Mitsubishi Electronics PUH-2.5AKA PUH-3VKA*, PCH-3GAK, PCH-GAK, PUH-3YKA, R22 Main Optional Parts

Page 14

G E N E R A L S P E C I F I C A C I O N S F O R A L L M O D E L S

Notes for All Specifications

Rating conditions: Cooling - Indoor 27ºCDB, 19ºCWB; Outdoor 35ºCDB

Heating - Indoor 20ºCDB

; Outdoor 7ºCDB,6ºCWB

● Data based on indicated voltage Indoor unit

: 1-ph, 240V, 50Hz

Outdoor unit : 1-ph, 240V, 50Hz/3-ph, 415V, 50Hz

Refrigerant piping length (one-way): 5m (16ft)

Refrigerant charge is suitable for 5m piping length.

■ Guaranteed Operating Range

 

Limits

Indoors

Outdoors

Cooling

 

Lower

21ºC DB, 15.5ºC WB

-5ºC DB

 

Upper

35ºC DB, 22.5ºC WB

46ºC DB

 

 

Heating

 

Lower

20ºC DB

-8.5ºC DB, -9.5ºC WB

 

Upper

27ºC DB

21ºC DB, 15.5ºC WB

 

 

■ Refrigerant Piping

Models

 

Between indoor & outdoor units

 

Pipe size O.D., mm

 

Max. height difference, m

Max. piping length, m

Max. number of bends

Liquid

Gas

PLH-3AAK, PKH-3FAK,

50

50

15

Ø 9.52

Ø 15.88

PCH-3GAK, PEH-2.5EAK, PEH-3EAK

 

 

 

 

 

PKH-4FAK PLH-4/5/6AAK,

50

50

15

Ø 9.52

Ø 19.05

PCH-4/5/6GAK, PEH-4/5/6EAK

 

 

 

 

 

■ Optional Refrigerant Pipes

Pipe length

Part number

5m

(16ft)

PAC-05FFS-E

PAC-SC51PI-E

7m

(23ft)

PAC-07FFS-E

PAC-SC52PI-E

10m (33ft)

PAC-10FFS-E

PAC-SC53PI-E

15m (49ft)

PAC-15FFS-E

PAC-SC54PI-E

Connection method

Flared-flared

Flared-flared

Pipe size OD, mm (ft)

Liquid: Ø 9.52 (3/8) Gas: Ø 15.88 (5/8)

Liquid: Ø 9.52 (3/8) Gas: Ø 19.05 (3/4)

Applicable models

PKH-3FAK, PLH-3AAK, PCH-3GAK, PEH-2.5EAK, PEH-3EAK

PKH-4FAK, PLH-4/5/6AAK, PCH-4/5/6GAK, PEH-4/5/6EAK

■ Additional Refrigerant Charge [R-22: kg]

Models

 

 

 

 

Piping length (one-way)

 

 

 

 

 

5m

10m

15m

20m

25m

30m

35m

40m

45m

50m

PUH-2.5AKA

0

0

0

0

0

0

0.2

0.2

0.5

0.5

PUH-3VKA/PUH-3YKA

0

0

0

0

0

0

0.2

0.2

0.5

0.5

PUH-4YKSA

0

0

0

0

0

0

0.3

0.3

0.6

0.6

PUH-5YKSA

0

0

0

0

0

0

0.3

0.3

0.6

0.6

PUH-6YKSA

0

0

0

0

0

0

0.3

0.3

0.6

0.6

Cooling Capacity Correction Factors

Models

 

 

 

 

Correction factors (Cooling / Heating)

 

 

 

One-way piping length, m

5

10

15

20

 

25

30

35

40

45

50

PEH-2.5EAK

1.00/1.00

0.989/1.00

0.980/1.00

0.970/1.00

 

0.960/1.00

0.950/1.00

0.940/0.998

0.930/0.995

0.920/0.993

0.910/0.990

PKH-3FAK, PCH-3GAK,

1.00/1.00

0.981/1.00

0.968/1.00

0.952/1.00

 

0.940/1.00

0.925/1.00

0.913/0.998

0.900/0.995

0.886/0.993

0.874/0.990

PLH-3AAK, PEH-3EAK

 

 

 

 

 

 

 

 

 

 

 

 

PKH-4FAK PCH-4GAK,

1.00/1.00

0.989/1.00

0.980/1.00

0.970/1.00

 

0.960/1.00

0.950/1.00

0.940/0.998

0.930/0.995

0.920/0.993

0.910/0.990

PLH-4AAK, PEH-4EAK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PCH-5GAK PLH-5AAK,

1.00/1.00

0.981/1.00

0.968/1.00

0.952/1.00

 

0.940/1.00

0.925/1.00

0.913/0.998

0.900/0.995

0.886/0.993

0.874/0.990

PEH-5EAK

 

 

 

 

 

 

 

 

 

 

 

 

PCH-6GAK, PLH-6AAK

1.00/1.00

0.975/1.00

0.955/1.00

0.935/1.00

 

0.918/1.00

0.900/1.00

0.884/0.998

0.869/0.995

0.855/0.993

0.840/0.990

PEH-6EAK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main Optional Parts

Model

Description

Applicable models

MAC-397IF-E

MA & Control Terminal Interface

New A/K control

PAC-SE55RA-E

Timer Adapter

New A/K control

PAC-725AD

Multiple Remote Controller Adapter (10 sets)

New A/K control

PAC-SE41TS-E

Remote Sensor

New A/K control

PAC-SA46DS-E

Drain Socket

PUH-2.5~4

PAC-SA47DS-E

Drain Socket

PUH-5/6

PAC-292SG-D

Air Outlet Guide

PUH-2.5~6

SDD-50S-E

Distribution Pipe for Twin Use

PUH-5/6

PAC-SG03TM-E

Multi-Function Casement

PLH series

PAC-SG01KF

High Efficiency Filter Element

PLH series

PAC-SG06SP-E

Air Outlet Shutter Plate

PLH series

PAC-SE85DMA-E

Drain Lift-Up Mechanism

PCH-3

PAC-SE86DMA-E

Drain Lift-Up Mechanism

PCH-4~6

PAC-SE81KF-E

High Efficiency Filter

PCH-3/4

PAC-SE82KF-E

High Efficiency Filter

PCH-5/6

PAR-SL99B-E

Wireless Remote Controller

PCH series

PAR-SL97A-E

Wireless Remote Controller

PLH series

 

 

 

13

Image 14
Contents Natural Comfort For Everybody O D U C T PLH-4AAK PKH-4FAK PCH-4GAK PEH-4EAK PUH-4YKSA MEQ Difference Comfort Efficiency DurabilityNew Remote Controller First Choice For Any and All ApplicationsMr. Slim New A/K Control System Configuration Sequential start adaptable Same mode operation MAC-397IF-ETwin Multi Operation Outdoor Unit and Twin-Multi CombinationsUnit height of only 258mm PLH-3 Design uniformity improves installation flexibilityPLH-AAK Automatic vane shutterPKH-FAK PCH-GAK Computerized dehumidification Limitless installation possibilitiesPEH-EAK PLH-AAKPOWER Ceiling Cassette PCH-GAKCEILING Suspended Main Optional Parts Outdoor Unit Installation Location Black Diamond Technologies