3 - HARDWARE DESCRIPTION
3.1 - General
Control board
The various control components are arranged in modules within the control cabinet:
• | Control module: This comprises the basic board, the |
| user interface, the EXV control board and option boards, |
| as well as the customer’s terminal block. |
9
2
• |
1
3
8 | 4 |
|
Legend | 7 | 6 | 5 |
|
|
|
1CCN connector
2Red LED, status of the board
3Green LED, communication bus SIO
4Orange LED, communication bus CCN
5Remote master board customer control connection contacts
6Remote master board customer control connection signal
7Remote master board customer report connection contacts
8Master PD4 basic board
9CCN/clock board
The control system consists of at least a PD4 basic board, a user interface, a
The CCN/clock board is connected and screwed to the master basic board. It permits communication with elements of the Carrier Comfort Network via the CCN bus.
| compressor protection boards, as well as the compressor |
| circuit breakers and contactors. |
• | Fan module |
| 4xDO boards together with the fan circuit breakers and |
| contactors. |
3.2 - Electronic boards
3.2.1 - The basic board
It can be used alone or in conjunction with slave boards. It holds the program that controls the machine. It continuously manages the information coming in from the various pressure and temperature sensors, and communicates with the slave boards via the SIO bus. It can also communicate with elements of the Carrier Comfort Network via the CCN bus.
NOTE: After a power cut the unit restarts in the same operating mode as before the power cut.
3.2.2 - Slave boards
•Compressor board RCPM: This board is used to control a compressor. Up to eight RCPM boards can be connected to the basic board.
•4xDO board: This board can be used to control fan stages.
•
•
•
Control box
Legend | 3 | Compressor | |
1 | Power supply disconnect switch | 4 | Control system |
2 | Fan | 5 | User interface |