Mitsubishi Electronics Electrical Parts Specifications for PDFY Series Air Conditioners

Page 8

3-2. Electrical parts specifications

Model

Symbol

PDFY-

PDFY-

PDFY-

PDFY-

PDFY-

PDFY-

Parts

P06,08,12

P15,18

P24,27

P30

P36

P48

 

NMU-E

NMU-E

NMU-E

NMU-E

NMU-E

NMU-E

name

 

 

 

 

 

 

 

 

Tranrsformer

T

 

(Primary) 240V 60Hz

(Secondary) (23.5V 0.9A)

 

Room

 

Resistance 0˚C[32˚F]/15k,10˚C[50˚F]/9.6k,20˚C[68˚F]/6.3k,25˚C[77˚F]/5.4k,

temperature

TH21

 

30˚C[86˚F]/4.3k,40˚C[104˚F]/3.0k

 

 

thermistor

 

 

 

 

 

 

 

 

 

 

 

Liquid pipe

TH22

Resistance 0˚C[32˚F]/15k,10˚C[50˚F]/9.6k,20˚C[68˚F]/6.3k,25˚C[77˚F]/5.4k,

thermistor

 

30˚C[86˚F]/4.3k,40˚C[104˚F]/3.0k

 

 

 

 

 

 

Gas pipe

TH23

Resistance 0˚C[32˚F]/15k,10˚C[50˚F]/9.6k,20˚C[68˚F]/6.3k,25˚C[77˚F]/5.4k,

thermistor

 

30˚C[86˚F]/4.3k,40˚C[104˚F]/3.0k

 

 

 

 

 

 

Fuse

 

 

 

 

 

 

 

(Indoor con-

FUSE

 

 

250V 6.3A

 

 

troller board)

 

 

 

 

 

 

 

Fan motor

 

4-pole

4-pole

4-pole Output 95W

4-pole

4-pole

(with Inner-

MF1

Output 75W

Output 85W

Output 140W

Output 190W

D104P95MW

thermostat)

 

D104P75MW

D104P85MW

NC-100VM1

NC-125VM1

 

 

 

Inner-

 

 

OFF 130˚C±5˚C[266˚F±41˚F]

 

OFF 150˚C±5˚C[302˚F±41˚F]

thermostat

 

 

 

 

 

ON 90˚C±20˚C[194˚F±68˚F]

 

ON 96˚C±15˚C[205˚F±59˚F]

(Fan motor)

 

 

 

 

 

 

 

 

 

 

Fan motor

C1

3.0F X 440V

5.0F X 440V

6.0F X 440V

5.0F

8.0F

capacitor

X 440V

X 440V

 

 

 

 

 

Linear

LEV

DC12V Stepping motor drive port dimension

DC12V Stepping motor drive port dimension

expansion valve

3.2(0~2000pulse) EDM-402MD

5.2(0~2000pulse) EDM-804MD

 

Power supply

TB2

 

 

(L1,L2,G) 330V 30A

 

 

terminal bed

 

 

 

 

 

 

 

 

 

 

 

Transmission

TB5

 

 

(1,2),(M1,M2,S) 330V 30A

 

 

terminal bed

TB15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

Image 8
Contents 2005 Safety Precautions Carefully read the labels affixed to the main unitPrecautions for devices that use R410A refrigerant Features Models Cooling capacity/Heating capacityPart Names and Functions Operation buttonsDisplay Specification SpecificationElectrical parts specifications R410A outdoor unit P36NMU-E P48NMU-E Wiring Diagram Symbol ExplanationP36·48NMU-E Refrigerant System Diagram Trouble Shooting How to check the partsLinear expansion valve Operation summary of the linear expansion valveOFF Unit Address board Disassembly Procedure Removing the control box coverRemoving the cover Removing the thermistorDrainpan Operating Procedure Removing the drainpanThermistor Gus piping temperature detection Removing the filter Removing the bottom plateRemoving the cable Sliding the fan sectionHeat Exchanger Operating Procedure New publication, effective Aug Specifications are subject to change without notice