for businesses that rely on a steady supply of hot water throughout the day.

The VB/VW series utilizes advanced insulation technology, which significantly reduces energy loss. This feature not only improves the overall energy efficiency of the units but also contributes to lower operational costs. The use of foam insulation helps maintain water temperature, allowing for reduced energy consumption and enhanced performance.

These models come equipped with advanced control systems, providing users with greater flexibility and ease of operation. The user-friendly digital display allows for precise temperature control and monitoring, ensuring optimal performance is maintained at all times. Additionally, the temperature settings can be adjusted to suit specific water heating requirements, catering to the unique needs of various applications.

A.O. Smith's commitment to safety is evident in the design of the VB/VW series. These models incorporate multiple safety features, including a high-temperature limit switch, fusible links, and proper venting systems, ensuring safe operation in any environment. The robust construction of the units, combined with the use of high-quality materials, enhances durability and extends the lifespan of the water heaters.

Moreover, these models are designed for easy maintenance. The intuitive design allows for simplified access to key components, making routine checks and servicing straightforward for technicians. This ease of maintenance contributes to reduced downtime and enhances the overall operational efficiency of the water heating system.

In summary, the A.O. Smith VB/VW 500, 750, and 1000 water heaters are engineered to meet the demands of commercial applications with their high efficiency, advanced technology, and safety features. With their ability to deliver consistent hot water, coupled with ease of maintenance and reduced energy consumption, these models stand out as a reliable choice for businesses seeking efficient and effective water heating solutions.