ICP-CC488 Installation Guide 17.0

System Event Timers

 

 

EN 77

10 – Normally Low, One-Shot Open

This one-shot polarity is normally 0 V and switches to open circuit when the event occurs. The output switches back to 0 V when the time parameter expires. This one-shot time setting always runs its full duration and cannot be manually reset.

11 – Normally Low, One-Shot Open with Reactivate

This one-shot polarity is normally 0 V and switches to open circuit when the event occurs. Every time the event occurs, it restarts the one-shot timer. The output switches back to 0 V when the one-shot time expires.

12 – Normally Low, One-Shot Open with Reset

This one-shot polarity is normally 0 V and switches to open circuit when the event occurs. Because the output switches back to 0 V when the one-shot time expires or when the event returns to normal, the one- shot timer can be shortened regardless of the time setting.

13 – Normally Low, One-Shot Open with Alarm

This one-shot polarity is normally 0 V and switches to open circuit when the event occurs. Because the output switches back to 0 V when the one-shot time expires, the event returns to normal, or the system is disarmed, the one-shot timer can be shortened regardless of the time setting.

14 – Normally Low, Latching Open

This polarity is normally 0 V and switches to open circuit when the event occurs. The output switches back to 0 V when the user holds down [7] on the remote codepad until two beeps sound. Time parameters do not apply to this polarity.

16.4Output Timing

The timing of outputs is calculated by the time base and a multiplier. These two values play different roles depending on the selected polarity. When you program outputs to pulse, you can set both the On and Off times. You can program one-shot polarities to operate from 200 ms to 99 hours.

The maximum value you can program in the two multiplier locations is 9,9.

Table 57: Time Base Settings

Option Description

1200 ms

21 sec

31 min

41 hour

You can only set the time base settings to one of the values listed in Table 57 on page 77. The multiplier value is a two-digit decimal number from 00 to 99. For greater accuracy, use 60 sec for 1-min intervals and 60 min for 1-hour intervals.

16.5Pulsing Polarities

When programming pulsing polarities, you must set both the On and Off times. The duration, or On time, for an output is determined by time base selected from one of the options in Table 57 on page

77.In other words, there are only four possible On times.

The Off time is calculated by multiplying the On time by a decimal number between 00 and 99. If you want an output to operate for 200 ms every 5 sec, program the time settings as:

On Time: 1

Off Time: 2 5

Table 58: Pulsing Time Settings

On Time

Off Time

Increments

Tolerance

200 ms

200 ms to

200 ms

±200 ms

 

19.8 sec

 

 

1 sec

1 to 99 sec

1 sec

±1 sec

1 min

1 to 99 min

1 min

±1 min

1 hour

1 to 99 hr

1 hr

± hr

16.6One-Shot Polarities

The duration, or On time, of an output is determined by the product of the time base and the multiplier.

If you want an output to operate for 5 sec, program the time settings as:

Time Base: 2

Multiplier: 0 5

The On time is calculated by multiplying the time base setting (1 sec) by the multiplier value (05) (for example, 1 x 05 – 5 sec).

Table 59: One-Shot Time Settings

On Time

Increments

Tolerance

200 ms to 19.8 sec

200 ms

±200 ms

1 to 99 sec

1 sec

±1 sec

1 to

99 min

1 min

±1 min

1 to

99 hr

1 hr

± hour

17.0 System Event Timers

This section covers the features that involve timing, such as Entry and Exit Times, Sensor Watch Time, Siren Run Time, and System Date and Time.

Bosch Security Systems, Inc. 12/08 F01U089457-02

Page 77
Image 77
Bosch Appliances ICP-CC488 manual System Event Timers, Output Timing, Pulsing Polarities, One-Shot Polarities