A.O. Smith BTH 300A, BTH 400A warranty Vent Pipe Termination, Direct Vent Terminal Installation

Page 10

Heater must be protected from freezing downdrafts during shutdown periods.

WARNING

NEVER OPERATE THE HEATER UNLESS IT IS VENTED TO THE OUTDOORS AND HAS ADEQUATE AIR SUPPLY TO AVOID RISKS OF IMPROPER OPERATION, FIRE, EXPLOSION OR ASPHYXIATION.

VENT PIPE TERMINATION

NOTE: Before installing venting, determine place of vent pipe termination. See Figure 5 and 6 before proceeding.

CAUTION

DO NOT TERMINATE THE VENTING WHERE NOISE FROM THE EXHAUST OR INTAKE WILLBE OBJECTIONABLE. THIS INCLUDES LOCATIONS CLOSE TO OR ACROSS FROM WINDOWS AND DOORS. AVOID ANCHORING THE VENT AND INTAKE PIPES DIRECTLY TO FRAMED WALLS, FLOORS OR CEILINGS UNLESS RUBBER ISOLATION PIPE HANGERSARE USED. THIS PREVENTS ANY VIBRATIONS FROM BEING TRANSMITTED INTO THE LIVING SPACES.

IMPORTANT

The vent system must terminate so that proper clearances are maintained as cited in local codes or the current editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the Canadian Electrical Code, CSA C22.1.

Do not terminate the exhaust vent terminal over public area where condensate or vapor can cause nuisance or hazard.

Plan the vent system layout so that proper clearances are maintained from plumbing and wiring.

Vent pipes serving power vented appliances are classified by building codes as "vent connectors". Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION OF HEATER and CLEARANCES, and with National Fuel Gas Code and local Codes.

IMPORTANT

Plan the layout of the vent system backwards from the vent termination to the appliance.

3"x 4" PVC REDUCER WITH INTAKE GUARD

FIGURE 7.

WARNING

WHEN THE UNIT IS TO BE SETUP AS A DIRECT VENT, THE INTAKE GUARD AND THE BALANCE PLATE MUST BE REMOVED. THE INLET VENT PIPE MAY THEN BE GLUED TO THE AIR INTAKE (see Figure 8) PROVIDED ON THE UNIT.

FIGURE 8.

DIRECT VENT TERMINAL INSTALLATION

IMPORTANT

4" VENT AND INTAKE TERMINALS ARE PROVIDED FOR NEW INSTALLATIONS. FOR REPLACEMENT OF PREVIOUS BTH 300 AND 400 WITH 3" TERMINALS, THE 4" TERMINALS ARE RECOMMENDED, BUT THE EXISTING 3" VENT/INTAKE TERMINALS ARE PERMITTED.

NOTE: TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY/COLD AREAS, THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS RECOMMENDED.

WARNING

USE ONLY THE VENT TERMINALS SUPPLIED WITH THIS UNIT. TERMINATION OF A VENT SYSTEM WITHA DEVICE OTHER THAN THE SUPPLIED VENT TERMINATIONS WILL AFFECT SYSTEM PERFORMANCE AND RESULT IN A SAFETY HAZARD.

DIRECT VENTING

The air intake provided on the unit contains an intake guard, see Figure 7.

IMPORTANT

WHEN LOCATING THE TERMINALS ON A SIDEWALL, THE FOLLOWING SPECIFICATIONS PERTAINING TO TERMINAL LOCATION MUST BE FOLLOWED.

1.The intake vent terminal and the exhaust vent terminal must terminate on the same exterior wall and must be located at a minimum of 24" (61cm) from the vertical centerline of the exhaust vent terminal (see Figure 9). In colder climates increasing the 24" (61cm) minimum to 48" (122cm) will reduce possibility of frost over from side winds blowing exhaust vapors to the air intake of the direct the vent and is recommended for Canada.

10

Image 10
Contents Cyclone XHE Model BTH 300A and 400A Foreword ROUGH-IN-DIMENSIONSGAS Valve Piping Table of Contents FeaturesQuick Installation Tips Horizontal Sidewall Venting Vertical Rooftop VentingHigh Limit Switch E.C.O Water Temperature Setpoint Adjustment ProcedureDishwashing Machine Requirement Required Ability Installation InstructionsCirculating Pump Insulation BlanketsUnconfined Space ClearancesHard Water Confined SpaceUS Direct Vent Canadian Direct VentUS Horizontal Vent Canadian Horizontal VentVent Pipe Termination Direct Vent Terminal InstallationDirect Venting Installation Sequence Vertical Vent Terminal InstallationInstallation of Vent System Vent Length TableBlocked Outlet Prover Switch Controls and SwitchesBlower Prover Switch Blocked Inlet Prover SwitchGAS Piping HOT Surface IgniterConnection of GAS Pipe System Connections Heater Wiring Page Sequence of Operation Self Diagnostic ControllerOperation GAS Valve LED FlashingError Codes Fault ConditionsECO Switch OPEN. See Figure Operating Instructions Adjustment Procedure Initial START-UPPrior to Start UP Required Ability Operating Instructions What to do if YOU Smell GASGeneral Information Draining Maintenance ScheduleFlushing Sediment RemovalPower Supply LED Meanings Powered Anode SystemPowered Anode Operation Drain Valve and Access PanelsInstallation Diagrams Install in Accordance with Local Codes Must be Identical Heaters Install in Accordance with Local Codes Page Manifold Kits Water is TOO HOT Burner Operational ProblemsNot Enough or no HOT Water Water Heater Makes SoundsMotor will not RUN Motor RUNS, Burner Lights Momentarily Then Locks OUTNoisy Burner Operation Replacement PartsGAS Fails to Shut OFF Model BTH Limited Warranty

BTH 300A, BTH 400A specifications

A.O. Smith has established itself as a leader in the water heating industry, offering a range of products that combine efficiency, reliability, and innovative technology. Among these products, the BTH 300A and BTH 400A models stand out for their advanced features and robust performance, catering to both residential and commercial needs.

The BTH 300A and BTH 400A are high-efficiency water heaters designed with cutting-edge condensing technology, allowing for significant energy savings compared to traditional water heating systems. These models utilize a modulating gas valve that adjusts the burner operation based on the demand for hot water. This smart system not only enhances efficiency but also ensures a consistent supply of hot water without the worry of fluctuations.

One of the standout features of the BTH series is its compact design. Both the BTH 300A and BTH 400A are engineered to fit into smaller spaces, making them ideal for properties with limited installation areas. Their lightweight construction and user-friendly installation features further simplify the process, ensuring that homeowners and professionals alike can set them up with ease.

The BTH models are equipped with advanced control systems that offer precise temperature adjustment capabilities. Users can easily customize their hot water settings to meet specific household or business requirements. This adaptability is supported by the built-in digital display, which provides real-time information about the operating status of the unit.

Safety is a key consideration in the design of the BTH 300A and BTH 400A. They feature a robust set of safety mechanisms, including temperature lockout and venting safeguards, ensuring reliable operation and peace of mind for users. A.O. Smith also understands the importance of longevity in water heaters, and these models are built with high-quality materials, making them resistant to corrosion and wear over time.

In terms of performance, both the BTH 300A and BTH 400A models deliver exceptional heating capabilities, capable of meeting high demands while maintaining efficiency. With customer satisfaction at the forefront, A.O. Smith backs these units with an extensive warranty, demonstrating their commitment to quality and long-term performance.

In summary, the A.O. Smith BTH 300A and BTH 400A water heaters exemplify the marriage of innovation and functionality. With their energy-efficient operation, customizable settings, compact design, and advanced safety features, these models are a compelling choice for those in need of reliable and effective hot water solutions.