Bosch Appliances ICP-CC488 manual 2.3ICP-CP500PWMaster Partitioned LED Codepad, Codepad Indicators

Models: ICP-CC488

1 118
Download 118 pages 4.08 Kb
Page 12
Image 12
2.3ICP-CP500PW Master Partitioned LED Codepad

ICP-CC488 Installation Guide 2.0

Codepad Indicators

 

 

EN 12

Section 3.5 to arm the system in STAY Mode 2.

Section 5.1.5 to use the Installer Code to set zones to be automatically isolated in STAY Mode 2.

Section 5.2.6 to use the Master Code to set zones to be automatically isolated in STAY Mode 2.

System Disarmed

This indicator lights with the OFF indicator when the system is disarmed.

MAINS Indicator

The MAINS indicator displays whether the systems AC MAINS supply is normal or failed.

When programming in Installer’s Programming Mode or using a Master Code function, the MAINS indicator lights to indicate a location value from 10 to

15.The MAINS indicator represents the 10 digit, which is added to the value of the lit zone indicator (for example, if the value programmed in a location is 12, the MAINS and Zone 2 indicators light).

Table 9: MAINS Indicator

Indicator

Definition

On

The AC MAINS power normal.

Flashing

The AC MAINS supply failed.

FAULT indicator

The FAULT indicator lights when the system detects a system fault (refer to Table 7 on page 11). Refer to Section 3.12 Fault Analysis Mode on page 18 for more information on system faults.

Each time a new system fault is detected (the FAULT indicator flashes), the codepad beeps once per min. Press [AWAY] to stop the beeping and acknowledge the fault.

Programming Mode

These two indicators flash when you enter Installer’s Programming Mode or use any Master Code function.

Flashing

OFF Indicator/Zone Sealed

The OFF indicator lights when the system is disarmed and flashes when a zone becomes unsealed when disarmed. The indicator stops flashing when all zones are sealed.

ON Indicator/Zone in Alarm

The ON indicator lights when the system is armed and flashes when an alarm occurs. The indicator is reset after a valid User Code is entered.

Audible Indicators

The codepad provides a number of audible indications. Refer to Table 8 on page 11.

2.3ICP-CP500PW Master Partitioned LED Codepad

Figure 3: ICP-CP500PW Master Partitioned Codepad

This codepad is used only on a partitioned ICP-CC488 Control Panel. The Master Partitioned LED codepad allows a user to operate both areas individually from the same codepad, without the need to operate individual areas from separate codepads.

The codepad is the communications interface between you and the alarm system. The codepad allows you to issue commands and offers visual and audible indications to guide you through general operation.

The codepad incorporates a number of indicators: eight zone indicators show the condition of each zone, eight area indicators show the area status, and four other indicators show general status. These indicators are described in the tables throughout this section.

Zone Indicators

The zone indicators (1 to 8) show the status of each zone as defined in Table 3 on page 10. The zones belong to the area with the lit Area Display indicator.

AREA ON/OFF Indicators

The group of four Area On/Off indicators shows the status of each area as defined in Table 10 on page 13.

If an area is armed in STAY Mode 1, the corresponding Area On/Off indicator is lit in conjunction with the PARTIAL indicator. If the area is armed in AWAY Mode, only the ON/OFF indicator is lit.

Bosch Security Systems, Inc. 12/08 F01U089457-02

Page 12
Image 12
Bosch Appliances manual 2.3ICP-CP500PWMaster Partitioned LED Codepad, ICP-CC488| Installation Guide, Codepad Indicators