Mitsubishi Electronics PAC-YG31CDA COV Change Of Value, Notification, COV notification setup

Page 31

8.8.2 Notification Setting

BMS carries out the monitor of the state, in order to know the state of Object of BACnetIF.

Notification is the function notified to the BACnet (or Building Automation System), when the value currently supervised exceeds a limit or it changes to an alarm value. There are COV type and EVENT in Notification.

Item

Contents

Target object name

COV (Change Of Value)

Example) When the [RoomTemp] value

All

Notification

currently supervised changes, BACnet IF

Except for

 

send a COV notification message to the

Notification Class and Device

 

BMS.

 

EVENT Notification

When the decided specific conditions are

All

 

satisfied, it announces to a BMS.

Except for

 

Example1) When the [Alarm Signal] value

Notification Class and Device

 

currently supervised changes to the alarm

 

 

value, BACnet IF send a notification

 

 

message to the BMS.

 

 

Example 2) When the [RoomTemp] value

 

 

currently supervised exceeds a limit,

 

 

BACnet IF sends a notification message to

 

 

the BMS.

 

8.8.2.1 COV notification setup

The destination address of a COV notification message is setup.

The number of the address, which can be registered, is to 10.

Select the [COV Notification Settings] tab.

COV No.

Set the number of COV notification.

(1) Add COV notification address

Click the [Add] button. The [Notification Address] screen will open.

28

Image 31
Contents Please read this manual before using the unit Test operation from BMS ………37………36 Page Other machines Safety PrecautionsRelocating the unit you may result in incorrect Making improper improvements or repairs mayOther Precautions Precautions for General UsageRequirements system recommendations System RequirementsCompatible Airconditioner Updating the G-50A RestrictionsNumber of units Checking the G-50A versionSystem Configuration Example System ConfigurationHardware Connection Diagram IC IC IC 01 02 IC IC 04 Group ConfigurationFunctional specification Analog Input Object ListList of the objects to be used is shown below SupportObject Object type Instance Object and Management ItemNumber Xxxx23 Horizontal Xxxx15 Inactive Permit Active Prohibit Filter resetXxxx22 Horizontal Swing Air direction stateExecute Reception and execution of service Service ListInitiate Issue of service Service Initiate ExecuteBACnet if receives Service list for every objectStandard support Setting change is possible BACnet if transmitsObject Object type Event Event Service specificationProhibition of local operation Mode FunctionSetting functional list Pre-installation Steps InstallationPreparing for installation 1CD-ROM directory structure BACnet if SetupStarting the setup program Setup the serial NoCheck the program folder Check the installation folderSetup completion Click the Finish button on the Setup Complete screenUninstall BACnet if UninstallDrag Part Names and FunctionsWindow Elements Basic Mouse OperationShutdown Initial Startup and ShutdownBefore Startup Start upPage Start Up SetBACnet System Setting ProcedureShutdown SetBACnet Title bar Get/Put system settingsWindows Elements Open/Close fileSetup for G-50A System Setting ProcedureAdd group Modify group configuration2 G-50A NO. and IP-Address 3 Add/Modify/Delete GroupSelect the model of a group ICIndoor unit LC Lossnay unit Group setup Group SetupFrom G-50A Input the number of a groupCommunication setup Setup for BACnetNotification Setting Add COV notification address COV notification setupCOV Change Of Value NotificationClick the Delete button. The confirmation screen will open Event Notification SettingModify notification address Delete notification addressAdd notification address Notification Class SettingNotification Address Setting Add notification classNotification setting parameter Time System SetupUnit Of temperature Use Speed Type50A test run Site AdjustmentSite Adjustment PC connections and settingsTest operation from centralized controller G-50A Tools for Site AdjustmentStep 50A main unit Initial setting of BACnet ifPC using BACnet if For BMS network For G-50A system Models IP address rangeIs it in agreement with the IP address set as G-50A? Setting CheckTime set Date and Time Is it set up correctly? SettingsTest operation from BMS Building Management System IPaddress Group Number BACnet Interface PAC-YG31CDA Site Adjustment sheet50A Number Was operated by BMS Appendix 1 Auto Log In Confirmation Method Appendix 2 Initial Value Page WT04221X03

PAC-YG31CDA specifications

Mitsubishi Electronics has long been recognized for its innovation and commitment to providing high-quality climate control solutions. The PAC-YG31CDA is one of the standout products from the company, designed to enhance the performance and functionality of air conditioning systems.

The PAC-YG31CDA is primarily used as a communication interface for centralized control settings in multi-split air conditioning systems. It allows for integration with various types of building management systems, making it an essential component in modern HVAC (heating, ventilation, and air conditioning) setups. This unit supports simplified control and monitoring, aiming to optimize energy use while maintaining user comfort.

One of the main features of the PAC-YG31CDA is its compatibility with a range of Mitsubishi air conditioning units, ensuring versatile application across different settings. This allows for centralized management of multiple indoor units, which is particularly useful in commercial environments. Users can easily adjust settings, schedules, and modes from a single interface, streamlining operations and enhancing convenience.

Another significant aspect of the PAC-YG31CDA is its advanced communication capabilities. It utilizes the proprietary MELCO communication protocol, ensuring seamless communication between the indoor and outdoor units. This capability is crucial for real-time monitoring and adjustments, which in turn promotes energy efficiency. The device can also be integrated with remote control units, offering users flexibility in managing their climate control preferences.

In terms of performance, the PAC-YG31CDA features a robust design that ensures reliability and durability. Its compact size allows for easy installation and integration into existing systems, minimizing disruption during setup. Furthermore, the unit is energy-efficient, designed to reduce operational costs while enhancing user comfort.

Overall, the Mitsubishi Electronics PAC-YG31CDA exemplifies the company's commitment to technical excellence and user satisfaction. With its comprehensive features, advanced technologies, and user-friendly design, the PAC-YG31CDA is an invaluable addition to HVAC systems, particularly in settings that require effective climate control management. Whether for commercial or residential applications, this unit stands out as a reliable solution that delivers both performance and value.