4.5.1 - Description of the Information menu
INFORMATION MENU [3]
ITEM | FORMAT | UNITS | DESCRIPTION | |
0 |
|
| Automatic display mode. It cycles through the following displays: | |
| ±nn.n | °C | 1: | Controlled water temperature: temperature of the water that the unit tries to maintain at the control point. |
|
|
| 2: | Unit operating type |
| LOFF | - |
| Local Off |
| - |
| Local On | |
| - |
| Local On - based on unit clock. | |
| CCn | - |
| CCN Control. |
| rEM | - |
| Remote Control |
| MASt | - |
| Master unit |
|
|
| 3: | Unit status |
| OFF | - |
| Off: Unit is stopped and not authorised to start. |
| rEADY | - |
| Ready: Unit is authorised to start |
| dELAY | - |
| Delay: Unit is in delay at |
|
|
|
| configured in the User Configuration menu. |
| StOPPing | - |
| Stopping: Unit is currently stopping. |
| running | - |
| On: Unit is running or authorised to start. |
| triPout | - |
| Fault shutdown. |
| OvErridE | - |
| Limit: The operating conditions do not allow total unit operation. |
|
|
| 4. | Unit occupied/unoccupied status |
| OCCUPIEd | - |
| Occupied: Unit in occupied mode |
| UNOCCUPIEd - |
| Unoccupied: Unit in unoccupied mode | |
|
|
| 5. | Heating/cooling operating mode |
| COOL | - |
| Cooling: Unit operates in cooling mode |
| HEAT | - |
| Heating: Unit operates in heating mode |
| rECLAIM | - |
| Cooling: Unit is in auto cooling and heat reclaim demand is active |
|
|
| 6. | Alarm mode |
| ALArM | - |
| Alarm: Unit is totally stopped because of failure. |
| ALErt | - |
| Alert: Unit is in failure but not completely stopped. |
|
|
| 7. | Master/Slave status |
| MAStEr | - |
| Master: The master/slave control is active and the unit is the master |
| SLAvE | - |
| Slave: The master/slave control is active and the unit is the slave |
|
|
|
| |
1 [1] | nn | - | Active mode codes. Each active mode is displayed in turn. This Item is masked when nil. Pressing the enter button when a mode code | |
|
|
| is displayed causes a character text expansion to be scrolled accross the | |
|
|
|
| |
2 [2] |
| - | This item indicates the current chiller occupied/unoccupied mode. | |
| occu |
| Occupied | |
| unoc |
| Unoccupied | |
| Forc |
| The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN. | |
3 | nn.n | minutes | ||
|
|
| has been switched on. The delay can be configured in the User Configuration 1 menu. | |
|
|
|
| |
4 [2] |
| - | Heating/cooling on selection: This item is accessible in read/write, if the unit is in local control mode. It is only displayed, if the unit is | |
|
|
| in LOFF, | |
| HEAt | - | Heating mode selection | |
| COOL | - | Cooling mode selection | |
5 [2] |
|
| Heat reclaim mode selection: This item is accessible in read/write, if the unit is in local control mode. It is only displayed, if the unit is | |
|
|
| in LOFF, | |
| YES | - | Heat reclaim mode selection, use of heat reclaim condensing setpoint. | |
| NO | - | Normal cooling mode selection, use of standard condensing setpoint | |
|
|
|
| |
6 | Nnn | % | Total active capacity of unit. | |
|
|
|
| |
7 | nnn | % | Total active capacity of circuit A. | |
|
|
|
| |
8 [2] | nnn | % | Total active capacity of circuit B. | |
|
|
|
| |
9 [2] | nnn |
| Present demand limit. This is the authorised operating capacity of the unit. See section 5.8. | |
| Forc | % | The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN. | |
10 | nnn | % | Present lag chiller demand limit. Displayed when the master/slave control is selected. | |
11 [2] |
| - | Setpoint select in local mode. This point is read/write accessible. Displayed only when the unit is LOFF, | |
|
| |||
|
| |||
| AUtO |
| AUtO = active setpoint depends on schedule 2 (setpoint selection schedule). See section 5.7.1 & 4.5.7.6. | |
|
|
|
| |
12 [2] |
| - | Setpoint occupied mode. | |
| occu |
| Occupied: cooling setpoint 1 is active | |
| unoc |
| Unoccupied: cooling setpoint 2 is active | |
| Forc |
| The value shall be displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN. | |
13 | ±nn.n | °C | Active setpoint. This is the current cooling/heating setpoint: it refers to cooling/heating setpoint 1 or 2. | |
14 | ±nn.n |
| Control point. This is the setpoint used by the controller to adjust the temperature of the leaving or entering water (according to | |
| Forc | °C | configuration). | |
|
|
| Control point = active setpoint + reset. See section 5.7 | |
|
|
| The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN. | |
|
|
|
| |
15 | ±nn.n | °C | Controlled water temperature. Water temperature that the unit tries to maintain at the control point. | |
|
|
|
| |
16 | ±nn.n | °C | Condensing setpoint. The value is displayed in turn with 'Forc' if the unit is in CCN mode and this parameter is forced by CCN. | |
| Forc | °C |
|
|
17 | n |
| Heat reclaim function indicator, circuit A (see heat reclaim section) | |
18 | n |
| Heat reclaim function indicator, circuit B (see heat reclaim section) |
Legend
1This item is masked when nil.
2This item is displayed in certain unit configurations only.
3Access to this menu is
15