ICP-CC488 Installation Guide 10.0

Dialer Reporting Formats

 

 

EN 44

Table 39: Contact ID Format Breakdown

Subscriber ID

 

 

 

 

 

Number

Qualifier

Event Code

Group Number

Point ID Number

SSSS

Q

 

XYZ

GG

CCC

Four-digit

Event Qualifier, which provides

Event Code

Group Number

Point ID Number

Subscriber ID

specific event information:

(comprised of three

(comprised of two

(comprised of

Number

1

– New event or opening

hex digits)

hex digits)

three hex digits)

 

3

– New restore or closing

 

 

 

10.1.2Contact ID Format

Contact ID Format can identify hundreds of protection zones by their unique codes. This format provides a single-digit Event Qualifier and a three- digit Event Code that quickly identifies the reported condition.

In general, Contact ID Format is very simple because most of the Event Codes and Point ID Codes are predefined. The base station software usually can identify an alarmed zone by its Point ID Code and usually pays little attention to the Event Code.

Refer to Section 10.1.3 Alarm Link Options for more information about the ICP-CC488 Point ID Codes.

10.1.3Point ID Codes

Table 43 on page 46 shows the different Point ID Codes and Event Codes transmitted to the base station receiver when using Contact ID Reporting Format. All Event Codes are fixed. The control panel always transmits the same code because there are no programming locations to change the codes.

10.1.44 + 2 Reporting Format

The 4 + 2 Express Format reports a Subscriber ID Number followed by an Expansion Code. The reporting Channel Number is transmitted directly after the Expansion Code.

Table 40: Example Reporting in 4 + 2 Format

Table 41: 4 + 2 Reporting Format

New Event

4 + 2 Report

Alarm

SSSS ACH

Trouble

SSSS TCH

Bypass

SSSS BCH

AC Fail

SSSS EAC

Low Battery

SSSS LLB

Opening Report

SSSS OU

Closing Report

SSSS CU

Test Report

SSSS TE

Program Altered

SSSS P0

Duress

SSSS DD0

Event

4 + 2 Report

Alarm Restore

SSSS R CH

Trouble Restore

SSSS TR CH

Bypass Restore

SSSS BR CH

AC Fail Restore

SSSS ER ACR

Low Battery

SSSS L LB

Low Battery Restore

SSSS LBR

Panic

SSSS P PCH

Subscriber ID

Expansion

Channel

Number

Code

Number

SSSS

A

CH

Bosch Security Systems, Inc. 12/08 F01U089457-02

Page 44
Image 44