5.3 - Evaporator water pump control | 5.5 - Control interlock contact |
The unit can control one or two evaporator water pumps. The evaporator water pump is turned on when this option is confi- gured (see User configuration) and when the unit is in one of the on modes described above or in delay mode. Since the minimum value for the delay at
The pump is kept running for 20 seconds after the unit goes to stop mode. The pump keeps working when the unit switches from heating to cooling mode or
The pump can be started in particular operating conditions when the evaporator heater is active. See section 5.19 for the particular evaporator pump control for the follower unit (master/slave assembly). If two pumps are controlled and the reversing function has been selected (see User 1 configuration), the control tries to limit the pump run time delta to the configured pump
The control provides a means to automatically start the pump each day at 14.00 hours for 2 seconds when the unit is off. If the unit is fitted with two pumps, the first pump is started on odd days and the second pump is started on even days. Starting the pump periodically for few seconds increases the
NOTE: If this function is used, there should not be any chilled water pump interlock between terminals 34 and 35 (see section 3.4).
5.4 - Condenser water pump control
Only available on
The condenser pump can be controlled by two modes, depend- ing on the configuration (only accessible by Carrier Service).
1 - Control based on unit start/stop control. In this case it is controlled in the same way as the evaporator pump.
2 - Control based on compressor status. In this case the pump is activated at the same time as the first compressor. It only switches off when no compressor is activated.
This contact can control the status of the water loop. Its function is to prevent unit
5.6 - Evaporator heater control
The evaporator heater can be activated to protect an evaporator that may be damaged by ice, if the unit is shut down for a long period at low outdoor air temperature. If the heater is not sufficient to increase the water temperature, the evaporator pump can be started.
NOTE: The evaporator heater control parameters may be modified using the Service Configuration menu.
5.7 - Control point
Control point represents the leaving water temperature that the unit must produce.
•In cooling mode: control point = active setpoint + reset
•In heating mode: control point = active setpoint - reset
5.7.1 - Active setpoint
Two setpoints can be selected as active in cooling mode. Usually, the second setpoint is used for unoccupied periods or for ice storage (medium or low brine unit). A single setpoint is available in heating mode.
Depending on the current operating mode, the active setpoint can be selected with the operating type selector button, or with the user’s
5.7.2 - Reset
Reset means that the active setpoint is modified so that less machine capacity is required (in cooling mode, the setpoint is increased, in heating mode it is decreased). This modification is in general a reaction to a drop in the load. For the
In both cases the reset parameters, i.e. slope, source and maxi- mum value, are configurable in the Setpoints menu (see section 4.5.4). Reset is a linear function based on three parameters.
•A reference at which reset is zero (outdoor temperature or delta T - no reset value).
•A reference at which reset is maximum (outdoor temperature or delta T - full reset value).
•The maximum reset value.
28