17.8Codepad Lockout Time

ICP-CC488 Installation Guide 17.0

System Event Timers

 

 

EN 79

The Sensor Watch Time counter is active only when the control panel is disarmed. If the system is disarmed for 8 hours a day and the Sensor Watch Time is programmed for 1 day, a zone programmed for Sensor Watch registers a Sensor Watch Fault if it is not activated while disarmed within 3 days.

This feature is useful, for example, when someone places objects in the view of a motion detector, which prevents the detector from picking up movement.

To disable Sensor Watch Reports, program Locations 389 and 390 as 0 (refer to Section 15.5 Zone Status – Sensor Watch Reports on page 66).

17.8Codepad Lockout Time

Location 478

0No lockout

1 to 15 Lockout time (increments of 10 sec)

All codepads are locked out for the programmed time if an invalid code is entered more times than allowed by the code retry attempts programmed in Location 424 (refer to Section 15.26 System Status – Access Denied on page 69). If the Codepad Lockout Time is programmed as 0, codepad lockout does not occur.

17.9Siren Run Time

Location 479

Default

5

0

No siren time

1 to 15 Siren time in min

The Siren Run Time determines how long the horn speaker operates during an alarm. You can program the Siren Run Time from 0 to 15 min in 1-min intervals.

17.10 Siren Sound Rate

Location 480

Default 7

0Slowest frequency

15 Fastest frequency

The Siren Sound Rate varies the frequency of the siren tone slowest (0) and to fastest (15). The Siren Sound Rate does not change the frequency of the fire alarm tone.

17.11 Auto Arming Pre-Alert Timer

Location 481

Default 1

0No alert time

1 to 15 Alert time (increments of 5 min)

This location sets the time period during which the control panel warns you it is automatically armed in AWAY Mode. The codepad beeps once every second until the Pre-Alert Timer expires: the system then automatically arms itself in AWAY Mode. If you want the system to automatically arm in STAY Mode 1, enable Option 4 in Location 496 (refer to Section 18.5 Consumer Options 1 on page 82).

After the control panel is automatically armed in AWAY Mode or STAY Mode 1, Exit Time starts. If a valid User Code is entered during the Pre-Alert Time, the Auto Arming Time programmed in Locations 482 to 485 (refer to Section 17.12 Auto Arming Time on page 79) is extended by 1 hour.

If you want a programmable output to operate during the Auto Arming Pre-Alert Time, use Output Event Type 0,5 Auto Arm Pre-Arming Alert Time (refer to page 71).

17.12 Auto Arming Time

Location 482 to 485

 

Location

Default

Hour of the day (tens digit)

482

0

Hour of the day (units digit)

483

0

Minute of the day (tens digit)

484

0

Minute of the day (units digit)

485

0

These locations specify the time of day the system automatically arms itself in AWAY Mode. Set this time in 24-hour format (for example, program 10:30 PM as 2230). If you want the system to arm in STAY Mode 1, select Option 4 in Location 496 (refer to Section 18.5 Consumer Options 1on page 82).

If forced arming is disabled for any zone, the automatic arming feature operates regardless of whether any zones are unsealed. Refer to Section

14.3.7Zone Options 2 on page 63 for more information on programming zones for forced arming.

User Code 16 is reported when this feature is used.

For partitioned ICP-CC488 Control Panels, both areas are automatically armed in AWAY Mode at the same time each day.

17.13 Auto Disarming Time

Location 486 to 489

 

Location

Default

Hour of the day (tens digit)

486

0

Hour of the day (units digit)

487

0

Minute of the day (tens digit)

488

0

Minute of the day (units digit)

489

0

These locations specify the time of day the system automatically disarms itself. Set this time in 24-hour format (for example, program 10:30 PM as 2230).

User Code 16 is reported when this feature is used.

Bosch Security Systems, Inc. 12/08 F01U089457-02