HOT SURFACE IGNITER

The Hot Surface Igniter is a device that ignites the main burner by high temperature (>1800°F or >982°C). When 120VAC is applied to the igniter, sufficient heat is generated to ignite the main burner. Although improvements have been made to strengthen the igniter, it is fragile and care must be taken when handling the igniter to prevent breakage.

GAS PIPING

Contact your local gas service company to ensure that adequate gas service is available and to review applicable installation codes for your area.

Size the main gas line in accordance with Table 3. The figures shown are for straight lengths of pipe at 0.5 in. W.C. (125Pa) pressure drop, which is considered normal for low pressure systems Note that fittings such as elbows and tees will add to the pipe pressure drop.

CAUTION

DO NOT USE FLEXIBLE GAS PIPING.

TABLE 3. MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR (Based upon a Pressure Drop of 0.5 inch Water Column and 0.6 Specific Gravity Gas and max. gas pressure of 0.5 psig).

 

LENGTH

 

NORMAL IRON PIPE SIZES (INCHES)

 

 

IN

 

INPUT IN THOUSANDS BTU/HR

 

 

FEET

1 1/4"

1 1/2"

2"

2 1/2"

3"

4"

10

1400

2100

3960

6300

11000

23000

20

950

1460

2750

4360

7700

15800

 

30

770

1180

2200

3520

6250

12800

40

660

990

1900

3000

5300

10900

 

50

580

900

1680

2650

4750

9700

60

530

810

1520

2400

4300

8800

 

70

490

750

1400

2250

3900

8100

 

80

460

690

1300

2050

3700

7500

90

430

650

1220

1950

3450

7200

100

400

620

1150

1850

3250

6700

125

360

550

1020

1650

2950

6000

150

325

500

950

1500

2650

5500

 

175

300

460

850

1370

2450

5000

200

 

430

800

1280

2280

4600

 

LENGTH

 

NORMAL IRON PIPE SIZES (INCHES)

 

 

IN

 

 

INPUT IN KW

 

 

 

METERS

1 1/4"

1 1/2"

2"

2 1/2"

3"

4"

3.0

410

615

1160

1845

3221

6735

6.1

278

428

805

1277

2255

4626

9.1

225

346

644

1031

1830

3748

12.2

193

290

556

878

1552

3192

 

15.2

170

264

492

776

1391

2840

18.3

155

237

445

703

1259

2577

21.3

143

220

410

659

1142

2372

 

24.4

135

202

381

600

1083

2196

27.4

126

190

357

571

1010

2108

 

30.5

117

182

337

542

952

1962

 

38.1

105

161

299

483

864

1757

45.7

95

146

278

439

776

1610

53.3

88

135

249

401

717

1464

61.0

 

126

234

375

688

1347

WARNING

THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN 11.0" WATER COLUMN (2.74 Kpa) FOR NATURAL GAS AND 14.0" W.C. (3.49kPa) FOR PROPANE GAS SUPPLY PRESSURE. HIGHER GAS SUPPLY PRESSURES REQUIRE SUPPLEMENTAL REDUCING SERVICE REGULATION. EXPOSURE TO HIGHER GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE GAS CONTROLS WHICH COULD RESULT IN

FIRE OR EXPLOSION. IF OVERPRESSURE HAS OCCURRED SUCH AS THROUGH IMPROPER TESTING OF GAS LINES OR EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM THE GAS VALVE MUST BE CHECKED FOR SAFE OPERATION. MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS AND THE SAFETY VENT VALVES ARE PROTECTED AGAINST BLOCKAGE. THESE ARE PARTS OF THE GAS SUPPLY SYSTEM, NOT THE HEATER. VENT BLOCKAGE MAY OCCUR DURING ICE STORMS. IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.

IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE.

BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED A SEDIMENT TRAP OR DRIP LEG) MUST BE INCORPORATED IN THE PIPING (SEE FIG. 14). THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS. INSTALLINACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFER TO THE NATIONAL FUEL GAS CODE OR THE NATURAL GAS AND PROPANE INSTALLATION CODE CSA B149.1.

FIGURE 14.

CONNECTION OF GAS PIPE

1.When connecting gas pipe to unit, apply wrench to flange only. Note: Do not use wrench on gas valve or gas bracket.

2.PERFORM THE GAS LEAK TEST ANY TIME WORK IS DONE ON A GAS SYSTEM TO AVOID THE POSSIBILITY OF FIRE OR EXPLOSION WITH PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.

The Gas Leak Test is performed as follows: Paint pipe connections upstream of gas control with a rich soap and water solution to test for leaks before operating main burner. Bubbles indicate gas leak. To stop leak, tighten pipe connections. After piping connections are checked, turn on main burner. With main burner in operation, paint pipe joints (including flanges), pilot gas tubing connections and control inlet and outlet with rich soap and water solution. Bubbles indicate gas leak. To stop leak, tighten flange screws, joints and pipe connections. Replace part if leak can’t be stopped.

To prevent damage, care must be taken not to apply too much torque when attaching gas supply pipe to gas valve inlet.

Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do not apply compound to the first two threads. Use compounds resistant to the action of liquefied petroleum gases.

DISCONNECT THE APPLIANCE AND ITS MANUAL GAS SHUTOFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSIG (3.45Kpa). GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM THE HEATER. FOR TEST PRESSURES OF 1/2 PSIG (3.45Kpa) OR

14

Image 14
Contents Cyclone XHE Model BTH 300A and 400A GAS Valve Piping ROUGH-IN-DIMENSIONSForeword Table of Contents FeaturesQuick Installation Tips Horizontal Sidewall Venting Vertical Rooftop VentingDishwashing Machine Requirement Water Temperature Setpoint Adjustment ProcedureHigh Limit Switch E.C.O Required Ability Installation InstructionsCirculating Pump Insulation BlanketsUnconfined Space ClearancesHard Water Confined SpaceUS Direct Vent Canadian Direct VentUS Horizontal Vent Canadian Horizontal VentDirect Venting Direct Vent Terminal InstallationVent Pipe Termination Installation Sequence Vertical Vent Terminal InstallationInstallation of Vent System Vent Length TableBlocked Outlet Prover Switch Controls and SwitchesBlower Prover Switch Blocked Inlet Prover SwitchConnection of GAS Pipe HOT Surface IgniterGAS Piping System Connections Heater Wiring Page Sequence of Operation Self Diagnostic ControllerOperation GAS Valve LED FlashingError Codes Fault ConditionsECO Switch OPEN. See Figure Prior to Start UP Required Ability Adjustment Procedure Initial START-UPOperating Instructions Operating Instructions What to do if YOU Smell GASGeneral Information Draining Maintenance ScheduleFlushing Sediment RemovalPower Supply LED Meanings Powered Anode SystemPowered Anode Operation Drain Valve and Access PanelsInstallation Diagrams Install in Accordance with Local Codes Must be Identical Heaters Install in Accordance with Local Codes Page Manifold Kits Water is TOO HOT Burner Operational ProblemsNot Enough or no HOT Water Water Heater Makes SoundsMotor will not RUN Motor RUNS, Burner Lights Momentarily Then Locks OUTGAS Fails to Shut OFF Replacement PartsNoisy Burner Operation Model BTH Limited Warranty

BTH 300A, BTH 400A specifications

A.O. Smith has established itself as a leader in the water heating industry, offering a range of products that combine efficiency, reliability, and innovative technology. Among these products, the BTH 300A and BTH 400A models stand out for their advanced features and robust performance, catering to both residential and commercial needs.

The BTH 300A and BTH 400A are high-efficiency water heaters designed with cutting-edge condensing technology, allowing for significant energy savings compared to traditional water heating systems. These models utilize a modulating gas valve that adjusts the burner operation based on the demand for hot water. This smart system not only enhances efficiency but also ensures a consistent supply of hot water without the worry of fluctuations.

One of the standout features of the BTH series is its compact design. Both the BTH 300A and BTH 400A are engineered to fit into smaller spaces, making them ideal for properties with limited installation areas. Their lightweight construction and user-friendly installation features further simplify the process, ensuring that homeowners and professionals alike can set them up with ease.

The BTH models are equipped with advanced control systems that offer precise temperature adjustment capabilities. Users can easily customize their hot water settings to meet specific household or business requirements. This adaptability is supported by the built-in digital display, which provides real-time information about the operating status of the unit.

Safety is a key consideration in the design of the BTH 300A and BTH 400A. They feature a robust set of safety mechanisms, including temperature lockout and venting safeguards, ensuring reliable operation and peace of mind for users. A.O. Smith also understands the importance of longevity in water heaters, and these models are built with high-quality materials, making them resistant to corrosion and wear over time.

In terms of performance, both the BTH 300A and BTH 400A models deliver exceptional heating capabilities, capable of meeting high demands while maintaining efficiency. With customer satisfaction at the forefront, A.O. Smith backs these units with an extensive warranty, demonstrating their commitment to quality and long-term performance.

In summary, the A.O. Smith BTH 300A and BTH 400A water heaters exemplify the marriage of innovation and functionality. With their energy-efficient operation, customizable settings, compact design, and advanced safety features, these models are a compelling choice for those in need of reliable and effective hot water solutions.