Alarm Link Software

ICP-CC488 Installation Guide 8.0

Alarm Link Software

 

 

EN 40

If you are required to disable the ability restore the control panel to its default settings, a special procedure eliminates the possibility of accidentally setting this option. You must hold down the default button on the printed circuit board (PCB) when programming this location.

To prevent manually restoring the default control panel settings:

1.Enter the Installer Code (the default is 1234) and press [#] to enter Installer’s Programming Mode. Two beeps sound and the remote codepad displays the data programmed in Location 000. If you are using the remote codepad, the STAY and AWAY indicators flash to indicate you entered Installer’s Programming Mode.

2.Enter [9 0 0 #] to move to Location 900.

3.Press and hold the default button.

The default button is located at the top of the PCB next to the PROGRAMMING KEY socket.

4.Enter [1 5 *] to program 15 into Location 900.

5.Release the default button.

6.Enter [9 6 0 #] to exit from Installer’s Programming Mode.

Two beeps sound and the system returns to the disarmed state.

If you are using a remote codepad, the STAY and AWAY indicators are extinguished to indicate that the system is disarmed.

If Location 900 is not programmed as 15, do one of the following procedures to restore the default control panel settings.

To default the control panel settings using the Installer Code:

1.Enter the Installer Code (the default is 1234) and press [#] to enter Installer’s Programming Mode. Two beeps sound. The STAY and AWAY indicators flash to indicate you entered Installer’s Programming Mode.

2.Enter [9 6 1 #].

Two beeps sound after the default control panel settings are restored.

3.Enter [9 6 0 #].

Two beeps sound. The STAY and AWAY indicators stop flashing and the system returns to the disarmed state.

The control panel default factory settings are restored.

To restore the default control panel settings using the default button:

1.Disconnect the AC MAINS supply and the backup battery from the control panel.

2.Press and hold the default button.

The default button is located at the top of the PCB next to the PROGRAMMING KEY socket.

3.Reconnect the AC MAINS supply to the control panel.

4.Wait 3 to 5 sec and release the default button.

5.Enter [2 5 8 0 *] to disarm the system using the default Master Code.

The control panel default factory settings are restored.

If the option to restore the default control panel settings is disabled using Location 900:

The dialer seize relay (RL2) clicks four times. You must return the control panel to Bosch Security Systems, Inc. for exchange. If the Installer Code is unknown, a service fee is charged to unlock the control panel’s memory

When programmed to disable the default control panel setting, you cannot use the command [961#] to retrieve the programming data.

The use of this feature is not recommended.

8.0Alarm Link Software

You can program or control the ICP-CC488 Control Panel remotely using an IBM or compatible personal computer and the CC816 Alarm Link Software. This software allows you to change your customer’s control panel without leaving your office, which improves customer service and saves you time and money. For locations where a control panel is installed hundreds of kilometers from your office, the Upload/Download feature is invaluable.

When selecting the control panel type during the setup of a new customer database in the Alarm Link Software, the software version number is ICP-CC488 V1.0X and the panel type is I488.

When you add a new customer in the Alarm Link Software, the Subscriber ID Number and the Installer Code must match the values programmed in the control panel for synchronization during connection to the control panel. If these two locations do not match those of the control panel, the computer and the control panel cannot be synchronized.

8.1Remote Connect

The remote connect feature allows you to establish a connection through the telephone network from your IBM or compatible computer to the ICP-CC488 Control Panel. This software allows you to offer faster service to your clients.

8.1.1Remote Connection with Customer Control

If you want to configure the control panel so that a remote connection can be established only when the client initiates it through the remote codepad, program the following information: