15.17 Codepad Fire Report

ICP-CC488 Installation Guide 15.0

System Reporting Information

 

 

EN 68

Restore Reports are not sent for this event.

If Codepad Panic Reports are not required, program Locations 405 and 406 as 0.

15.17 Codepad Fire Report

Location

407 to 408

 

 

Location

Default

Tens digit

407

7

Units digit

408

14

 

 

 

A Fire Alarm Report (Contact ID Event Code 110) is sent to the base station receiver when a user presses

[4]and [6] at the same time. A Fire Alarm is audible, but you can program the alarm as silent by selecting Option 2 in Location 493 (refer to Section 18.2 System Options 2 on page 81). A distinct fire sound is emitted through the horn speaker to indicate this type of alarm. The fire sound is different than the burglary sound.

Restore Reports are not sent for this event.

If Codepad Fire Reports are not required, program Locations 407 and 408 as 0.

15.18 Codepad Medical Report

Location

409 to 410

 

 

Location

Default

Tens digit

409

7

Units digit

410

13

 

 

 

A Medical Report (Contact ID Event Code 100) is sent to the base station receiver when a user presses

[7]and [9] at the same time. A Medical Alarm is

audible, but you can program the alarm as silent by selecting Option 4 in Location 493 (refer to Section 18.2 System Options 2 on page 81).

Restore Reports are not sent for this event.

If Codepad Medical Reports are not required, program Locations 409 and 410 as 0.

15.19 Codepad Reporting Options

Location 411

0No Codepad Alarm Reports allowed

1 Report to Receiver 1

2 Report to Receiver 2

4 Report to both Receiver 1 and Receiver 2

8 Report to Receiver 2 only if Receiver 1 fails

Location 411 is set by default to report only to Receiver 1. You can select whether Codepad Alarm Reports are sent to Receiver 1, Receiver 2, or both, Receiver 2 only when Receiver 1 fails, or no reporting.

15.20System Status – AUX Power Supply Fail Report

Location

412 to 413

 

 

Location

Default

Tens digit

412

10

Units digit

413

3

 

 

 

A System Trouble Report (Contact ID Event Code

300)is sent when either the codepad AUX power supply is blown or the AUX power supply malfunctions. The system reports the event approximately 10 sec after the failure.

15.21System Status – AUX Power Supply Fail Restore Report

Location

414 to 415

 

 

Location

Default

Tens digit

414

10

Units digit

415

8

 

 

 

A System Trouble Restore Report (Contact ID Event Code 300) is sent when the AUX power supply is reset. The system reports the event approximately 10 sec after power supply is reset.

15.22 System Status – AC Fail Report

Location

416 to 417

 

 

Location

Default

Tens digit

416

10

Units digit

417

2

An AC Fail Report (Contact ID Event Code 301) is sent to the base station receiver when the AC MAINS supply is disconnected for 2 min. If you do not want an AC Fail Report to be sent until the AC MAINS supply is disconnected for 1 hour, select Option 1 in Location 494 (refer to Section 18.3 System Options 3 on page 81). If you want to ignore AC Fail, select Option 2 in Location 494.

If AC Fail Reports are not required, program Locations 416 and 417 as 0.

15.23System Status – AC Fail Restore Report

Location

416 to 417

 

 

Location

Default

Tens digit

416

10

Units digit

417

7

An AC Fail Restore Report is sent when the AC MAINS supply is connected continuously for longer than 2 min.

If AC Fail Restore Reports are not required, program Locations 418 and 419 as 0.

Bosch Security Systems, Inc. 12/08 F01U089457-02

Page 68
Image 68