ICP-CC488 Installation Guide 16.0

Programmable Outputs

 

 

EN 72

0,12 Entry Warning + Day Alarm Resetting

This output combines Entry Warning and Day Alarm Resetting so that either of these two events activates the output.

If the output is activated by Entry Timer 1, Entry Timer 2, or Entry Guard Timer for STAY Mode, the output is reset when the Entry Time expires or the system is disarmed.

If a zone programmed for Day Alarm is activated when the system is disarmed, the output is reset when the zone is resealed. You can turn Day Alarm on and off by holding down [4]. Refer to Section 14.1 Day Alarm Information for programming zones to operate for Day Alarm.

0,13 Exit Warning + Entry Warning + Day Alarm Resetting

This output operates when the system is armed, regardless of whether zones are sealed or unsealed, until Exit Time expires.

The output operates again during Entry Time and is reset when Entry Time expires or the system is disarmed. The output also operates during the Entry Guard Timer for STAY Mode time.

If a zone programmed for day alarm is activated when the system is disarmed, the output is reset when the zone is resealed. You can turn Day Alarm on and off by holding down [4]. Refer to Section 14.1 Day Alarm Information for programming zones to operate for Day Alarm.

0,14 Day Alarm Resetting

This output operates when a zone programmed for Day Alarm is activated. The output is reset when the Day Alarm zone is resealed. You can turn Day Alarm on and off by holding down [4]. Refer to Section 14.1 Day Alarm Information for programming zones to operate for Day Alarm.

0,15 Day Alarm Latching

This output operates when a zone programmed for Day Alarm is activated. The output is reset by pressing [AWAY]. You can turn Day Alarm on and off by holding down [4]. Refer to Section 14.1 Day Alarm Information on page 56 for programming zones to operate for Day Alarm.

If the ICP-CC488 Control Panel is partitioned, pressing [AWAY] on a CP5 Area Addressable codepad other than the one to which the zone is allocated, or pressing [AWAY] on a CP5 Master Partitioned Codepad does not reset the output. You can reset only this output on the area codepad to which the zone is allocated.

1,0 Day Alarm Enabled

This output operates when Day Alarm is enabled. The output is reset when Day Alarm is turned off. Refer to Section 14.1 Day Alarm Information on page 56 for programming zones to operate for Day Alarm.

You can turn Day Alarm on and off by holding down [4]. Three beeps indicate that Day Alarm is turned on, two beeps indicate that Day Alarm is turned off. Refer to Section 5.4.7 Turning Day Alarm On and Off on page 33 for more information.

1,1 Telephone Line Fail

This output operates when the built-in telephone line fault module detects that the telephone line is disconnected longer than 40 sec. The output is reset when the telephone line is restored continuously for 40 sec. This output does not operate unless Option 1 in Location 176 is selected (refer to Section 11.11 Telephone Line Fault Options on page 52).

1,2 Kiss-off Received

This output operates after the control panel successfully transmitted to the receiving party.

1,3 AUX Power Supply Fail

This output operates when either the 1 A codepad AUX power supply or the 1 A accessories AUX power supply fails. The output is reset when the faulty AUX power supply is reset.

1,4

AC Fail

This output operates when the AC MAINS fails. The output is reset when the AC MAINS is restored. This output operates regardless of whether Option 2 in Location 494 is selected (refer to Section 18.3 System Options 3 on page 81).

1,5 Low Battery

This output operates when a Dynamic Battery Test detects the battery failed or the battery voltage is below 11.2 VDC. The Dynamic Battery Test is performed every 4 hours after the system is powered up and every time the system is armed.

This output is reset only after a Dynamic Battery Test reports that the backup battery voltage is normal.

1,6 Horn Speaker Monitor Fail

If the Enable Monitoring of Horn Speaker option (2) in Location 492 is selected (refer to Section 18.1 System Options 1 on page 80), this output operates when the horn speaker is disconnected. The output is reset when the horn speaker is reconnected.

Bosch Security Systems, Inc. 12/08 F01U089457-02

Page 72
Image 72
Bosch Appliances ICP-CC488 Exit Warning + Entry Warning + Day Alarm Resetting, Day Alarm Enabled, Telephone Line Fail