3 Installation
3.3.1Air humidity and ambient temperature
The installation area should be
Specifications for air humidity and ambient temperature
Air humidity and ambient temperature
Air humidity
max. 93% RH at +25°C
Ambient temperature
Functional: 0 ≤ t ≤ 60°C
3.3.2Maximum floor loading
In view of the weight of the device, take the maximum floor loading into account. See the table below.
Specification for weight in connection with the maximum floor loading
Weight of the device filled with water
TWI
199 kg
TWI
271 kg
3.3.3Water composition
The device is designed for heating drinking water. The drinking water shall comply with the regulations for drinking water for human consumption. The table gives an overview of the specifications.
Specifications for water
Water composition
Hardness
(alkaline earth ions)
>1.00 mmol/l:
-German hardness > 5.6° dH
-French hardness > 10.0° fH
-British hardness > 7.0° eH
Conductivity
> 125 muS/cm
Acidity
7.0 <
Remark
When the specifications mentioned in the table are deviated from, the protection of the tank can not be guaranteed (11 “Warranty (certificate)”).
3.3.4Working area
In view of the accessibility of the device, it is recommended to apply the following distances (see figure):
•AA: on the front side of the device: 100 cm.
•BB: around the device: 50 cm.
•Top side of the device: 50 cm.
16 | Instruction manual TWI |