ICP-CC488 Installation Guide 16.0

Programmable Outputs

 

 

EN 73

1,7 Sensor Watch Alarm

This output operates when the Sensor Watch Count is reached. Refer to Section 14.3.5 Zone Options 1 on page 61 for more information on programming zones for sensor watch. Refer to Section 15.5 Zone Status – Sensor Watch Reports on page 78 for setting the number of days before a zone registers as a faulty sensor watch zone.

1,8 Codepad Medical Alarm

This output operates when a user activates a Codepad Medical Alarm by pressing [7] and [9] at the same time on the remote codepad. This output is reset when a valid User Code is entered at the remote codepad.

1,9 Codepad Fire Alarm

This output operates when a user activates a Codepad Medical Alarm by pressing [4] and [6] at the same time on the remote codepad. This output is reset when a valid User Code is entered at the remote codepad.

1,10 Codepad Panic Alarm

This output operates when a user activates a Codepad Panic Alarm (audible or silent) by pressing either [1] and [3] or [STAY] and [AWAY] at the same time on the remote codepad. This output is reset when a valid User Code is entered at the remote codepad.

1,11 Codepad Duress Alarm

This output operates when a user activates a Duress Alarm by adding a 9 to the end of the User Code used to disarm the system. This output is reset the next time the system is armed.

1,12 Codepad Tamper – Access Denied

This output operates when the wrong code is entered more times than allowed. The number of incorrect attempts allowed is programmed in Location 424 (refer to Section 15.26 System Status – Access Denied on page 69). This output is reset when a valid User Code is entered.

1,13 Speaker Beeps

This output functions during all remote radio or keyswitch operations, which allows you to install a 12 VDC buzzer or light as a status indicator. The identification beeps are defined in Table 55.

Table 55: Horn Speaker Beeps

No of Beeps

System Status

1

System disarmed

2

System armed in AWAY Mode

3

System armed in STAY Mode 1

1,14 Horn Speaker (Output 1 Only)

This output operates only on Output 1. Use this output for one or two 8 Ω horn speakers. Refer to Section 17.9 Siren Run Time and Section 17.10 Siren Sound Rate to program the speaker.

To enable monitoring of the horn speaker, select Option 2 in Location 492 (refer to Section 18.1 System Options 1 on page 80).

1,15 Sirens Running

This output operates for the duration of the Siren Run Time programmed in Location 479 (refer to Section 17.9 Siren Run Time). When the sirens are activated, this output is reset when the Siren Run Time expires. The relay output (Output 4) is set by default for this operation.

2,0 Strobe Operating

This output operates when an alarm occurs and is reset when a valid User Code is entered. The strobe output (Output 3) is set by default for strobe operation and is programmed to reset automatically after 8 hours.

2,1 Silent Alarm

This output operates when any zone programmed to be silent activates. The output is reset when the Siren Run Time expires, an audible alarm is activated, or a valid User Code is entered.

2,2 Alarm When in STAY Mode

This output operates when an audible or silent alarm zone is activated when the system is armed in STAY Mode 1 or STAY Mode 2. The output is reset when the system is disarmed.

2,3 Alarm When in AWAY Mode

This output operates when an audible or silent zone alarm is activated when the system is armed in AWAY Mode. The output is reset when the system is disarmed.

2,4 Mimic System Fault

This output operates without time delays when any system fault occurs, including an AC MAINS supply failure. The output is reset when the system fault or the AC MAINS supply is restored.

2,5 Fire Alarm Resetting

This output operates when a 24-Hour Fire Zone is activated. The output is reset when a valid User Code is entered or when Siren Run Time expires.

2,6 Fire Alarm Latching

This output operates when a 24-Hour Fire Zone is activated and is reset when the system is armed or disarmed.