ICP-CC488 Installation Guide 14.0

Zone Information

 

 

EN 56

Master Code Functions

The user has access to all Master Code functions. Refer to Section 5.2 Master Code Functions on page 26 for more information.

14.0Zone Information

14.1Day Alarm Information

Location 265

Default 0

1 Zone 1

2 Zone 2

4Zone 3

8 Zone 4

This location has four programming options. You can select any combination of the options by programming a single value. Calculate this value by adding the option bit numbers together. Refer to Section 7.3 Programming Option Bits on page 36 for more information.

Day Alarm allows some zones to be monitored when the system is disarmed. Indications are available at any of the programmable outputs, including the codepad buzzer. This function accommodates latching and non-latching Day Alarm Output Event Types.

When the system is armed in AWAY Mode, STAY Mode 1, or STAY Mode 2, zones programmed as Day Alarm Zones activate the sirens and dialer just as non-Day Alarm Zones do. When Day Alarm is activated, it ignores any zone Pulse Count settings programmed for that zone (that is, the zone Pulse Count is only relevant when the system is armed).

Example

You can set up a Day Alarm at the front door of a shop with a pressure mat or electronic beam that is activated when a customer enters the shop. When a customer walks on the pressure mat or breaks the electronic beam, the codepad buzzer beeps.

14.1.1Day Alarm Resetting

An output that is programmed for Day Alarm Resetting operates when a zone programmed for Day Alarm is activated. The output is reset after the zone is resealed. This occurs only when the system is disarmed. Refer to Output Event Type 0,14 Day Alarm Resetting on page 72 for more information.

14.1.2Day Alarm Latching

An output that is programmed for Day Alarm Latching operates when a zone programmed for Day Alarm is activated. The zone indicator and the latching output resets when [AWAY] is pressed. This occurs only when the system is disarmed. Refer to Output Event Type 0,15 Day Alarm Latching on page 72 for more information.

14.1.3Day Alarm Operation

If a zone is programmed for Day Alarm, the zone can be isolated in the normal way so that it does not register as a Day Alarm Zone when the system is disarmed. You can use only Zones 1 to 4 as Day Alarm Zones.

You can program the STAY indicator to indicate whether Day Alarm is turned on or off by selecting Option 8 in Location 496 (refer to Section 18.5 Consumer Options 1 on page 82). When Day Alarm is on, the STAY indicator flashes once every 3 sec.

You can program an output to mimic a zone for monitoring Zones 5 to 8. Refer to Section 16.2 Output Event Types on page 71 for more information on the Output Event Types that you can program.

To turn Day Alarm on:

Press and hold [4] until three beeps sound.

To turn Day Alarm off:

Press and hold [4] until two beeps sound.

14.2EOL Resistor Value

Location 266

0No EOL

11K (brown, black, red)

2 1K5 (brown, green, red)

3 2K2 (red, red, red)

4 3K3 (orange, orange, black, brown) 1%

5 3K9 (orange, white, red)

6 4K7 (yellow, violet, red)

7 5K6 (green, blue, red)

8 6K8 (blue, grey, black, brown) 1%

9 10K (brown, black, orange)

10 12K (brown, red, orange)

11 22K (red, red, orange)

12 Reserved

13 Reserved

14 Split EOL (3K3/6K8) with tamper (1K)

15 Split EOL 1% resistors

You can program the control panel for different end- of-line (EOL) resistor values. This is a global parameter that affects all zones simultaneously. This feature allows you to install the ICP-CC488 Control Panel at an existing site without changing the EOL resistors. This feature also increases the security of the system because eleven possible EOL resistor values can be used, which makes it extremely difficult to tamper with the system.

Bosch Security Systems, Inc. 12/08 F01U089457-02