3.9Codepad Fire Alarm

ICP-CC488 Installation Guide 3.0

System Operations

 

 

EN 17

3.9Codepad Fire Alarm

An audible codepad Fire Alarm activates when a user presses [4] and [6] on the remote codepad simultaneously. A distinct fire sound emits through the horn speaker to indicate this type of alarm. The fire sound is different than the burglary sound.

Select Option 2 in Location 493 to program the codepad Fire Alarm as silent (refer to Section 18.2 System Options 2 on page 81). To disable the codepad Fire Alarm Report, program Locations 407 and 408 to 0 (refer to Section 15.17 Codepad Fire Report). A codepad Fire Alarm transmits a Contact ID Event Code 110 to a base station receiver.

3.10Codepad Medical Alarm

An audible codepad Medical Alarm activates when a user presses [7] and [9] simultaneously.

Select Option 4 in Location 493 to program codepad Medical Alarm as silent (refer to Section 18.2 System Options 2 on page 81). To disable reporting of the codepad Medical Alarm Report, program Locations 409 and 410 to 0 (refer to Section 15.18 Codepad Medical Report). A codepad Medical Alarm transmits a Contact ID Event Code 100 to a base station receiver.

3.11Isolating Zones

Isolating zones allows you to manually disable one or more zones before arming the system in AWAY Mode, STAY Mode 1, or STAY Mode 2. When a zone is isolated, access is allowed into that zone when the system is armed without activating an alarm.

For example, you might want to isolate a zone before arming the system because a zone passive infrared (PIR) detector is activating false alarms or because you need to leave a pet inside a particular zone while you are away.

You can isolate zones using one of two methods. One method requires a valid User Code and the other does not. The ability to isolate zones is determined by the priority level assigned to each User Code holder. Some User Code holders cannot isolate zones. Refer to Section 13.3 User Code Priority for more information. By default, the standard isolation method is used.

Zones that are manually isolated using this method transmit a Zone Bypass Report (Contact ID Event Code 570) for each isolated zone when the system is armed. A Zone Bypass Restore Report is transmitted when the system is disarmed.

When you select a 24-Hour Burglary Zone to be isolated, a Contact ID Event Code 572 is sent. If you select a 24-Hour Fire Zone to be isolated, a Contact ID Event Code 571 is sent.

3.11.1Standard Isolating

Standard isolating allows any operator to isolate zones because no code is required.

1.Press [STAY] twice.

Three beeps sound and the STAY indicator flashes.

2.Enter the number of the zone to be isolated and press [STAY].

The indicator for the zone flashes.

24-Hour zones are automatically isolated as soon as you press [STAY]. All other Burglary Zones are automatically isolated only after the system is armed.

3.Repeat Step 2 for each zone you want to isolate.

As each zone is selected to be isolated, the corresponding zone indicator flashes. If you make a mistake, enter the incorrect zone number and press [STAY]. This zone is no longer selected to be isolated and the zone indicator is extinguished.

4.Press [AWAY].

Two beeps sound and the system returns to the disarmed state.

The indicators for the selected zones continue to flash until the next time the system is disarmed.

Example

To manually isolate zones 1, 3, and 4, press:

[STAY][STAY][1][STAY][3][STAY][4][STAY]

[AWAY]

3.11.2Code to Isolate

The code to isolate method permits only those User Code holders with a priority level that includes Code to Isolate. The standard isolating method is disabled for any User Code with this priority level set.

1.Press [STAY].

2.Enter your code and press [STAY].

Three beeps sound and the STAY indicator flashes.

If you attempt to enter isolating mode with a User Code that is not set for Code to Isolate, the system ignores the attempt.

3.Enter the number of the zone to be isolated and press [STAY].

The indicator for the zone flashes.

24-Hour zones are automatically isolated as soon you press [STAY]. All other Burglary zones are automatically isolated only after the system is armed.

4.Repeat Step 3 for each zone you want to isolate.

As each zone is selected to be isolated, the corresponding zone indicator flashes. If you make a mistake, enter the incorrect zone number and press [STAY]. This zone is no longer selected to be isolated and the zone indicator is extinguished.