DESCRIPTION OF OPERATING MODES (ITEM 1 OF THE INFORMATION MENU)

MODE # MODE NAME

DESCRIPTION

7

Delay at start-up active

The delay at start-up operates after the unit has been switched on. If the delay has not expired, the mode is active.

 

 

The delay is configured in the User1 configuration menu.

8

2nd cooling setpoint active

The second cooling setpoint is active. See section 5.7.1

9

Setpoint reset active

In this mode, the unit uses the reset function to adjust the leaving or entering water temperature setpoint. See

 

 

section 5.7.2.

10

Demand limit active

In this mode, the capacity at which the unit is allowed to operate is limited. See section 5.8.

11

Ramp loading active

Ramp loading is active. In this mode, the controlled high or low water temperature value (in °C/min) in heating mode

 

 

is limited to a preset value in order to prevent compressor overload. The ramp function must be configured (see

 

 

User1 configuration menu). The ramp values can be modified (see setpoint menu).

12

Low entering water temperature

The unit is in heating mode and the temperature of the evaporator leaving water is lower than the lesser of the two

 

protection in heating mode

cooling setpoints. A capacity stage is removed. This mode only applies to heat pumps.

13,14

Low suction temperature protection

13 = circuit A & 14 = circuit B. Protection for evaporator suction low temperature circuit is active. In this mode, circuit

 

 

capacity is not authorised to rise if the unit is in cooling mode, and saturated suction temperature in the circuit is

 

 

lower by more than 13°C at the leaving chilled water and lower than the frost protection threshold.

15,16

Low discharge superheat protection

15 = circuit A & 16 = circuit B.

 

 

In this mode the circuit capacity is shut down by pumpout and not allowed to restart, when the low superheat alarm

 

 

conditions are satisfied. During the shutdown/start-up sequence, mode 15 or 16 is active. See descriptions for

 

 

alarms 48 and 49.

17,18

High pressure protection

17 = circuit A & 18 = circuit B. The circuit is in high pressure protection mode because the HP protection threshold

 

 

has been exceeded. The circuit capacity is not authorised to rise and any slave compressor can be stopped in order

 

 

to prevent a high pressure break.

 

 

 

19,20

Not used

 

 

 

 

21

Heat reclaim active

Circuit A or circuit B operates in heat reclaim mode and not in standard cooling mode (pumpdown phase is

 

 

activated).

 

 

 

22

Evaporator heater active

Mode active if risk of frost exists.

 

 

 

23

Evaporator pump reversal active

Two evaporator water pumps installed on the unit and pump reversal is active. See section 5.3

 

 

 

24

Periodic evaporator pump start-up

The unit is shut down and is started every day at 14:00 hours for 2 seconds. This function must be configured in the

 

 

User1 menu. See sections 5.3 and 4.5.7.3.

 

 

 

25

Low night-time capacity

Unit capacity is limited. The period when this mode starts, as well as the limited capacity in night-time mode are

 

 

controlled in Client1 menu.

26

Unit under SM control

Unit is under control of a System Manager (FSM or CSM III).

27

Master/slave link active

Unit is connected to a secondary unit by a master slave link and either:

 

 

- the unit is configured as a master and this master is operating, or

 

 

- the unit is configured as a slave and this slave is operating.

 

 

 

4.5.2 - Description of the Temperatures menu

TEMPERATURES MENU [2]

ITEM

FORMAT UNITS

COMMENTS

0

±nn.n

°C

Evaporator entering water temperature

 

 

 

 

1

±nn.n

°C

Evaporator leaving water temperature

 

 

 

 

2[1]

±nn.n

°C

Condenser entering water temperature

 

 

 

 

3[1]

±nn.n

°C

Condenser leaving water temperature

 

 

 

 

4[1]

±nn.n

°C

Reclaim condenser entering water temperature

 

 

 

 

5[1]

±nn.n

°C

Reclaim condenser leaving water temperature

 

 

 

 

6

±nn.n

°C

Saturated discharge temperature circuit A

 

 

 

 

7

±nn.n

°C

Saturated suction temperature circuit A

 

 

 

 

