3.4 - User connections

3.4 - User connections

The connections below are available at the customer’s terminal block. Some of them can only be used in special operating modes. For further details see the sections that describe the functions (section 5) and the configurations (section 4.2.1).

NOTE: The bridge between terminals 32, 63 and 65 on the customer’s terminal block must not be removed.

CONNECTION BLOCK

DESCRIPTION

CONNECTOR/CHANNEL

TERMINAL

DESCRIPTION

REMARKS

Alarm relay output, circuit A

J3 / CH24

30A - 31A

Indicates alarms in circuit A

Volt-free contacts 24 V a.c. 48

Alarm relay output, circuit B

J3 / CH25

30B - 31B

Indicates alarms in circuit B

V d.c. max, 20 V a.c. or V

d.c., 3 A max, 80 mA min,

 

 

 

 

 

 

 

 

external power supply.

 

 

 

 

Connector: 6 pin WAGO

 

 

 

 

231-306/026000 pitch 5.08.

User safety loop and chilled water

J4 / CH15a

34 - 35

This contact is mounted in series with the water flow

24 V a.c., 20 mA

pump interlock

 

 

control contact. It can be used for any user safety loop

 

 

 

 

that requires that the unit is shut down, if it is open. The

Connector: 10 pin WAGO

 

 

 

chilled water pump operation auxiliary contact is

734-110, pitch 3.5

 

 

 

connected between these two terminals.

 

 

 

 

 

 

Remote start/stop

J4 / CH11

32 - 33

The remote start/stop command is only used if the unit is

 

 

 

 

under remote operation control (rEM). See section 4.2.1.

 

Remote cooling setpoint selection

J4 / CH12

65 - 66

The remote cooling setpoint selection command is only

 

 

 

 

used if the unit is under remote operation control (rEM).

 

 

 

 

See section 4.2.1.

 

Remote heating/cooling control

J4 / CH13

63 - 64

The remote heating/cooling control command is only used

 

 

 

 

if the unit is under remote operation control (rEM). See

 

or

 

 

section 4.2.1.

 

 

 

 

 

 

remote heat reclaim control

J4 / CH13

63 - 64

The command allows selection of the second condensing

 

 

 

 

setpoint or of the heat reclaim mode. It is only used if the

 

 

 

 

unit is under remote operation control (rEM). See section

 

 

 

 

4.2.1.

 

Demand limit command

J4 / CH14

73 - 74

This contact permits activating the unit demand limit

 

 

 

 

function. See section 5.8. This contact is active, whatever

 

 

 

 

the operating type.

 

 

 

 

 

 

0-10 V d.c. setpoint reset or

J8 / CH10

71 - 72

This 0-10 V d.c. input is used for setpoint reset or unit

Connector: 2 pin WAGO 231-

demand limit entry

 

 

demand limit. It is active, whatever the unit operating type.

302/026000 pitch 5.08

 

 

 

This 0-10 V signal can be supplied by a user command or

 

 

 

 

a 0-10 V temperature sensor.

 

Connection to CCN

J12

1 - 2 - 3

A RS-485 bus is used for connection to the CCN.

Use of a shielded cable (max.

 

 

 

The CCN connector is located on the CCN/clock board

length: 1000 m)

 

 

 

(inserted on the PD4 Basic Board)

Shielding: braiding on 95% -

 

 

 

- Pin 1: signal +

100% of the cable surface.

 

 

 

- Pin 2: ground

Shielding connection at the

 

 

 

- Pin 3: signal -

two cable ends.

AVAILABLE TERMINALS

 

 

 

 

 

 

Description

Connector/

Terminal

Description

 

channel

 

 

 

 

 

 

Condenser water flow

J5/CH17

 

This contact is used to detect lack of condenser water flow and

switch input

 

 

shuts down the unit.

 

 

 

 

Evaporator 1 and 2 pump

J5/CH18

 

This contact is used to detect an evaporator pump operation

operation input

 

 

fault and switches over to the other evaporator pump*.

Evaporator 1 control

J2/CH19

 

This contact permits control of evaporator 1 pump by the unit*.

Evaporator 2 control

J2/CH20

 

This contact permits control of evaporator 2 pump by the unit*.

Condenser pump control

J2/CH21

 

This contact permits control of condenser pump by the unit*.

 

 

 

 

Remarks

24 V a.c - 20mA

24 V a.c. internal supply.

Max. consumption

-each output: 20 VA/10W

-for all 3: 40 VA/20 W if all are used

Legend

*Associated functions, if selected: automatic changeover, pump 1 and 2; manual or CCN selection; periodical; by default.

9

Page 9
Image 9