Bosch Appliances manual ICP-CC488| Installation Guide, Programming Sheets, En

Models: ICP-CC488

1 118
Download 118 pages 4.08 Kb
Page 102
Image 102
Manual background
Refer to page 52
0

ICP-CC488 Installation Guide 25.0

Programming Sheets

 

 

EN 102

Transmission Format for Receiver 2

Location

073

Refer to page 50

1

Contact ID

 

2

4 + 2 express

 

3

FSK 300 baud

 

4

Domestic

 

5

Basic pager

 

6

Reserved

 

7

Reserved

 

8

Reserved

 

The Basic Pager option supports only eight zones due to protocol limitations. If you use more than eight zones, this option is not recommended.

If you use the Zone 16, the 4 + 2 Express and FSK 300 Baud formats are not recommended because Zone 16 will be assigned as "0" and some receivers will not support this zone.

Subscriber ID Number For Receiver 2

Location

074 to 079

Refer to page 50

Default

0 0 0 0 0 0

Dialing Format

Location

080

Refer to page 50

1Australian DTMF (5 digits/sec)

2 Australian decadic

3 Alternate DTMF and Australian decadic

4 International DTMF

5 Reversed decadic

6 Alternate DTMF and reversed decadic

Reserved

Location 081 to 112

Telco Arming Sequence

Location

113 to 142

Refer to page 50

Default

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

 

 

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Telco Disarming Sequence

Location

143 to 158

Refer to page 51

Default

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Callback Telephone Number

Location

159 to 174

Refer to page 51

Default

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Ring Count

Location

175

Refer to page 51

Default

 

8

0

Panel will not answer

 

1 to 13

Number of rings until panel answers

14

Answering machine bypass 2

15

Answering machine bypass 1

Telephone Line Fault Options

Location 176

Default

1Display FAULT indicator if telephone line fails

2Sound alarm when system is armed if telephone line fails

4Sound alarm when system is disarmed if telephone line fails

8Reserved

Dialer Options 1

Location

 

177

 

Refer to page 52

1Dialer reporting functions allowed

2 Remote arming by telephone

4 Answering machine bypass only when armed

8Use Bell 103 for FSK format (disabled – CCITT v21)

Dialer Options 2

Location

 

178

 

Refer to page 53

Default

0

1Open/Close Reports only after alarm

2Open/Close Reports in STAY Mode allowed

4 Delay siren until transmission complete

8 Extend wait for handshake from 30 sec to 60 sec

Dialer Options 3

Location

 

179

 

Refer to page 53

Default

2

1Set DTMF dialing pulses to 1 digit/sec

2 Lockout telephone line fail alarm

4 Change decadic dialing to 60/40

8 Reserved

Alarm Link Options

Location

 

180

 

Refer to page 41

1Upload/download allowed

2Callback phone number required for upload/download

4Exit upload/download connection on alarm

8 Reserved

Bosch Security Systems, Inc. 12/08 F01U089457-02