4.5.5 - Description of the Inputs menu
INPUTS MENU [2]
ITEM | FORMAT | UNITS | COMMENTS |
0 | OPEn/CLoS | - | Remote contact 1 status |
|
|
| This contact is used to start (contact closed) and stop (contact open) the chiller. It is only valid, if the unit is in the remote operating |
|
|
| control (rEM) mode. |
|
|
|
|
1 | OPEn/CLoS | - | Remote contact 2 status |
|
|
| This contact is used to select a cooling only setpoint, if the unit is in cooling mode and in the remote operating control (rEM) type. |
|
|
| Contact open = csp1 |
|
|
| Contact closed = csp2 |
2[1] | OPEn/CLoS | - | Remote contact 3 status |
|
|
| This contact is used to select the heating or cooling mode, only if the unit is in the remote operating control type. |
|
|
| Contact open: unit in cooling mode |
|
|
| Contact closed: unit in heating mode |
3[3] | OPEn/CLoS | - | Remote contact 4 status |
|
|
| This contact is used to select the second condensing setpoint or the heat reclaim mode (for a heat reclaim unit), only if the unit is in |
|
|
| the remote operating control type. |
|
|
| Contact open = unit uses the normal condensing setpoint and is in normal mode (no heat reclaim) |
|
|
| Contact closed = unit uses the heat reclaim setpoint and is in heat reclaim mode. |
4 | OPEn/CLoS | - | Remote contact 5 status* |
|
|
| If this contact is closed, it permits limiting the unit demand, based on the demand limit setpoint, if the demand limit method by |
|
|
| contact has been selected. |
5 | OPEn/CLoS | - | Water flow and customer interlock control contact status* |
|
|
| Opening of this contact shuts the unit off or prevents its |
6[1] | OPEn/CLoS | - | Water pump operation status. If the contact opens when the evaporator pump has received a command to operate, this trips a |
|
|
| pump failure alarm. |
7[1] | OPEn/CLoS | - | Condenser water flow control. Controls the condenser water circulation. |
8[1] | OPEn/CLoS | - | Control box thermostat and phase reversal interlock status*. Opening of this contact shuts the unit off or prevents its |
|
|
| and generates an alarm. |
|
|
|
|
9[1] | nn.n | - | External |
|
|
| limit function of the unit. |
|
|
|
|
Legend
1This item is displayed in certain unit configurations only
2Access to this menu is
*Active in all operating types See section 3.4
4.5.6 - Description of the Outputs/Tests menu
4.5.6.1 - General
This menu displays the status of the controller outputs. More- over, when the machine is fully stopped (LOFF) the outputs can be activated for manual or automatic tests (the access to the tests is password controlled).
4.5.6.2 - Menu description
OUTPUTS STATUS AND TESTS MENU [2] [3]
ITEM FORMAT UNITS | DESCRIPTION. |
0 | Compressor status |
-b1 = compressor A1
-b2 = compressor A2
-b3 = compressor A3
-b4 = compressor A4
This item permits display of the compressor status in circuit A. It also permits independent testing. In test mode the direction arrows permit successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation of each output.
1 [1] | Compressor status |
-b1 = compressor B1
-b2 = compressor B2
-b3 = compressor B3
-b4 = compressor B4
This item permits display of the compressor status in circuit B. It also permits independent testing. In test mode the direction arrows permit successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation of each output.
2 [1] | tEST | Capacity reduction status, circuits A & B | |
| - | b1 = capacity reduction A1 | |
| - | b2 | = capacity reduction B1 |
|
| This item permits display of the capacity reduction status in circuit A. It also permits independent testing. | |
3 [1] | tESt | Fan contactor status/test, circuit A | |
| - | b1 | = fan contactor assembly 1 |
| - | b2 | = fan contactor assembly 2 |
| - | b3 | = fan contactor assembly 3 |
| - | b4 | = fan contactor assembly 4 |
This item permits display of the fan stages. It also permits independent testing. In test mode the direction arrows permit successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation of each output.