3.4 - User connections
The connections below are available at the customer’s terminal block. Some of them can only be used in special operating modes. For further details see the sections that describe the functions (section 5) and the configurations (section 4.2.1).
NOTE: The bridge between terminals 32, 63 and 65 on the customer’s terminal block must not be removed.
CONNECTION BLOCK
DESCRIPTION | CONNECTOR/CHANNEL | TERMINAL | DESCRIPTION | REMARKS | |
Alarm relay output, circuit A | J3 / CH24 | 30A - 31A | Indicates alarms in circuit A |
| |
Alarm relay output, circuit B | J3 / CH25 | 30B - 31B | Indicates alarms in circuit B | V d.c. max, 20 V a.c. or V | |
d.c., 3 A max, 80 mA min, | |||||
|
|
|
| ||
|
|
|
| external power supply. | |
|
|
|
| Connector: 6 pin WAGO | |
|
|
|
| ||
User safety loop and chilled water | J4 / CH15a | 34 - 35 | This contact is mounted in series with the water flow | 24 V a.c., 20 mA | |
pump interlock |
|
| control contact. It can be used for any user safety loop |
| |
|
|
| that requires that the unit is shut down, if it is open. The | Connector: 10 pin WAGO | |
|
|
| chilled water pump operation auxiliary contact is | ||
|
|
| connected between these two terminals. |
| |
|
|
|
|
| |
Remote start/stop | J4 / CH11 | 32 - 33 | The remote start/stop command is only used if the unit is |
| |
|
|
| under remote operation control (rEM). See section 4.2.1. |
| |
Remote cooling setpoint selection | J4 / CH12 | 65 - 66 | The remote cooling setpoint selection command is only |
| |
|
|
| used if the unit is under remote operation control (rEM). |
| |
|
|
| See section 4.2.1. |
| |
Remote heating/cooling control | J4 / CH13 | 63 - 64 | The remote heating/cooling control command is only used |
| |
|
|
| if the unit is under remote operation control (rEM). See |
| |
or |
|
| section 4.2.1. |
| |
|
|
|
|
| |
remote heat reclaim control | J4 / CH13 | 63 - 64 | The command allows selection of the second condensing |
| |
|
|
| setpoint or of the heat reclaim mode. It is only used if the |
| |
|
|
| unit is under remote operation control (rEM). See section |
| |
|
|
| 4.2.1. |
| |
Demand limit command | J4 / CH14 | 73 - 74 | This contact permits activating the unit demand limit |
| |
|
|
| function. See section 5.8. This contact is active, whatever |
| |
|
|
| the operating type. |
| |
|
|
|
|
| |
J8 / CH10 | 71 - 72 | This | Connector: 2 pin WAGO 231- | ||
demand limit entry |
|
| demand limit. It is active, whatever the unit operating type. | 302/026000 pitch 5.08 | |
|
|
| This |
| |
|
|
| a |
| |
Connection to CCN | J12 | 1 - 2 - 3 | A | Use of a shielded cable (max. | |
|
|
| The CCN connector is located on the CCN/clock board | length: 1000 m) | |
|
|
| (inserted on the PD4 Basic Board) | Shielding: braiding on 95% - | |
|
|
| - Pin 1: signal + | 100% of the cable surface. | |
|
|
| - Pin 2: ground | Shielding connection at the | |
|
|
| - Pin 3: signal - | two cable ends. |
AVAILABLE TERMINALS |
|
| |
|
|
|
|
Description | Connector/ | Terminal | Description |
| channel |
|
|
|
|
|
|
Condenser water flow | J5/CH17 |
| This contact is used to detect lack of condenser water flow and |
switch input |
|
| shuts down the unit. |
|
|
|
|
Evaporator 1 and 2 pump | J5/CH18 |
| This contact is used to detect an evaporator pump operation |
operation input |
|
| fault and switches over to the other evaporator pump*. |
Evaporator 1 control | J2/CH19 |
| This contact permits control of evaporator 1 pump by the unit*. |
Evaporator 2 control | J2/CH20 |
| This contact permits control of evaporator 2 pump by the unit*. |
Condenser pump control | J2/CH21 |
| This contact permits control of condenser pump by the unit*. |
|
|
|
|
Remarks
24 V a.c - 20mA
24 V a.c. internal supply.
Max. consumption
-each output: 20 VA/10W
-for all 3: 40 VA/20 W if all are used
Legend
*Associated functions, if selected: automatic changeover, pump 1 and 2; manual or CCN selection; periodical; by default.
9