OUTPUTS STATUS 2 AND TESTS MENU [2] [3] - cont.

ITEM

FORMAT

UNITS

DESCRIPTION

4 [1]

tESt

-

 

Fan contactor status/test, circuit B

 

 

-

 

b1 = fan contactor assembly 1

 

 

-

 

b2 = fan contactor assembly 2

 

 

 

 

b3 = fan contactor assembly 3

 

 

 

 

b4 = fan contactor assembly 4

 

 

 

 

This item permits display of the fan stages. It also permits independent testing. In test mode the direction arrows permit

 

 

 

 

successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation of each output.

5

tESt

 

 

Alarm command status/test

 

 

-

 

b1 = alarm circuit A

 

 

-

 

b2 = alarm circuit B

 

 

 

 

In test mode the direction arrows permit successive display of 01 and 10, so as to in turn force authorisation of each alarm

 

 

 

 

output.

6

tESt

%

 

EXV position, circuit A

 

 

 

 

In the test mode the direction arrows permit forcing the valve to its fully open position.

7

tESt

%

 

EXV position, circuit B

 

 

 

 

In the test mode the direction arrows permit forcing the valve to its fully open position.

8 [1]

tESt

%

 

Variable speed fan, circuit A or condenser water valve position in %

 

 

 

 

 

9 [1]

tESt

%

 

Variable speed fan, circuit B or condenser water valve position in %

 

 

 

 

 

10

On

-

 

Evaporator water pump No. 1 command status. Not displayed if unit does not control a pump.

 

Stop

-

 

On: the pump operates

 

tESt

-

 

Stop: the pump has stopped

 

FAIL

-

 

Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump

 

Good

-

 

without delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it is

 

Forc

-

 

then immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with 'Forc' if its

 

 

 

 

status is forced by CCN.

 

 

 

 

During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display

 

 

 

 

appears:

 

 

 

 

- Fail: displayed if the test has failed, because the pump is not started

 

 

 

 

- Good: displayed if the test succeeds

11

On

-

 

Evaporator water pump No. 2 command status. Not displayed if unit does not control a pump.

 

OFF

-

 

On: the pump operates

 

tESt

-

 

Stop: the pump has stopped

 

FAIL

-

 

Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump

 

Good

-

 

without delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it is

 

Forc

-

 

then immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with 'Forc' if its

 

 

 

 

status is forced by CCN.

 

 

 

 

During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display

 

 

 

 

appears:

 

 

 

 

- Fail: displayed if the test has failed, because the pump is not started

 

 

 

 

- Good: displayed if the test succeeds

12

On

-

 

Condenser pump status/test

 

OFF

-

 

On: the pump operates

 

tESt

 

 

Stop: the pump has stopped

 

FAIL

 

 

Forc: This item is only displayed if the unit is in local off mode (LOFF). Selecting this item permits energising the pump

 

Good

 

 

without delay and for an unlimited period. The pump continues to operate, until any key on the user interface is pressed: it is

 

Forc

 

 

then immediately switched off. If the unit is in CCN control mode, the pump status is displayed alternately with 'Forc' if its

 

 

-

 

status is forced by CCN.

 

 

 

 

During the test phase, pump supply is energised for 10 seconds only. When the test has finished, the following display

 

 

 

 

appears:

 

 

 

 

- Fail: displayed if the test has failed, because the pump is not started

 

 

 

 

- Good: displayed if the test succeeds

 

 

 

 

 

13[1]

nn

 

 

Evaporator heater and heat reclaim condenser status

 

 

-

 

b1 = evaporator heater

 

 

-

 

b2 = heat reclaim condenser heater

 

 

 

 

 

14[1]

tESt

%

 

Condenser water valve position in heat reclaim mode

 

 

 

 

 

15[1]

 

 

 

Solenoid valve status/test, heat reclaim function

 

 

-

 

b1 = heat reclaim coil shutoff solenoid valve, circuit A

 

 

-

 

b2 = heat reclaim coil drain solenoid valve, circuit A

 

 

-

 

b3 = heat reclaim coil shutoff solenoid valve, circuit B

 

 

-

 

b4 = heat reclaim coil drain solenoid valve, circuit B

 

 

 

 

In test mode the direction arrows permit successive display of 0001, 0010, 0100 and 1000, so as to in turn force authorisation

 

 

 

 

of each output.

16

YES

 

 

Used only for local interface

 

no

 

 

Cause all diodes and blocks to light up or flash, to verify that they are operating correctly

 

tESt

 

 

 

 

 

 

 

 

Legend

1This item is displayed in certain unit configurations only

2A test is only possible if the units are in local off mode and if all compressors have stopped

3The password is only valid for the test. 'Test' is displayed during the test, alternating with the item number

19

Page 19
Image 19
Carrier 30GK manual Format Units Description

30GK specifications

The Carrier 30GK is a prominent chiller model known for its efficiency and reliability in various commercial and industrial applications. Offering a blend of advanced technology and robust design, the 30GK series caters to diverse cooling needs while maintaining energy efficiency and low operational costs.

One of the standout features of the 30GK is its use of the latest scroll compressor technology. This contributes to its efficient performance, enabling the chiller to operate at optimal levels while minimizing energy consumption. The scroll compressor is known for its quiet operation, which reduces noise pollution, making it an ideal choice for buildings located in noise-sensitive environments.

The 30GK chiller series is equipped with microchannel coil technology, which allows for improved heat exchange efficiency. The microchannel design uses a compact coil structure that enhances refrigerant flow and reduces refrigerant volume, leading to a smaller footprint compared to traditional coil designs. This innovative design not only saves space but also improves the chiller's overall performance.

Another notable characteristic of the Carrier 30GK is its environmental consciousness. The chiller operates using environmentally friendly refrigerants, aligning with modern regulations and sustainability goals. Its design incorporates energy-efficient components that contribute to significant reductions in greenhouse gas emissions, making it suitable for environmentally responsible projects.

Moreover, the 30GK is designed for easy serviceability, with accessible components that simplify maintenance. This feature is particularly important for facility managers seeking to minimize downtime and keep maintenance costs low. The chiller also includes advanced monitoring and control systems, which enable real-time performance tracking and diagnostics, enhancing operational efficiency.

In terms of performance, the 30GK chiller is known for its wide capacity range, making it versatile for various applications. Whether for commercial spaces, industrial processes, or large buildings, the 30GK can meet the cooling demands reliably.

Overall, the Carrier 30GK chiller represents a perfect balance of cutting-edge technology, energy efficiency, and sustainability. Its features make it a leading choice in the market, suited for those looking to invest in high-quality and dependable cooling solutions.