Mitsubishi Electronics PKA-A-GA installation manual L2 G B, Power supplies only

Page 8

6. Electrical work

6.1.2.Separate indoor unit/outdoor unit power supplies (A-control application)

The following connection patterns are available.

The outdoor unit power supply patterns vary on models.

1:1 System

C

 

F

L1

 

L1

A B L2 G B

L2

GR

 

GR

S1

 

S1

S2

 

S2

S3

D

S3

 

1

 

E

 

 

2

*Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.

Simultaneous twin system

AOutdoor unit power supply

BWiring circuit breaker or isolating switch

COutdoor unit

DIndoor unit/outdoor unit connecting cords

ERemote controller (Only for PKA-A·GA)

FIndoor unit

GIndoor unit power supply

C

 

F

F

L1

G B

L1

L1

A B L2

L2

L2

GR

 

GR

GR

S1

 

S1

S1

S2

 

S2

S2

S3

D

S3

S3

 

1

1

 

E

 

2

2

* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.

AOutdoor unit power supply

BWiring circuit breaker or isolating switch

COutdoor unit

DIndoor unit/outdoor unit connecting cords

ERemote controller (Only for PKA-A·GA)

FIndoor unit

GIndoor unit power supply

If the indoor and outdoor units have separate power supplies, refer to the table at the below. Change the indoor unit electrical box wiring refering to the figure in the right and the DIP switch settings of the outdoor unit control board.

 

 

Indoor unit specifications

Indoor unit electrical box connector con-

 

 

Required

 

 

nection change

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Label affixed near each wiring diagram

 

 

Required

 

 

for the indoor and outdoor units

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit DIP switch settings (when

 

 

 

 

 

 

 

using separate indoor unit/outdoor unit

 

ON

 

 

 

3

(SW8)

power supplies only)

 

OFF

1

2

 

 

 

 

 

 

 

 

 

 

*There are three types of labels (labels A, B, and C). Affix the appropriate labels to the units according to the wiring method.

Connectors (connections when shipped from the factory are for indoor unit power supplied from outdoor unit)

L2

BLUE

BLUE

 

 

 

L1

 

 

 

 

 

GR

YELLOW

YELLOW

CND

ORANGE

 

 

 

 

 

 

 

CND

 

S1

 

 

 

Indoor unit

 

 

 

 

control board

 

S2

 

 

 

 

 

 

 

 

 

S3

 

 

 

 

 

Indoor unit power supplied from outdoor unit

L1

(when shipped from factory)

 

 

L2

 

 

 

 

 

GR

 

 

 

 

 

S1

 

 

 

 

 

S2

 

 

 

 

 

S3

If the indoor and outdoor units have separate power supplies, change the connections of the connectors as shown in the following figure.

 

 

 

Connectors

YELLOW

BLUE

CND

 

BLUE

YELLOW

ORANGE

 

 

 

CND

 

 

 

Indoor unit

 

 

 

control board

Separate indoor unit/outdoor unit power supplies

Indoor unit model

 

PKA

Indoor unit power supply

 

Single 208/230 V, 60 Hz

Minimum circuit ampacity

 

1 A

Maximum rating of overcurrent protective device

 

15A

 

No.Wiresize

Indoor unit power supply

 

2 Min. AWG16

 

Wiring

Indoor unit power supply earth

 

1 Min. AWG16

 

 

 

 

 

Indoor unit-Outdoor unit

*1

2 AWG22 (polar)

 

 

 

Indoor unit earth

 

 

 

Remote controller-Indoor unit

*2

2 AWG22 (Non-polar)

 

Circuit

rating

Indoor unit L1-L2

*3

AC 208/230 V

 

Indoor unit-Outdoor unit S2-S3

*3

DC24 V

 

 

Indoor unit-Outdoor unit S1-S2

*3

 

 

 

 

 

 

 

 

Remote controller-Indoor unit

*3

DC12 V

*1. Max. 50 m, 165 ft

*2. The 10 m, 30 ft wire is attached in the remote controller accessory. Max. 500 m, 1500 ft

*3. The figures are NOT always against the ground.

Notes: 1. Wiring size must comply with the applicable local and national code.

2.Use copper supply wires.

3.Use wires rated 300V or more for the power supply cables.

4.Install an earth longer than other cables.

8

Image 8
Contents Air-Conditioners Contents Safety precautionsInstallation location Installing the indoor unitWhen embedding pipes into the wall Fig Installing the wall mounting fixturePreparing the indoor unit Mounting the indoor unitInstalling the refrigerant piping PrecautionsConnecting pipes Fig For devices that use R410A refrigerantDrainage piping work Positioning refrigerant and drain pipingRefrigerant piping Fig Drainage piping work FigConnect each wire properly to the terminal block Electrical workIndoor unit Fig Put all the parts back the way they werePower supplies only L2 G BFor heat pump models For cooling only models Control applicationFor heat pump models For wireless remote controller Remote controllerFor wired remote controller Function settings Function setting on the unit Selecting the unit functionsFunction setting on the remote controller Assigning a remote controller to each unit FigUsing wired remote controller Fig Using wireless remote controller FigTest run Before test runUsing SW4 in outdoor unit Wired remote controller FigWireless remote controller Fig Self-checkOutdoor unit fan safeguard stop For about 2 minutes following power-on, operationPower-on Rect operation Power for remote controllerEasy maintenance function This function only for A-control Stable operationBG79U874H01

PKA-A-GA specifications

Mitsubishi Electronics has long been a key player in the realm of air conditioning and climate control technologies, offering a range of innovative solutions that cater to both residential and commercial needs. Among their impressive lineup, the Mitsubishi PKA-A-GA stands out as a noteworthy model known for its advanced features, efficiency, and reliability.

The Mitsubishi PKA-A-GA is a wall-mounted air conditioning unit specifically designed for easy installation and optimal performance. One of its main features is the sleek and modern design, which allows it to blend seamlessly with various interior settings. Its compact form factor saves space while maximizing cooling efficiency.

This model utilizes cutting-edge inverter technology, which significantly enhances energy efficiency. By adjusting the compressor speed according to the cooling demand, the PKA-A-GA maintains a consistent temperature while reducing energy consumption. This not only lowers utility bills but also contributes to a more sustainable operation, making the unit eco-friendly.

A remarkable characteristic of the PKA-A-GA is its advanced air filtration system. Equipped with a high-performance filter, the unit effectively removes allergens, dust, and other particulates from the indoor air, ensuring a cleaner and healthier environment. Additionally, the unit features a self-cleaning function, which helps maintain the filter's efficiency by reducing the buildup of dust and other particles.

Another compelling aspect of the Mitsubishi PKA-A-GA is its whisper-quiet operation. The unit is designed to minimize noise, making it ideal for bedrooms, offices, and other spaces where tranquility is essential. This is particularly beneficial for users who require a calm atmosphere for work or relaxation.

Furthermore, the PKA-A-GA is compatible with smart controls, allowing users to operate and monitor their air conditioning system remotely via smartphones or tablets. This feature adds convenience and lets users optimize their energy consumption even when they're away from home.

Lastly, the durability of the Mitsubishi PKA-A-GA is noteworthy. Built with high-quality materials and robust components, this air conditioning unit is designed to withstand the rigors of daily use while providing reliable performance over the years.

Overall, the Mitsubishi PKA-A-GA is an exceptional air conditioning solution, blending efficiency, smart technology, and user-friendly features into a compact design. Whether for residential or commercial applications, it promises to deliver comfort and satisfaction in an ever-evolving climate.