5.8 - Demand limit
Generally, demand limit is used by an energy management system in order to restrict the unit electricity consumption.
The
•By reference to a limiting signal from a
•By reference to an external
Whatever the method used, demand limit is active in all operating types: Local, Remote or CCN. However, in Local operating type, demand limit can be disabled with keypad commands (see section 4.3.3) and in CCN operating type, demand limit can be controlled directly with the aid of CCN commands.
NOTE: A limitation value of 100% means that the unit may call upon the full array of its capacity stages.
Here is an example of demand limit by an external
Demand limit by 0-10 V d.c. signal
|
| No demand limit |
Maximum permitted | capacity | Total demand limit |
| ||
|
|
5.9 - Capacity control
This function activates the compressors and capacity unloaders to keep the entering or leaving water temperature at its setpoint. The precision with which this is achieved depends on
the capacity of the water loop, the flow rate, the load, and the number of stages available on the unit.
The control system continuously takes account of the tempera- ture error with respect to the setpoint, as well as the rate of change in this error and the difference between entering and leaving water temperatures, in order to determine the optimum moment at which to add or withdraw a capacity stage.
NOTE: If the same compressor undergoes too many starts (per hour) this automatically brings about reduction of compressor starts, which makes leaving water temperature control less precise.
5.10 - Determining the lead circuit
This function commands the start/stop sequence of the two refrigerant circuits called A and B. The circuit authorised to start first is the lead circuit. Three methods can be configured by the user in the Configuration menu:
•Auto mode: the control system determines the lead circuit so as to equalise the number of starts on each circuit (value weighted by the operating times of each circuit). Thus, the circuit with the least number of starts is always given precedence to start. The lead circuit is stopped last. This function is only available in
NOTE: If one circuit has more unloaders than the other, this circuit is always the lead circuit, independent of the configuration and the operating hours of the two circuits.
•Circuit A as leader: Circuit A is always the lead circuit. It is the first to start and the last to stop.
•Circuit B as leader: Circuit B is always the lead circuit. It is the first to start and the last to stop. This choice is only available in
5.11 - Circuit loading sequence
Two circuit loading sequences are available. The choice of sequence can be configured by the user in the Configuration menu (see section 4.5.7.3). This function is only available in
•Balanced circuit loading: If this sequence is selected, the control system tries to keep the capacity of circuits A and B equal as the total load on the unit increases or decreases.
•Loading with priority given to one circuit: If this sequence is selected, the control system loads the lead circuit completely before the second circuit starts up. When there is a demand limit, the second circuit is unloaded first.
NOTE: If the unit is
29