OUTPUTS STATUS 2 AND TESTS MENU [2] [3] - cont.

ITEM

FORMAT

UNITS

DESCRIPTION

4 [1]

tESt

-

 

Fan contactor status/test, circuit B

 

 

-

 

b1 = fan contactor assembly 1

 

 

-

 

b2 = fan contactor assembly 2

 

 

 

 

b3 = fan contactor assembly 3

 

 

 

 

b4 = fan contactor assembly 4

 

 

 

 

This item permits display of the fan stages. It also permits independent testing. In test mode the direction arrows permit

 

 

 

 

successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation of each output.

5

tESt

 

 

Alarm command status/test

 

 

-

 

b1 = alarm circuit A

 

 

-

 

b2 = alarm circuit B

 

 

 

 

In test mode the direction arrows permit successive display of 01 and 10, so as to in turn force authorisation of each alarm

 

 

 

 

output.

6

tESt

%

 

EXV position, circuit A

 

 

 

 

In the test mode the direction arrows permit forcing the valve to its fully open position.

7

tESt

%

 

EXV position, circuit B

 

 

 

 

In the test mode the direction arrows permit forcing the valve to its fully open position.

8 [1]

tESt

%

 

Variable speed fan, circuit A or condenser water valve position in %

 

 

 

 

 

9 [1]

tESt

%

 

Variable speed fan, circuit B or condenser water valve position in %

 

 

 

 

 

10

On

-

 

Evaporator water pump No. 1 command status. Not displayed if unit does not control a pump.

 

Stop

-

 

On: the pump operates

 

tESt

-

 

Stop: the pump has stopped

 

FAIL

-

 

Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump

 

Good

-

 

without delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it is

 

Forc

-

 

then immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with 'Forc' if its

 

 

 

 

status is forced by CCN.

 

 

 

 

During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display

 

 

 

 

appears:

 

 

 

 

- Fail: displayed if the test has failed, because the pump is not started

 

 

 

 

- Good: displayed if the test succeeds

11

On

-

 

Evaporator water pump No. 2 command status. Not displayed if unit does not control a pump.

 

OFF

-

 

On: the pump operates

 

tESt

-

 

Stop: the pump has stopped

 

FAIL

-

 

Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump

 

Good

-

 

without delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it is

 

Forc

-

 

then immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with 'Forc' if its

 

 

 

 

status is forced by CCN.

 

 

 

 

During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display

 

 

 

 

appears:

 

 

 

 

- Fail: displayed if the test has failed, because the pump is not started

 

 

 

 

- Good: displayed if the test succeeds

12

On

-

 

Condenser pump status/test

 

OFF

-

 

On: the pump operates

 

tESt

 

 

Stop: the pump has stopped

 

FAIL

 

 

Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump

 

Good

 

 

without delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it is

 

Forc

 

 

then immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with 'Forc' if its

 

 

-

 

status is forced by CCN.

 

 

 

 

During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display

 

 

 

 

appears:

 

 

 

 

- Fail: displayed if the test has failed, because the pump is not started

 

 

 

 

- Good: displayed if the test succeeds

 

 

 

 

 

13[1]

nn

 

 

Evaporator heater and heat reclaim condenser status

 

 

-

 

b1 = evaporator heater

 

 

-

 

b2 = heat reclaim condenser heater

 

 

 

 

 

14[1]

tESt

%

 

Condenser water valve position in heat reclaim mode

 

 

 

 

 

15[1]

 

 

 

Solenoid valve status/test, heat reclaim function

 

 

-

 

b1 = heat reclaim coil shutoff solenoid valve, circuit A

 

 

-

 

b2 = heat reclaim coil drain solenoid valve, circuit A

 

 

-

 

b3 = heat reclaim coil shutoff solenoid valve, circuit B

 

 

-

 

b4 = heat reclaim coil drain solenoid valve, circuit B

 

 

 

 

In test mode the direction arrows permit successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation

 

 

 

 

of each output.

16

YES

 

 

Used only for local interface

 

no

 

 

Cause all diodes and blocks to light up or flash, to verify that they are operating correctly

 

tESt

 

 

 

 

 

 

 

 

Legend

1This item is displayed in certain unit configurations only

2A test is only possible if the units are in local off mode and if all compressors have stopped

3The password is only valid for the test. 'Test' is displayed during the test, alternating with the item number