8

±nn.n

°C

Suction temperature compressor A1

 

 

 

 

9

±nn.n

°C

Superheat circuit A

 

 

 

 

10[1]

±nn.n

°C

Saturated discharge temperature circuit B

 

 

 

 

11[1]

±nn.n

°C

Saturated suction temperature circuit B

 

 

 

 

12[1]

±nn.n

°C

Suction temperature compressor B1

 

 

 

 

13[1]

±nn.n

°C

Superheat circuit B

 

 

 

 

14[1]

±nn.n

°C

Outdoor temperature

 

 

 

 

15[1]

±nn.n

°C

Water loop temperature, master/slave assembly

 

 

 

 

Legend

1This item is displayed in certain unit configurations only

2Access to this menu is read-only.

4.5.3 - Description of the Pressures menu

PRESSURES MENU [2]

ITEM

FORMAT

UNITS

COMMENTS

0

nnnn

kPa

Discharge pressure circuit A

 

 

 

 

1

nnnn

kPa

Suction pressure circuit A

 

 

 

 

2

nnnn

kPa

Differential oil pressure compressor A1

3

nnnn

kPa

Discharge pressure circuit B

4

nnnn

kPa

Suction pressure circuit B

 

 

 

 

5

nnnn

kPa

Differential oil pressure compressor B1

 

 

 

 

6[1]

nnnn

kPa

Differential oil pressure compressor A2

7[1]

nnnn

kPa

Differential oil pressure compressor A3

8[1]

nnnn

kPa

Differential oil pressure compressor A4

 

 

 

 

9[1]

nnnn

kPa

Differential oil pressure compressor B2

 

 

 

 

10[1]

nnnn

kPa

Differential oil pressure compressor B3

11[1]

nnnn

kPa

Differential oil pressure compressor B4

12[1]

nnnn

kPa

Pumpdown pressure, heat reclaim, circuit A

 

 

 

 

13[1]

nnnn

kPa

Pumpdown pressure, heat reclaim, circuit B

 

 

 

 

Legend

1This item is displayed in certain unit configurations only.

2Access to this menu is read-only

16

Page 16
Image 16
Carrier 30GK Description of the Temperatures menu, Description of the Pressures menu, Pressures Menu Format Units Comments

30GK specifications

The Carrier 30GK is a prominent chiller model known for its efficiency and reliability in various commercial and industrial applications. Offering a blend of advanced technology and robust design, the 30GK series caters to diverse cooling needs while maintaining energy efficiency and low operational costs.

One of the standout features of the 30GK is its use of the latest scroll compressor technology. This contributes to its efficient performance, enabling the chiller to operate at optimal levels while minimizing energy consumption. The scroll compressor is known for its quiet operation, which reduces noise pollution, making it an ideal choice for buildings located in noise-sensitive environments.

The 30GK chiller series is equipped with microchannel coil technology, which allows for improved heat exchange efficiency. The microchannel design uses a compact coil structure that enhances refrigerant flow and reduces refrigerant volume, leading to a smaller footprint compared to traditional coil designs. This innovative design not only saves space but also improves the chiller's overall performance.

Another notable characteristic of the Carrier 30GK is its environmental consciousness. The chiller operates using environmentally friendly refrigerants, aligning with modern regulations and sustainability goals. Its design incorporates energy-efficient components that contribute to significant reductions in greenhouse gas emissions, making it suitable for environmentally responsible projects.

Moreover, the 30GK is designed for easy serviceability, with accessible components that simplify maintenance. This feature is particularly important for facility managers seeking to minimize downtime and keep maintenance costs low. The chiller also includes advanced monitoring and control systems, which enable real-time performance tracking and diagnostics, enhancing operational efficiency.

In terms of performance, the 30GK chiller is known for its wide capacity range, making it versatile for various applications. Whether for commercial spaces, industrial processes, or large buildings, the 30GK can meet the cooling demands reliably.

Overall, the Carrier 30GK chiller represents a perfect balance of cutting-edge technology, energy efficiency, and sustainability. Its features make it a leading choice in the market, suited for those looking to invest in high-quality and dependable cooling solutions.